Check And Replacing Ignition Electrode - Potterton EC three 125 Installation, Operation And Maintenance Manual

Floor standing condensing gas boilers 125 to 300kw
Table of Contents

Advertisement

Maintenance
9.6 Check and replacing Ignition
electrode
Fig. 36: Remove ignition electrode block
134
Note: To avoid an influence of the ionisation current by the ignition, the ignition
electrode must only immerse into the edge of the flame.
Change ignition electrodes
Danger of electric shock! Before performing service work, power to the boiler must
be shut off and it must be secured from accidentally being switched back on!
Eurocondense three
125 - 170
1. Loosen ignition cable
2. Remove nuts and pull out the ignition electrode block (1) with the seal (2)
3. Insert the new ignition electrode block with seal and fasten with nuts
Note: Installation position and electrode clearance has to be maintained according
to Fig. 38 .
4. Reconnect the ignition cable
Condensing gas boiler Eurocondense three125-300 kW
Eurocondense three
215 - 300
1
2
1
2
C0004597
7308536-02 06.13