Siemens Apogee P1 Technical Manual

Communications option
Hide thumbs Also See for Apogee P1:

Advertisement

Siemens APOGEE P1
Communications Option
Technical Manual
HA470909 Issue 3
Compatible with Version 1.x Software
© Copyright 2010 Parker Hannifin Ltd.
All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any
form or by any means to persons not employed by a Parker Hannifin Ltd., Automation Group, SSD Drives
Europe without written permission from Parker Hannifin Ltd., Automation Group, SSD Drives Europe. Although
every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to
make amendments or correct omissions. Parker Hannifin ltd., Automation Group, SSD Drives Europe cannot
accept responsibility for damage, injury, or expenses resulting there from.
Parker Hannifin Ltd., Automation Group, SSD Drives Europe, warrants the goods against defects in design, materials
and workmanship for the period of 24 months from the date of manufacture, or 12 months from the date of delivery
(whichever is the longer period) on the terms detailed in Parker SSD Drives Standard Conditions of Sale IA500504.
Parker Hannifin Ltd., Automation Group, SSD Drives Europe reserves the right to change the content and product
WARRANTY
specification without notice.

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Apogee P1

  • Page 1 Siemens APOGEE P1 Communications Option Technical Manual HA470909 Issue 3 Compatible with Version 1.x Software © Copyright 2010 Parker Hannifin Ltd. All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed by a Parker Hannifin Ltd., Automation Group, SSD Drives...
  • Page 2 FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE. This document and other information from Parker-Hannifin Corporation, its subsidiaries and authorized distributors provide product or system options for further investigation by users having technical expertise.
  • Page 3 Safety Information Requirements IMPORTANT: Please read this information BEFORE installing the equipment. Intended Users This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation. The information given is intended to highlight safety issues, EMC considerations, and to enable the user to obtain maximum benefit from the equipment.
  • Page 4 Safety Information Hazards DANGER! - Ignoring the following may result in injury 1. This equipment can endanger life by exposure to 5. For measurements use only a meter to IEC 61010 rotating machinery and high voltages. (CAT III or higher). Always begin using the highest range.
  • Page 5: Table Of Contents

    Protocol ........................1 Product Features ......................1 Size Notation – Part Numbers ..................1 Installation....................... 2 APOGEE P1 FLN Communication Module (HVAC10) ........... 2 • User Connections to the Main Serial Port (P1)..........3 • DIL Switch (SW1) Settings ................. 3 •...
  • Page 7: Siemens Apogee P1 Option

    PTION A System Overview The APOGEE P1 Technology Option provides a serial data port, allowing VSDs (variable speed drives) to be linked to form a network. Using an APOGEE Controller, this network can be continuously controlled to provide supervision and monitoring for each VSD in the system.
  • Page 8: Installation

    Wiring is very simple - all connections are SELV (Safe Extra Low Voltage). It is possible to establish serial communications without adhering to the following recommendations, however, the recommendations will promote greater reliability. Consult with the Siemens Building Technology office for information on wiring and Note: cabling.
  • Page 9: User Connections To The Main Serial Port (P1)

    User Connections to the Main Serial Port (P1) The serial port on the Option allows the following APOGEE P1 links to be made. RS485 Electrical Connections 2-wire differential Number of transmitters and transceivers 32 transceivers allowed per differential pair of wires...
  • Page 10: Terminal Block (Tb1) Connections

    Option. On the SIZE 1 unit it will protrude slightly above the standard plastic enclosure. • Make all user wiring connections. Refer to the Wiring Diagrams. • Re-fit the terminal cover securely with the screws. Siemens APOGEE P1 Communications Interface...
  • Page 11: Wiring Diagrams

    Figure 3 2-Wire Wiring Diagram for the HVAC10 Size 2 & 3 Drive DRIVE DRIVE (slave) (slave) APOGEE Controller FL1, FL2 or FL3 connections 0V SCR 0V SCR Figure 4 2-Wire Wiring Diagram for the HVAC10 Size 1 Drive Siemens APOGEE P1 Communications Interface...
  • Page 12: Initial Check For Connection

    Module LED Indication FAULT Parameter Indication Description SELF TEST Initialising SHORT FLASH HARDWARE Hardware fault FLASH TYPE MISMATCH Wrong type or disabled LONG FLASH PARAMETER Set-up fault, parameter values out-of-range NONE Valid set-up, ready for external communications Siemens APOGEE P1 Communications Interface...
  • Page 13 SOFT TIMEOUT: Drive not addressed in the last 10 seconds. OK: Device has been addressed. Note: The NETWORK LED can only be in the ON state when the MODULE LED is ON continuously, indicating that the Option is ready for external communications. Siemens APOGEE P1 Communications Interface...
  • Page 14: Initial Set-Up For Apogee P1

    Initial Set-up for APOGEE P1 Configuring the Drive Using the Operator Station (MMI) or other suitable PC programming tool, the TEC OPTION function block requires configuring before the APOGEE P1 option can be used. MMI Menu Map Non-specific MMI view...
  • Page 15 5 : DISABLED Serial communication has been disabled (default) Also refer to Network LED, page 7. NIGHT Range: FALSE/TRUE Shows the Night occupancy set by the FLN P1 network. Siemens APOGEE P1 Communications Interface...
  • Page 16: Troubleshooting

    Check that switch SW1:1 is ON, i.e. selected for 2- wire operation. Check power for all equipment on the network, e.g. RS232 to RS485 converter or repeater. SOFT TIMEOUT: Check the APOGEE controller program is running. Drive not addressed in the last 10 seconds. Siemens APOGEE P1 Communications Interface...
  • Page 17: Point Database For Siemens Apogee P1

    Point Database for Siemens APOGEE P1 Point Point Subpoint Name Factory Default Engr. Units Slope Intercept On Text Off Text Number Type (SI Units) (SI Units) (SI Units) (SI Units) CTRL ADDRESS – – – ED_HVAC10 2731 – – –...
  • Page 18 Point Database for Siemens APOGEE P1 cont. Analog 1 Out 0.01 -163.83 – – Analog 2 Out 0.01 -163.83 – – Analog 3 Out 0.01 -163.83 – – Analog In 1 0.01 -163.83 – – Analog In 2 0.01 -163.83 –...
  • Page 19: Point Database Cross Reference

    Setup/Motor Control/Flycatching/Enable Flycatching Setup/Motor Control/Flycatching/Active Analog 1 Out Setup/Inputs & Outputs/An Out/An Out 1/Value Analog 2 Out Setup/Inputs & Outputs/An Out/An Out 2/Value Analog 3 Out Setup/Inputs & Outputs/An Out/An Out 3/Value continued on next page… Siemens APOGEE P1 Communications Interface...
  • Page 20 Skip Freq 4 Startup/Setpoint Funcs/Skip Frequencies/Freq 4 Band 4 Startup/Setpoint Funcs/Skip Frequencies/Band 4 AR Enable Setup/Seq & Ref/Auto Restart/Enable AR attempts Setup/Seq & Ref/Auto Restart/Attempts AR Delay Setup/Seq & Ref/Auto Restart/Attempt Delay 1 Error Status Siemens APOGEE P1 Communications Interface...