Sanyo SPW-C1155DXHN8 Technical Data & Service Manual page 38

2-way eco-i multi system
Hide thumbs Also See for SPW-C1155DXHN8:
Table of Contents

Advertisement

4. Installation Instructions
4-2. Shield for Horizontal Exhaust Discharge
It is necessary to install an air-discharge chamber (field sup-
ply) to direct exhaust from the fan horizontally if it is difficult to
provide a minimum space of 2 m between the air-discharge
outlet and a nearby obstacle. (Fig. 4-4)
CAUTION
4-3. Installing the Outdoor Unit in Heavy Snow Ar-
eas
In locations where wind-blown snow can be a problem, snow-
proof vents should be fitted to the unit and direct exposure to
the wind should be avoided as much as possible. (Fig. 4-6)
The following problems may occur if proper countermeasures
are not taken:
The fan in the outdoor unit may stop running, causing the
unit to be damaged.
There may be no air flow.
1
The tubing may freeze and burst.
The condenser pressure may drop because of strong
wind, and the indoor unit may freeze.
4-4. Precautions When Installing in Heavy Snow
Areas
2
a) The platform should be higher than the maximum snow
depth. (Fig. 4-5)
b) The 2 anchoring feet of the outdoor unit should be used
for the platform, and the platform should be installed be-
neath the air-intake side of the outdoor unit.
c)
The platform foundation must be solid and the unit must
3
be secured with anchor bolts.
d) When installing on a roof subject to strong wind, counter-
measures must be taken to prevent the unit from being
overturned.
4
5
6
7
8
In regions with heavy snowfall,
the outdoor unit should be
provided with a solid, raised
platform and snow-proof
vents.(Fig. 4-5)
Design of W-2WAY ECO-i SYSTEM Unit Specifications
AVOID
Without snow-
proof vents
(Without platform)
2-28
Fig. 4-4
DO
Fallen snow
With snow-
proof vents
(High platform)
Fig. 4-5
Fig. 4-6