8.2.4

Two-wire control, method 2

You switch the motor on and off using a control command (ON/OFF1) and at the same time
select clockwise motor rotation. You also use the other control command to switch the motor
on and off, but in this case you select counter-clockwise rotation for the motor.
The inverter only accepts a new control command when the motor is at a standstill.
Figure 8-4
Table 8- 3
Parameter
p0015 = 17
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
Example
p3331 = 722.0
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Two-wire control, method 2
Function table
ON/OFF1
ON/OFF1
clockwise
counter-
rotation
clockwise
rotation
0
0
1
0
0
1
1
1
Description
Macro drive unit
Controlling the motor using the
digital inputs of the inverter:
BI: 2-3-WIRE control command 1 (ON/OFF1 clockwise rotation)
BI: 2-3-WIRE control command 2 (ON/OFF1 counter-clockwise rotation)
DI 0: ON/OFF1 counter-clockwise rotation
Also see section Digital inputs (Page 96).
Function
OFF1: The motor stops.
ON: Clockwise motor rotation.
ON: Counter-clockwise motor rotation.
ON: The motor direction of rotation is based on the signal that
assumes status "1" first.
Setting functions
8.2 Inverter control
DI 0
DI 1
ON/OFF1
ON/OFF1
clockwise rotation
counter-clockwise
rotation
221