Mode 3: Setpoint Operation: Adjust Display - Camus Hydronics MFH060 Installation, Operation And Service Manual

Micoflame series gas fired residential and commercial copper tube boilers
Table of Contents

Advertisement

12.5

MODE 3: SETPOINT OPERATION: ADJUST DISPLAY

From the Home display;
1) Press
Display
simultaneously to view the following parameters:
Parameter
Name
Mode
Boiler Target
Temperature
Tank Target
Temperature
Tank
Differential
Differential
Temperature
Pump Delay
Temperature
Units
Parameter Description
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
To provide a target setpoint for
the heating system. Setpoint is
controlled to the inlet sensor
To provide a target setpoint for
the Tank. Setpoint is controlled to
the Tank sensor
To provide a modulation rate
above and below the Tank Target
Temperature. For example, if the
o
value is 10
F and the Tank
Target Temperature is 160
boiler will begin to modulate at
o
150
F and shut off at 170
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
o
if the value is 10
F and the Boiler
o
Target is 160
F the boiler will
begin to modulate at 150
o
shut off at 170
F.
Boiler post pump time after
burner has shut off, in seconds.
Select the desired unit of
measurement
21
Parameter Range
1 to 6
Default = 1
OFF, 70 to 220
(OFF,21 to 104
Default = 140
o
(82
C)
OFF, 70 to 190
(OFF, 21 to 88
Default = 130
o
(54
C)
o
2 to 10
F
o
(1 to 5
C)
o
F the
Default = 3
o
F.
o
Au, 2 to 42
(Au, -17 to 5
Default = 10
o
F and
OFF, 0:20 to 9:55
min, On
Default = 1:00 min
o
o
F,
C
o
Default =
F
o
F
o
C)
o
F
o
F
o
C)
o
F
o
o
F (1
C)
F
o
C)
o
F