Motor noise, EMI measures, mechanical resonance

4.16 Motor noise, EMI measures, mechanical resonance

Purpose
Reduction of the motor noise
Measures against EMI and leakage currents
Reduction of the motor noise
Measures against EMI and leakage currents
Reduce mechanical resonance

4.16.1 Carrier frequency and Soft-PWM selection under general-purpose motor

control (Pr. 72, Pr. 240, Pr. 260)
You can change the motor sound.
Parameter
Name
Number
PWM frequency
72 *
selection
Soft-PWM operation
240 *
selection
PWM frequency
260
automatic switchover
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201.)
* This parameter allows its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write selection.
(1) PWM carrier frequency changing (Pr. 72)
⋅ You can change the PWM carrier frequency of the inverter.
Changing the PWM carrier frequency produces an effect on avoiding the resonance frequency of a mechanical system or
motor or on EMI measures or on leakage current reduction caused by the PWM switching.
⋅ When using an option sine wave filter (MT-BSL/BSC) for the 75K or higher, set "25"(2.5kHz) in Pr. 72.
(2) Soft-PWM control (Pr. 240)
⋅ Soft-PWM control is a control method that changes the motor noise from a metallic tone into an unoffending
complex tone.
(3) PWM carrier frequency automatic reduction function (Pr. 260)
⋅ If continuous operation is performed at 85% or higher of the rated inverter current (the value in the parenthesis on
page 346) with Pr.260 = "1 (initial setting)" and Pr.72 ≥ "3 (inverter carrier frequency is set to 3kHz is higher)," E.THT
(Inverter overload trip) is likely to occur. To avoid that, the carrier frequency is automatically lowered to as low as
2kHz. (Motor noise increases, but not to the point of failure.)
⋅ When Pr. 260 is set to"0", the carrier frequency becomes constant (Pr. 72 setting) independently of the load, making
the motor sound uniform.
Note that continuous operation should be performed at less than 85% of the inverter rating.
CAUTION
⋅ Decreasing the PWM carrier frequency is effective on EMI measures and on leakage current reduction, but increases motor
noise.
⋅ When PWM carrier frequency is set to 1kHz or less (
operation due to increase in ripple currents, resulting in insufficient torque. In such case, set fast-response current limit
operation invalid using
Pr.156
♦ Parameters referred to ♦
Pr.156 Stall prevention operation selection
182
Carrier frequency and Soft-PWM
selection under general-purpose motor
control
Carrier frequency and Soft-PWM
selection under IPM motor control
Speed smoothing control
Initial
Setting Range
Value
55K or
lower
2
75K or
higher
1
1
Pr.72
Stall prevention operation selection.
Refer to page 91
Parameter that must be Set
S
S
S
V/F
V/F
V/F
MFVC
MFVC
MFVC
< V / F > < S MF V C >
PWM carrier frequency can be changed. The setting
0 to 15
displayed is in [kHz]. Note that 0 indicates 0.7kHz, 15
indicates 14.5kHz and 25 indicates 2.5kHz.
0 to 6, 25
(25 is exclusively for a sine wave filter.)
0
Soft-PWM is invalid
When Pr. 72 = "0 to 5" (
1
PWM is valid.
PWM carrier frequency is constant independently of
load.
0
When the carrier frequency is set to 3kHz or more (Pr.
72 ≥ "3"), perform continuous operation at less than
85% of the rated inverter current.
Decreases PWM carrier frequency automatically when
1
load increases.
≤1), fast-response current limit may function prior to stall prevention
Refer to
Page
Pr. 72, Pr. 240, Pr. 260
Pr. 72, Pr. 240, Pr. 260
Pr. 653, Pr. 654
Description
"
"
0 to 4
for 75K or higher), soft-
182
183
184