Operation Panel
Indication
Name
Communication fault (inverter)
This function stops the inverter output when communication error occurs consecutively for more than
permissible retry count when a value other than "9999" is set in Pr. 335 RS-485 communication retry count
Description
during RS-485 communication from the RS-485 terminals. This function also stops the inverter output if
communication is broken for the period of time set in Pr. 336 RS-485 communication check time interval.
Check point
Check the RS-485 terminal wiring.
Corrective action
Perform wiring of the RS-485 terminals properly.
Operation Panel
Indication
Name
Analog input fault
Stops the inverter output when a 30mA or higher current or a 7.5V or higher voltage is input to terminal
Description
2 while the current input is selected by Pr.73 Analog input selection, or to terminal 4 while the current
input is selected by Pr.267 Terminal 4 input selection.
Check point
Check the setting of Pr. 73 Analog input selection and Pr. 267 Terminal 4 input selection. (Refer to page 185.)
Either give a frequency command by current input or set Pr. 73 Analog input selection or Pr. 267 Terminal
Corrective action
4 input selection to voltage input.
Operation Panel
Indication
Name
PID signal fault
If any of PID upper limit (FUP), PID lower limit (FDN), and PID deviation limit (Y48) turns ON during PID
control, inverter shuts off the output. This function is active under the following parameter settings: Pr.554 PID
signal operation selection ≠ "0,10", Pr.131 PID upper limit ≠ "9999", Pr.132 PID lower limit ≠ "9999", and Pr.553 PID
Description
deviation limit ≠ "9999". This protective function is not active in the initial setting (Pr.554 = "0", Pr.131 = "9999",
Pr.132 = "9999", Pr.553 = "9999").
· Check if the measured PID value is greater than the upper limit (Pr.131) or smaller than the lower limit
Check Point
(Pr.132).
· Check if the absolute PID deviation value is greater than the limit value (Pr.553).
Make correct settings for Pr.131 PID upper limit, Pr.132 PID lower limit, Pr.553 PID deviation limit.
Corrective Action
261
)
Operation Panel
Indication
Name
Internal circuit fault
Description
Trips when an internal circuit error occurred.
Corrective action
Please contact your sales representative.
CAUTION
• If protective functions of E.ILF, E.SOT, E.PTC, E.PE2, E.CDO, E.IOH, E.SER, E.AIE, E.PID are activated when using the FR-
PU04, "Fault 14" appears.
Also when the faults history is checked on the FR-PU04, the display is "E.14".
• If faults other than the above appear, contact your sales representative.
E.SER
E.AIE
E.PID
E.13
Causes and corrective actions
FR-PU04
Fault 14
FR-PU07
VFD Comm error
FR-PU04
Fault 14
FR-PU07
Analog in error
FR-PU04
Fault 14
Fault
FR-PU07
PID Signal Error
FR-PU04
Fault 13
FR-PU07
(Refer to page
5
321