IGNITION SYSTEM SAFETY SHUT-OFF DEVICE

After initial fill while the main burner is firing, shut off gas to the pilot and clock the time taken for the main
gas valve to shut down. If the safety control is functioning properly, power to the gas valve will be shut off
within 4 seconds of the pilot gas being shut off. If shut down takes longer, ignition control or gas valve may
be defective.
14.

LOW WATER TEMPERATURE SYSTEMS

In applications where the heating system requires supply water temperatures below 110°F, a bypass line
must be installed upstream of the boiler pump so that outlet water can be re-circulated to raise the inlet
temp to a minimum of 110°F. Balancing valves, preferably globe valves are used to adjust flow. (See
Figure 5)
simultaneously to view the following parameters:
Parameter
Name
Mode
Pump Delay
Temperature
Units
Parameter Description
Operating mode for the boiler.
NOTE: A complete description of each
mode can be found in section 8.4
Modes of Operation in this manual.
Boiler post pump time after burner has
shut off, in seconds.
Select the desired unit of measurement
26
Parameter Range
1 to 6
Default = 1
OFF, 0:20 to 9:55
min, On
Default = 1:00 min
o
o
F,
C
o
Default =
F

Advertisement

Table of Contents
loading

Table of Contents