MICOFLAME CONTROL PANEL

This controller accommodates up to four-stage control with six modes of operation which provides
setpoint as well as rest control. It provides the following:
1. Readings of inlet and outlet water temperatures as well as ∆T temperature rise
2. Six pre-set modes of operation; mode 1, 2, 4, and 5 for heating, mode 3 for DHW and mode 6
for operation by a remote controller.
3. Operation as an auto reset limit.
4. Operation as a control for inlet water temperature.
5. Optional tank mounted sensor used in conjunction with inlet sensor.
6. Adjustable pump delay feature based on ∆T temperature difference between inlet and outlet
temperatures. Accepts 1/6 hp. pump directly across terminals 13 & 14.
7. Adjustable; target temp, inter-stage differential, on delay between stages, minimum on time
per stage, minimum off time per stage.
8. Display of run hours for maintenance purposes. Counter wraps around at 1000 hours.
9. Flame failure signal 24 V.
10. Molex connector for ease of service.
11. Error message display.
12. Test override feature to test pump operation, stages 1, 2, 3, and 4 and alarm.
13. Pump exercising feature runs pump 10 seconds every three days of no pump operation.
Table 4: BTC 1 Key Functions
KEY
KEY DESCRIPTION
The abbreviated name of the selected
item will be displayed in the item field of
Item
the display. To view the next item, press
the Item button.
Increase a parameter value.
Decrease a parameter value.
16