Buderus Logamax plus GB162 Applications Manual page 36

Gas condensing boiler
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

3 6 |
Programming - System 2
When powering up the AM10 the current outdoor
temperature is displayed (Fig. 28).
Press the mode key to switch to the next menu item. On
the screen a block will indicate the current step from 1
through 5.
The second menu item is the current supply temperature
computed based on the current outdoor temperature
(Fig. 29).
Press the mode key to switch to the next menu item.
Define the heating curve by entering two distinct set points.
(A) Supply water temperature at 14°F (-10°C) outdoor
temperature (Fig. 30), and by pressing the mode key
again, (B) supply water temperature at 68°F (20°C) outdoor
temperature (Fig. 31).
Press the mode key to switch to the warm weather shut
down (WWSD) temperature (Fig. 32). If the outdoor
temperature rises above this value space heating will stop.
Pressing the mode key again will return the display to the
current outdoor temperature (Fig. 28).
Supply water temperature at 14°F:
Supply water temperature at 68°F:
Warm weather shut down temperature:
See also chapter 2.3 for additional information on the AM10.
Technical specifi cations are subject to change without prior notice
Range
Factory Default
68 - 194 °F
167 °F
68 - 194 °F
86 °F
32 - 86 °F
70 °F
GB162 Applications Manual
Fig.28 Default display: Current outdoor temperature
Fig. 29 Current target supply temperature
Fig. 30 Heating curve upper value (14 °F)
Fig. 31 Heating curve lower value (68 °F)
Fig. 32 Warm weather shut down temperature
Logamax plus GB162 applications manual | 03.2013