Installation of the inverter and
enclosure design
1.4.2

Cooling system for inverter enclosure

From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps,
resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature
lower than the permissible temperatures of the in-enclosure equipment including the inverter.
The cooling systems are classified as follows in terms of the cooling calculation method.
1) Cooling by natural heat dissipation from the enclosure surface (Totally enclosed type)
2) Cooling by heat sink (Aluminum fin, etc.)
3) Cooling by ventilation (Forced ventilation type, pipe ventilation type)
4) Cooling by heat exchanger or cooler (Heat pipe, cooler, etc.)
Cooling System
Natural ventilation
(Enclosed, open type)
Natural
cooling
Natural ventilation
(Totally enclosed type)
Heatsink cooling
Forced
Forced ventilation
cooling
Heat pipe
1.4.3

Inverter placement

(1) Installation of the inverter
Installation on the enclosure
30K or lower
10
Enclosure Structure
INV
INV
heatsink
INV
INV
Heat
pipe
INV
37K or higher
Fix six positions for the FR-F740P-
185K to 400K and fix eight positions
for the FR-F740P-450K to 560K.
Comment
Low in cost and generally used, but the enclosure size
increases as the inverter capacity increases. For
relatively small capacities.
Being a totally enclosed type, the most appropriate for
hostile environment having dust, dirt, oil mist, etc. The
enclosure size increases depending on the inverter
capacity.
Having restrictions on the heatsink mounting position
and area, and designed for relative small capacities.
For general indoor installation. Appropriate for
enclosure downsizing and cost reduction, and often
used.
Totally enclosed type for enclosure downsizing.
CAUTION
When encasing multiple inverters, install them in parallel as
a cooling measure. Install the inverter vertically.
*Refer to the clearances on the next page.
Vertical
*