CONDENSING HEAT RECOVERY MODULE

The MicoFlame could be provided in condensing mode for a variety of application including domestic hot
water and hydronic space heating.
The CHRM is intended to extract total (sensible and latent) heat from the flue gases downstream of the
primary heat exchanger. As a result, condensation of moisture in the flue gas will take place on the CHRM
surfaces and in the exhaust vent. This condensation is a natural outcome when efficiencies exceed 90%.
A neutralizer cartridge is provided and must be installed in the line from the condensate collection pot to
the drain. PH level of the condensate is to be checked regularly and neutralizing medium is to be replaced
as required to maintain effectiveness. A neutralizer cartridge is available from the factory.
Recommended installation methods of the condensing MicoFlame will vary depending on the application
and the expected water temperature variation of the system.
Examples of recommended installation for typical applications are shown below: