Sanyo SPW-C1155DXHN8 Technical Data & Service Manual page 15

2-way eco-i multi system
Hide thumbs Also See for SPW-C1155DXHN8:
Table of Contents

Advertisement

1. Model Selecting and Capacity Calculator
3:
If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1 rank for the
gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table on the following page.)
4:
If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the
size.
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then
change the size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit: 28 kg
Max. additional charge for 2 outdoor units: 50 kg
Max. additional charge for 3 outdoor units: 60 kg
Table 1-2 Refrigerant Charge Amount at Shipment (for outdoor unit)
SPW-C0705DXHN8
12 kg
Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 1-3 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size
Amount of refrigerant
ø6.35
ø9.52
ø12.7
ø15.88
ø19.05
ø22.22
Table 1-4 System Limitations
Max. No. allowable connected outdoor units
Max. capacity allowable connected outdoor units
Max. connectable indoor units
Max. allowable indoor/outdoor capacity ratio
*1: In the case of 22 hp (type 61.5 kW) or smaller units, the number is limited by the total capacity of the connected indoor units.
*2: Up to 3 units can be connected if the system has been extended.
SPW-C0905DXHN8
SPW-C1155DXHN8
12 kg
Required amount of charge = (Amount of refrigerant charge per meter of
charge/m (g/m)
each size of liquid tube × its tube length) + (...) + (...)
26
*Always charge accurately using a scale for weighing.
56
*If the existing tubing is used, and the amount of on-site additional
128
refrigerant charge exceeds the value listed below, then change the size
185
of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit : 28 kg
259
Max. additional charge for 2 outdoor units: 50 kg
366
Max. additional charge for 3 outdoor units: 60 kg
135 kW (48 hp)
Design of W-2WAY ECO-i SYSTEM Unit Specifications
SPW-C1305DXHN8
12 kg
3 *²
40 *¹
50 – 130 %
2-5
SPW-C1405DXHN8
13 kg
13 kg
1
2
3
4
5
6
7
8