400V class (when input power supply is 440V)
Terminal
Tightening
Applicable
Screw
Inverter Model
Size
*4
FR-F740P-0.75K
M4
to 3.7K
FR-F740P-5.5K
M4
FR-F740P-7.5K
M4
FR-F740P-11K
M4
FR-F740P-15K
M5
FR-F740P-18.5K
M5
FR-F740P-22K
M6
FR-F740P-30K
M6
FR-F740P-37K
M6
FR-F740P-45K
M8
FR-F740P-55K
M8
FR-F740P-75K
M8
FR-F740P-90K
M10
FR-F740P-110K
M10
FR-F740P-132K
M10
FR-F740P-160K
M10
FR-F740P-185K
M12 (M10)
FR-F740P-220K
M12 (M10)
FR-F740P-250K
M12 (M10)
FR-F740P-280K
M12 (M10)
FR-F740P-315K
M12 (M10)
FR-F740P-355K
M12 (M10)
FR-F740P-400K
M12 (M10)
FR-F740P-450K
M12 (M10)
FR-F740P-500K
M12 (M10)
FR-F740P-560K
M12 (M10)
*1
For the FR-F740P-55K or lower, the recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with continuous
maximum permissible temperature of 75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
For the FR-F740P-75K or higher, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cross-linked polyethylene insulated
cable)) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 50°C or less and wiring is performed
in an enclosure.
*2
For the FR-F740P-45K or lower, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of
75°C. Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the FR-F740P-55K or higher, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of
90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the United States.)
*3
For the FR-F740P-45K or lower, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of
70°C. Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the FR-F740P-55K or higher, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of
90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the Europe.)
*4
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
A screw for earthing (grounding) of the 185K or higher is indicated in ( ).
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
Crimping
(Compression)
Terminal
Torque
R/L1,
R/L1,
N·m
U, V, W
S/L2,
S/L2,
T/L3
T/L3
1.5
2-4
2-4
2
1.5
2-4
2-4
2
1.5
5.5-4
5.5-4
3.5
1.5
5.5-4
5.5-4
5.5
2.5
8-5
8-5
8
2.5
14-5
8-5
14
4.4
14-6
14-6
14
4.4
22-6
22-6
22
4.4
22-6
22-6
22
7.8
38-8
38-8
38
7.8
60-8
60-8
60
7.8
60-8
60-8
60
14.7
60-10
60-10
60
14.7
80-10
80-10
80
14.7
100-10 100-10
100
14.7
150-10 150-10
125
24.5
150-12 150-12
150
24.5
100-12 100-12 2×100 2×100 2×100
46
100-12 100-12 2×100 2×100 2×125
46
150-12 150-12 2×125 2×125 2×125
46
150-12 150-12 2×150 2×150 2×150
46
200-12 200-12 2×200 2×200 2×200
46
C2-200 C2-200 2×200 2×200 2×200
46
C2-250 C2-250 2×250 2×250 2×250
46
C2-250 C2-250 2×250 2×250 3×200
46
C2-200 C2-200 3×200 3×200 3×200
1000
Main circuit terminal specifications
Cable Sizes
2
AWG/MCM
HIV, etc. (mm
)
*1
R/L1,
Earthing
U, V, W
P/+, P1
S/L2,
cable
T/L3
2
2
2
14
2
3.5
3.5
12
3.5
3.5
3.5
12
5.5
5.5
8
10
8
8
8
8
14
14
14
22
14
22
22
14
22
22
14
38
38
22
60
60
22
1/0
60
60
38
1/0
60
80
38
3/0
80
100
38
3/0
100
100
38
4/0
125
150
38
250
150
2×100
38
300
38
2×4/0
38
2×4/0
38
2×250 2×250 2×120 2×120
60
2×300 2×300 2×150 2×150
60
2×350 2×350 2×185 2×185
60
2×400 2×400 2×185 2×185
60
2×500 2×500 2×240 2×240 2×120
100
2×500 2×500 2×240 2×240 2×120
100
3×350 3×350 3×185 3×185 2×150
PVC, etc. (mm
*2
R/L1,
Earthing
U, V, W
U, V, W
S/L2,
T/L3
14
2.5
2.5
14
2.5
2.5
12
4
4
10
6
6
8
8
10
10
6
8
16
10
6
6
16
16
4
4
25
25
4
4
25
25
1
2
50
50
1/0
50
50
1/0
50
50
3/0
50
50
3/0
70
70
4/0
95
95
250
120
120
300
150
150
2×4/0
2×95
2×95
2×4/0
2×95
2×95
2
)
*3
cable
2.5
4
4
10
10
16
16
16
16
25
25
25
25
35
50
70
95
95
95
120
150
2×95
2×95
2
21