Freeze Protection; Warning Regarding Chilled Water Systems - Camus Hydronics MFH060 Installation, Operation And Service Manual

Micoflame series gas fired residential and commercial copper tube boilers
Table of Contents

Advertisement

BOILER APPLICATION (HYDRONIC HEATING)
In case of boiler (Hydronic heating boiler) application, the return water (supply water) may be more than
115ºF (46ºC), therefore there is no need for a recirculation loop and the primary heat exchanger and
CHRM can be piped in parallel. Since the inlet water temperature to CHRM exceeds 115ºF (46ºC) it will
not condense fully and therefore the CHRM will not perform to its maximum efficiency capacity. If water
colder than 115ºF (46ºC) is available it can be fed to the CHRM.
WATER HEATER APPLICATION (HOT WATER SUPPLY)
In case of domestic water supply (Water Heating), the fresh inlet water temperature will be less than 115ºF
(46ºC), in this case the CHRM may be fed directly with part of the supply water using a secondary pump.
8.

FREEZE PROTECTION

Appliance installations are not recommended outdoors in areas where danger of freezing exists
unless precautions are taken. Maintaining a mixture of 50% water and 50% propylene glycol is the
preferred method of freeze protection in hydronic systems. This mixture will protect the appliance
to approximately -35ºF (-37ºC). To maintain the same temperature rise across the appliance
increase the GPM flow by 15% and the head loss by 20%.
The following example demonstrates the procedure to follow for calculating the revised head for the heat
exchanger when using a water / glycol mixture.
Given that Camus is showing a heat exchanger flow and head loss of 100 gpm @ 10 feet
Increasing the flow by 15% now results in a head loss of 13 feet at 115 gpm (from B&G system
syzer). At this increased flow Camus now recommends to increase the head loss by 20%.
The requirement for the heat exchanger with water / glycol mixture will now be 115 gpm @ 15.6
feet. (ie. 1.2 x 13ft. = 15.6 ft.)
A similar procedure must be followed to calculate the additional head loss in pipe and fittings in
order to arrive at the proper pump selection.
For Outdoor installations a snow screen should be installed to prevent snow and ice accumulation
around the appliance. Regular inspections should be made to ensure that air intake and vent are
free of snow and ice. Always consider the use of a shelter such as a garden shed in lieu of direct
exposure of the appliance to the elements. The additional protection afforded by the shelter will
help to minimize nuisance problems with electrical connections and will allow easier servicing of
the appliance under severe weather conditions.
9.

WARNING REGARDING CHILLED WATER SYSTEMS

When a boiler is connected to an air conditioning system where the same water is used for heating and
cooling, the chiller must be piped in parallel with the boiler. Appropriate flow control valves; manual or
motorized must be provided to prevent the chilled water from entering the boiler. (See Figure 3)
13