4. Installation Instructions
Refrigerant tube port
Use caulking, putty, or a similar material to fill any gaps at
the refrigerant tube port (
ter, dust or foreign substances from entering the unit.
* Perform this work even if the tubing is routed out in a
downward direction.
Tighten each cap as specified below.
Tightening torque for each cap
Cap tightening torque
Service port cap
(width 15 mm, 17 mm)
Valve cap
(width 22 mm, 24 mm)
Service port cap
(width 15 mm)
Valve cap
(width 22 mm)
1
Valve cap
(width 22 mm)
Service port cap
(width 15 mm)
Flare nut
(
ø
6.35 mm)
Flare nut
2
(
9.52 mm)
ø
Do not apply a monkey wrench
to the hexagonal part.
Do not use two monkey wrenches when
3
removing or installing the balance tube
flare nut. In particular, do not apply a
monkey wrench to the hexagonal part at
the top of the valve.
(If force is applied to this part,
gas leakage will occur.)
4
5
Precautions for brazing
Be sure to replace the air inside the tube with nitrogen to prevent oxide film from forming during the brazing process. Be sure
to use a damp cloth or other means to cool the valve unit during brazing.
Work method
Field-supply tube
6
Brazing locations
7
CAUTION
8
) in order to prevent rainwa-
·
·
7
12 N
m (70
120 kgf
cm)
·
·
20
25 N
m (200
250 kgf
cm)
(0705
0905 Type)
Valve cap
(width 22 mm)
Service port cap
(width 15 mm)
Remote valve
Taping
1.
Be sure to use nitrogen. (Oxygen, CO
2.
Use a pressure-reducing valve on the nitrogen tank.
3.
Do not use agents intended to prevent the formation of oxide film. They will adversely affect the
refrigeration oil, and may cause equipment failure.
4.
The balance tube is not used if only 1 outdoor unit is installed. Use the unit in the same condi-
tions as when it was shipped from the factory.
Design of W-2WAY ECO-i SYSTEM Unit Specifications
Tubing routed out
through the front side
* Be careful of the cap sizes. The sizes of the service port cap and valve cap on
the 1155
1405 type liquid tube valves are different from other valve caps.
(1155
Service port cap
(width 17 mm)
Valve cap
(width 24 mm)
Valve cap
(width 22 mm)
Service port cap
(width 15 mm)
Flare nut
(
ø
6.35 mm)
Flare nut
(
12.7 mm)
ø
Use two monkey wrenches, as shown in the figure,
when removing the liquid tube valve flare nut.
1. Do not apply a wrench to the valve cap when removing or
installing the flare nuts. Doing so may damage the valve.
2. If the valve cap is left off for a long period of time, refrigerant
leakage will occur. Therefore, do not leave the valve cap off.
3. Applying refrigerant oil to the flare surface can be effective in
preventing gas leakage, however be sure to use a refrigerant
oil which is suitable for the refrigerant that is used in the system.
(This unit utilizes R410A refrigerant, and the refrigerant oil is
ether oil (synthetic oil). However, hub oil (synthetic oil) can also
be used.)
Pressure-reducing valve (regulator)
2
, and CFC must not be used.)
2-36
Tubing
cover
Tubing routed out
through the bottom
1305
1405 Type)
Valve cap
(width 22 mm)
Service port cap
(width 15 mm)
Bottom
plate