System 6: Multi-Boiler Cascade I - Buderus Logamax plus GB162 Applications Manual

Gas condensing boiler
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

GB162 Applications Manual

3.6 System 6: Multi-boiler Cascade I

Summary:
Multi-boiler system with staging control and many options for
heat distribution.
MCM10 Staging control each for 2 to 4 boilers and a
maximum of 16 boilers per system
Boiler rotation based on hours run time
Different options for input of heat demand:
- AM10 outdoor reset controller
- 0-10V input for output power control (boiler modulation)
- 0-10V input for supply water temperature control
- Dry contact input
- RC35 outdoor reset control with room influence
Buderus offers convenient racking systems and low loss
headers for quick and easy installation.
In detail:
The cascade controller fires, runs, and modulates the boilers
based on heat demand, plus rotates the boilers to achieve
equal run time.
The cascade controller strives to run boilers at low fire for the
longest time possible where efficiency is at their highest.
Low loss headers decouple the boilers from the system loop
independently of the number of zones calling. Boilers are piped
in reverse-return for equal flow rate through all boiler headers.
Required components:
GB162 boilers with individual manifolds and low loss
header
MCM10 multi cascade module (up to 4 boilers each)
Heat demand input via:
- AM10 outdoor reset controller
- 0-10V input (output power or system supply water
temperature)
- Dry contact input
- RC35 outdoor reset control with room influence
Logamax plus GB162 applications manual | 03.2013
Technical specifi cations are subject to change without prior notice
| 49