Siemens Simovert P 6SE21 Series Operating Instructions Manual page 21

Table of Contents

Advertisement

SIMOVERT P 6SE21 Series Inverters
Parameter
Description
Number
P05
RUN/STOP mode
(see section 5.1.1 for detailed
explanation)
P06
Voltage to frequency curve selection
VOLTAGE
100
50
VOLTAGE
100
60
VOLTAGE
100
VOLTAGE
100
VOLTAGE
100
50
VOLTAGE
100
60
VOLTAGE
100
Knee Point
Curve type
P16
Siemens plc 1995
Display
Setting
(Default)
000
001
002
003
004
005
006
007
008
009
(000)
000
400
FREQUENCY
001
400
FREQUENCY
002
400
87
FREQUENCY
003
120
400
FREQUENCY
004
400
FREQUENCY
005
400
FREQUENCY
006
400
P15
FREQUENCY
(000)
[001]
Operating Instructions
Notes
Ramp down; edge–triggered; trip inactive.
Ramp down; level–triggered; trip inactive.
Free run; edge–triggered; trip inactive.
Free run; level–triggered; trip inactive.
Ramp down; edge–triggered; trip active.
Free run; edge–triggered; trip active.
Ramp down; level–triggered; trip active.
Free run; level–triggered; trip active.
Ramp down; push–button control.
Free run; push–button control.
Linear 0 – 50 Hz
100% 50 – 400 Hz
Linear 0 – 60 Hz
100% 60 – 400 Hz
Linear 0 – 87 Hz
100% 87 – 400 Hz
Linear 0 – 120 Hz
100% 120 – 400 Hz
1.5
Voltage
(frequency)
0 – 50 Hz
100% 50 – 400 Hz
(Suitable for use with pumps and fans.)
1.5
Voltage
(frequency)
0 – 60 Hz
100% 60 – 400 Hz
(Suitable for use with pumps and fans.)
User–defined curve.
When this curve is selected, the 'knee–point' and curve type must be
selected using parameters P15 and P16.
English
23
G85139–A1615–U156–A