SIMOVERT P 6SE21 Series Inverters

2. TECHNICAL DATA

Rated supply voltage:
Models 6SE21**–1AA11
Models 6SE21**–3AA21
** – May be any number
Output voltage
Output frequency
Efficiency
Motor power factor
Ambient operating temperature
(unit must not be exposed to direct sunlight)
Storage/transport temperature
Degree of protection
Humidity
Frequency stability at T
Frequency resolution
Overload rating

2.1 Equipment Ratings Table

Max.
Input
Cont.
Model
Model
Voltage
Voltage
Input
Input
Range
Range
Current
Current
6SE21..
6SE21..
01–1AA11
9.8 A
198–264 V
198–264 V
02–1AA11
13.5 A
1 phase
1 phase
1 phase
03–1AA11
26.5 A
03–3AA21
5.5 A
05–3AA21
10.0 A
08–3AA21
17.0 A
13–3AA21 342–550 V
28.0 A
342–550 V
3 phase
3 phase
17–3AA21
38.0 A
22–3AA21
40.0 A
27–3AA21
48.0 A
33–3AA21
70.0 A
42–3AA21
87.0 A
* Siemens 4–pole motor, 1LA5 series or equivalent.
** Automatically selected on voltage/frequency curve types 4 and 5 (see section 1.4.1).

2.2 Cable Lengths

The inverters will operate satisfactorily with unscreened cables of up to 150 m in length and screened or armoured
cable of up to 50 m in length. For applications where longer cables are required, inductors must be fitted to reduce
capacitive currents.
Note
If long cables are used, it may be necessary to change the value of parameter P52 to compensate for any
inaccuracies in the output current reading.
The following chokes are suitable for applications where up to 100/200 m screened/unscreened cables are required:
Model No.
6SE210*–1AA11 & 6SE2103–3AA21
6SE2105–/6SE2108–3AA21
6SE2113–/6SE2117–/6SE2122–3AA21 4EP3800–4DB
6SE2127–/6SE2133–3AA21
6SE2142–3AA21
Siemens plc 1995
o
10
C referred to f
max
max
Constant Torque
Circuit
Output
Breaker
Breaker
Continuous
Motor
Current
Rating *
16.0 A
2.8 A
.55 kW
16.0 A
3.9 A
.75 kW
32.0 A
6.8 A
1.5 kW
10.0 A
4.0 A
1.5 kW
16.0 A
7.6 A
3.0 kW
20.0 A
12.0 A
5.5 kW
32.0 A
19.0 A
7.5 kW
40.0 A
25.0 A
11.0 kW
50.0 A
32.0 A
15.0 kW
63.0 A
38.0 A
18.5 kW
80.0 A
46.0 A
22.0 kW
100.0 A
60.0 A
30.0 kW
Choke Type
4EP3601–8DB
4EP3801–4DB
4EP4002–1DB
4EU2421–8AA00
1 AC 50/60 Hz +/–1%, 220 – 240 V +/–10%
3 AC 50/60 Hz +/–1%, 380 – 500 V +/–10%
0 V – rated supply voltage
0.0 – 400 Hz
0.94
0.9 lagging/inductive
o
0 – 40
C
o
–30 – +85
C
IP21 (NEMA 1)
o
0 – 95% at 25
C
Analogue setpoint 1%
Digital setpoint 0.01%
0.1 Hz
1.5 x rated current for up to 60 seconds
Variable Torque
Variable Torque
Output **
Output **
460 V (USA)
Continuous
Motor
Continuous
Current
Rating *
Current
3.9 A
.75 kW
4.8 A
1.1 kW
10.0 A
2.2 kW
5.5 A
2.2 kW
4.8 A
9.5 A
4.0 kW
8.1 A
17.0 A
7.5 kW
14.0 A
23.0 A
11.0 kW
21.0 A
32.0 A
15.0 kW
27.0 A
38.0 A
18.5 kW
34.0 A
46.0 A
22.0 kW
40.0 A
60.0 A
30.0 kW
52.0 A
75.0 A
37.0 kW
65.0 A
English
Operating Instructions
Variable Torque
Output **
500 V
Motor
Continuous
Motor
Rating *
Current
Rating *
3 hp
4.8 A
2.2 kW
5 hp
8.1 A
4.0 kW
10 hp
12.0 A
7.5 kW
15 hp
19.0 A
11.0 kW
20 hp
25.0 A
15.0 kW
25 hp
32.0 A
18.5 kW
30 hp
38.0 A
22.0 kW
40 hp
46.0 A
30.0 kW
50 hp
60.0 A
37.0 kW
G85139–A1615–U156–A
02.95
Overload
Current
Current
4.2 A
5.8 A
10.2 A
6.0 A
11.4 A
18.0 A
28.5 A
37.5 A
48.0 A
57.0 A
69.0 A
90.0 A
11