Usage according to purpose...................... General safety instructions......................Regulations and standards......................Liquid gas under ground......................CE-Marking..........................Conformity declaration......................Technical Data Paramount Three 30-115....................10 Dimensions and connections..................... 11 Specification..........................13 Wiring diagram........................15 Sensor value tables........................17 Prior to installation..........................18 Air Supply Openings.........................
Page 4
At the end of the maintenance work..................131 10.9 Check Electrodes........................132 10.10 Fault switch-off........................132 10.11 Fault code table........................134 10.12 Maintenance code table......................137 10.13 Operating phases of the Control Centre LMS................137 Paramount three 30-115 kW 7308272-03 03.14...
Caution! If warning is not observed, danger exists for environment and the device. Note/tip: Here, you can find background information and useful tips. Reference to additional information in other documents. 1.4 For whom is this manual intended? This installation manual is intended for the heating specialist. Paramount three 30-115 kW 7308272-03 03.14...
Setting, maintenance and cleaning of the device must only be carried out by a qualified gas heating specialist! Used accessories must comply with the technical rules and have been approved in connection with these device by the manufacturer. Caution! Only original spare parts must be used. 7308272-03 03.14 Paramount three 30-115 kW...
92/42/EG as condensing boiler. When natural gas is used, the gas condensing-boiler emit less than 60 corresponding to the requirements as per §6 of the Ordinance regarding small fir- ing places dated 26.01.2010 (1. BImSchV). Paramount three 30-115 kW 7308272-03 03.14...
Condensing gas boiler Trade mark Paramount Product ID number CE-0085 CL 0072 Type, Model Paramount three 30, 40, 60, 80, 95, 115 EU directives 2006/95/EEC, 2004/108/EEC, 2009/142/EEC, 1992/42/EEC Standards DIN VDE 0722 DIN EN 50081-1, DIN EN 50082-2 DIN EN 60335-1, DIN EN 483...
Technical Data Paramount Three 30-115 3.1 Dimensions and connections Fig. 1: Dimensions and connections 30/40 kW 60-115 kW 30/40 kW: Ø125 60-115 kW: Ø160 30/40 kW: Ø80 60-115 kW: Ø110 aGR030B 7308272-03 03.14 Paramount three 30-115 kW...
Page 12
Technical Data Paramount Three 30-115 Tab. 1: Dimensions and connections Model Paramount Paramount Paramount Paramount Paramount three 30/40 three 60 three 80 three 95 three 115 - Heating flow G 1" G 1 1/2“ - Heating return G 1" G 1 1/2“...
Technical Data Paramount Three 30-115 3.2 Specification Tab. 2: Specification Model Paramount three Product-ID-No. CE-0085BL0514 VDE-Reg.-No. VDE-mark International protection IPx4D Gas category 2H3+ Device categories Nominal heat input Natural Heating kW 5,6-30,0 9,0-38,0 14,0-58,0 21,0-77,0 20,0-95,0 25,0-115,0 range mode Nominal heat out- Natural 80/60°C...
Page 14
Technical Data Paramount Three 30-115 Model Paramount three Heating water Adjustment range heating water temper- °C 20 - 85 atur Max. temp °C Operating pressure min. max. Hydraulic resistance Flow rate @20K kg/h 1254 1583 2150 3311 4085 4945 Hydraulic resistance @20K...
- For buffer cylinders in conjunction with solar thermal systems or solid fuel boil- ers, take the buffer capacity into consideration when determining the fill water volume. Paramount three 30-115 kW 7308272-03 03.14...
The total water volume in the heating system is composed of the system volume (= fill water volume) plus the top-up water volume. In the POTTERTON boiler-spe- cific diagrams, only the system volume is given to make them easier to use. Over the entire service life of the boiler, a maximum top-up volume of twice the system volume is assumed.
To set this operating point, the heat transfer medium should be diluted with water in a ratio of 2:1. This mixing ratio has been test by Potterton in relation to its practical suitability for use with gas condensing boilers.
≤ 8.4 < 0.11 200 - 600 ≤ 8.4 ≤ 0.11 < 0.11 > 600 ≤ 0.11 < 0.11 < 0.11 *) for system boilers (< 0.3 l/kW) and systems with electric heating elements 7308272-03 03.14 Paramount three 30-115 kW...
To this are also included especially alumi- nium, brass and copper installations. For damages occurring due to the installation in an unsuitable location or based on improper combustion air supply, there is no warranty claim. Paramount three 30-115 kW 7308272-03 03.14...
Page 23
Prior to installation 7308272-03 03.14 Paramount three 30-115 kW...
Prior to installation 4.8 Application example Paramount three 30-115 kW 7308272-03 03.14...
Page 25
Prior to installation 7308272-03 03.14 Paramount three 30-115 kW...
Page 26
Prior to installation Paramount three 30-115 kW 7308272-03 03.14...
Page 27
Prior to installation Further application examples (mixing circuits, solar connection, etc.) may be found in the Programming and hydraulic system manual 7308272-03 03.14 Paramount three 30-115 kW...
Note: This system has been type-approved and certified as a system by Paramount DVGW. The enclosed assembly instruction for the exhaust gas pipeline system has to be observed. 1 ) accessory 7308272-03 03.14 Paramount three 30-115 kW...
The ducts must be made of non-combustible, dimensionally stable materials. Fire resistance duration of the shaft: 90 min. Fire resistance duration of the shaft in case of buildings of lower building height: 30 min. Paramount three 30-115 kW 7308272-03 03.14...
- per 87° elbow = 2.50 m - per 45° elbow = 1.00 m - per 30° elbow = 0.50 m - per 15° elbow = 0.50 m - per revision T-piece = 2,50 m 7308272-03 03.14 Paramount three 30-115 kW...
An approved thermally activated shut-off device has to be installed. In case of regionally existing old gas pipes, the installation of a gas filter is recom- mended. Paramount three 30-115 kW 7308272-03 03.14...
-content has to be set by adjusting the nozzle pressure at the gas valve (see section Guide line for nozzle pressure) The CO -content must be between the values according to section Technical Data at full load as well as low load. 7308272-03 03.14 Paramount three 30-115 kW...
2 Setting for full load 5 Protective plug 3 Setting for low load (remove protective plug in 6 Fan pressure advance (5)) X Flow direction Note: The Torx-key is located in the accessory bag. Paramount three 30-115 kW 7308272-03 03.14...
The values given in Tab. 6 (Page 36) are guide values. It is important that the gas quantity is set via the injector pressure in such a way that the CO -value is within the specified values (see Tab. 2 (Page 13) ). 7308272-03 03.14 Paramount three 30-115 kW...
1 mm or 3 x 1.5 mm We recommend the installation of a mains isolator upstream of the Paramount. This should isolate all poles and provide contact separation of at least 3 mm. Paramount three 30-115 kW 7308272-03 03.14...
The wiring diagram must be followed! Optional accessories must be fitted and connected according to the instructions provided. Ensure earthing is correct. Outdoor temperature sensor (included in delivery) The outdoor temperature sensor is located in the accessory box. Follow pictorials on box for installation instructions. 7308272-03 03.14 Paramount three 30-115 kW...
5.19.7 Replacing cables All connecting cables, except for the mains connection cable, have to be replaced by Potterton-special cables in case of replacement. When replacing the mains con- nection cable, only cables of the types 3 x 1 mm or 3 x 1,5 mm should be used.
Switch on boiler electrical isolation Open gas shut-off device (1) and the water shut off valves (2 and 3) 3. Open front panel cover and switch on operating switch on the front panel of the boiler 7308272-03 03.14 Paramount three 30-115 kW...
Heating circuit pumps have been switched on and mixer is set to manual opra- tion 6.6.2 Adjusting setpoint manual control Using the operation mode "manual operation" you can choose a nominal tempera- ture value for it: Paramount three 30-115 kW 7308272-03 03.14...
Only components tested to the respective standard and marked have been used. All components have been installed according to the maufac- turer's instruction. The whole system conforms to the relevant standard. 7308272-03 03.14 Paramount three 30-115 kW...
Only components tested and marked according to he respective standard have been used. Date /signature To ensure the heat source operates reliably and economically for a long period, Company stamp we recommend annual maintenance for the heat source........ Paramount three 30-115 kW 7308272-03 03.14...
7.3 Stop heating operation Changeover between operating modes for heating operation will be carried out with the operating button "' Heating operation'. The selected setting will be marked with a bar underneath the operating mode symbol. xxxxxxxxxxxxxx Paramount three 30-115 kW 7308272-03 03.14...
DHW ist being heated up to 65 °C once for eliminating the existing legionellas. 7.5 Setting room setpoint Setting comfort setpoint: 1. Set comfort setpoint with the control knob => The value will automatically be take over 7308272-03 03.14 Paramount three 30-115 kW...
7.7 Error message If the fault sign appears in the display, a fault exists in the heating system. - Press information button (i) - Further information can be called up (see Fault code table). Paramount three 30-115 kW 7308272-03 03.14...
=> The activated special function is displayed by the symbol in the display. Note: If a heat demand from a cylinder with internal indirect coil is present, this demand will continue to be met while the emissions test function is running. 7308272-03 03.14 Paramount three 30-115 kW...
Select the required setting level with the control knob. Programming levels - Enduser (Eu) - Commissioning (C), incl. enduser (Eu) - Engineer (E), incl. enduser (E) and commissioning (C) - OEM, includes all other setting levels (password-protected) 4. Press OK button Paramount three 30-115 kW 7308272-03 03.14...
The basic programming processs is depicted in the following by the setting of time and date. Press OK button Note: If parametres which are not mentioned in the level below are subject to change consider section Programming procedure! 7308272-03 03.14 Paramount three 30-115 kW...
Page 50
Tip: The previous menu point will be called-up by pressing the ESC-button without taking over previously modified values. If no settings are carried out for approxi- mately 8 minutes, the basic display is called-up without taking over previously modified values. Paramount three 30-115 kW 7308272-03 03.14...
Heating circuit 1 | Heating circuits 1 and 2 | Heating circuits 1 and 3/P | All heating circuits This parameter is only visible in the room device, as the operating unit in the boiler is fixed programmed for the operating device! 7308272-03 03.14 Paramount three 30-115 kW...
Page 52
Mo-Su | Mo-Fr | Sa-Su | Mo | Tu | We | Th | Fr | Sa | Su 1st phase on 06:00 (h/min) 1st phase off 22:00 (h/min) 2nd phase on --:-- (h/min) 2nd phase off --:-- (h/min) 3rd phase on --:-- (h/min) 3rd phase off --:-- (h/min) Copy? Paramount three 30-115 kW 7308272-03 03.14...
Page 53
Time program 5 Preselection Mo - Su Su | Mo-Fr | Sa-Su | Mo | Tu | We | Th | Fr | Sa | SuMo- 1st phase on 06:00 (h/min) 1st phase off 22:00 (h/min) 7308272-03 03.14 Paramount three 30-115 kW...
Page 54
0.0 °C Heating curve adaption Off | On Summer/winter heating limit 18°C 24-hour heating limit 0 °C Flow temp setpoint min 8°C Flow temp setpoint max 80°C Flow temp setpoint room stat --- °C Paramount three 30-115 kW 7308272-03 03.14...
Page 55
Parameter only visible if heating circuit 2 is installed. Comfort setpoint 1010 20.0°C Reduced setpoint 1012 18.0°C Frost protection setpoint 1014 10.0°C Heating curve slope 1020 1.50 Heating curve displacement 1021 0.0 °C Heating curve adaption 1026 Off | On 7308272-03 03.14 Paramount three 30-115 kW...
Page 58
- No | Yes Consumer circuit 2 Flow temp setp cons request 1909 70°C DHW charging priority 1924 No | Yes Excess heat draw 1925 Off | On With buffer storage tank 1928 No | Yes Paramount three 30-115 kW 7308272-03 03.14...
Page 59
Frost prot plant boiler pump 2300 Off | On Boiler pump on heat gen lock 2301 Off | On Impact heat generation lock 2305 Heating mode only Heating mode only | Heating and DHW mode 7308272-03 03.14 Paramount three 30-115 kW...
Page 60
Pump speed min 2322 Pump speed max 2323 100% Output nominal 2330 Paramount Three 30: 28 Paramount Three 40: 38 Paramount Three 60: 50 Paramount Three 80: 70 Paramount Three 95: 90 Paramount Three 115: 110 kW Output basic stage...
Page 61
Programming Function Prog. Standard value Level Max fan output heating full charging 2442 Paramount Three 30: 28 Paramount Three 40: 38 Paramount Three 60: 50 Paramount Three 80: 70 Paramount Three 95: 90 Paramount Three 115: 110 kW Fan output DHW max.
Page 62
Collector start function Off 3833 19:00 (h:min) Collector start funct grad 3834 - - - min/°C Collector frost protection 3840 - - - °C Collector overtemp prot 3850 - - - °C Evaporation heat carrier 3860 130°C Paramount three 30-115 kW 7308272-03 03.14...
Page 63
Full charging sensor 4813 With B42/41 With B4 | with B42/41 DHW-storage Parameter subject to the respective system hydraulics. Charge push forward time 5011 60 min Flow setpoint boost 5020 18°C Transfer boost 5021 10°C 7308272-03 03.14 Paramount three 30-115 kW...
Page 64
5144 30 s Flow setp compensation Tv 5145 30 s Full charging with B36 5146 No | Yes Min start temp diff Q33 5148 -3°C Excess interm circ temp del 5151 30 s Configuration Paramount three 30-115 kW 7308272-03 03.14...
Page 65
B13 | Solar flow sensor B63 | Solar return sensor B64 Sensor input BX2 5931 DHW sensor B31 Parameters see Sensor input BX1 (prog.-no. 5930)! Sensor input BX3 5932 Buffer st tank sensor B4 Parameters see Sensor input BX1 (prog.-no. 5930)! 7308272-03 03.14 Paramount three 30-115 kW...
Page 69
7044 --- months Time since maintenance 7045 0 months Fan speed ionization current 7050 0 rpm Message ionization current 7051 No |Yes Chimney-sweep function 7130 Off | On Manual control 7140 Off | On 7308272-03 03.14 Paramount three 30-115 kW...
Page 70
Voltage signal H2 EM1 7845 Contact state H2 EM1 7846 NO | NC Voltage signal H2 EM2 7848 Contact state H2 EM2 7849 NO | NC Contact state H4 7860 NO | NC Frequency H4 7862 Paramount three 30-115 kW 7308272-03 03.14...
Page 71
Parameters see Priority/state source 1 (prog.no. 8100)! Priority/state source 9 8116 Parameters see Priority/state source 1 (prog.no. 8100)! Priority/state source 10 8118 Parameters see Priority/state source 1 (prog.no. 8100)! Priority/state source 11 8120 Parameters see Priority/state source 1 (prog.no. 8100)! 7308272-03 03.14 Paramount three 30-115 kW...
Page 72
8390 Collector pump 1 8499 Solar ctrl elem buffer 8501 Solar ctrl elem swi pool 8502 Collector temp 1 8510 Collector temp 1 max 8511 Collector temp 1 min 8512 dt collector 1/DHW 8513 Paramount three 30-115 kW 7308272-03 03.14...
Page 73
Off | On Speed heating circuit pump 2 8765 Room temperature 2 8770 Room setpoint 2 8771 Flow temperature 2 8773 Flow temp setpoint 2 8774 Room thermostat 2 8779 No demand | Demand 7308272-03 03.14 Paramount three 30-115 kW...
Page 74
8981 Buffer temp-act value low (B41) 8982 Buffer temp-act value middle (B42) 8983 Relay output QX1 9031 Off | On Relay output QX2 9032 Off | On Relay output QX3 9033 Off | On Paramount three 30-115 kW 7308272-03 03.14...
Under prog. no. 5 the start of summertime is set. under prog. no. 6 the end of (5 - 6) summertime is set. The time changing will be carried out on the Sunday following the set date. Paramount three 30-115 kW 7308272-03 03.14...
- Activation of the prog. no. 31 at the room unit: The individual programming of the room unit will be written into the control. This parameter is only visible if a suitable standard setting is available in the pro- gramming unit. 7308272-03 03.14 Paramount three 30-115 kW...
Note: The time programme 1 and 2 are always assigned to the respective heating circuits (1 - 3) and only displayed if these heating circuits are present and also turned on in the menu Configuration (prog.-no. 5710 and 5715). Paramount three 30-115 kW 7308272-03 03.14...
Selection of the operation level (reduced setpoint or frost protection) for the holi- (648, 658, 668) day program. Note: A holiday period ends each time on the last day at 12:00 AM (00:00). The holiday programs are only activated in the operation mode Automatic . 7308272-03 03.14 Paramount three 30-115 kW...
° C 1,75 1,25 0,76 0,25 ° C Outside temperature Heating curve displacement Correction of the heating curve by parallel shifting in case of generally too high or (721, 1021,1321) too low room temperature. Paramount three 30-115 kW 7308272-03 03.14...
Page 81
Flow temp setpoint room stat For room thermostat mode the flow setpoint set here applies. (742, 1042, 1342) In the setting "--°C", the value calculated via the heating curve is used as the set flow temperature. 7308272-03 03.14 Paramount three 30-115 kW...
Page 82
0.25°C below the set room set point. This function is only possible with the RGT/ RGTF or RGB room unit and active room influence. A room sensor must be connected. This function only applies to pumped heating circuits. Paramount three 30-115 kW 7308272-03 03.14...
Page 83
Fig. 16: Boost heating TRSPR Room temperature setpoint Room temperature actual value DTRSA Room temperature set point-raised 2 ) accessories 7308272-03 03.14 Paramount three 30-115 kW...
Page 84
Without room sensor an advance time is calculated based on the outside temper- ature and the building time constant (prog. no. 6110). The optimization time (ad- vance) is limited here to a maximum value. By setting the optimization time = 0, the function is switched off. Paramount three 30-115 kW 7308272-03 03.14...
Page 85
Between these two points there is a linear increase of the "re- duced setpoint" up to the "comfort setpoint". Fig. 18: Reduced setpoint increase TRwA1 Red setpoint increase start TRwA2 Red setpoint increase end Comfort nominal value Room temperature reduced setpoint Outside temperature composite 7308272-03 03.14 Paramount three 30-115 kW...
Page 86
- Functional- and curing heating: The whole temperature profile will be run through automatically. - Manually: control to the Floor curing setpoint manually. Fig. 19: Temperature profile during floor curing function [day] Fh+Ch Start day Fh Functional heating Ch Curing heating Paramount three 30-115 kW 7308272-03 03.14...
Page 87
The temperature actual value is attenuated with a filter (time constant capable of parameterization) Pump speed min Using this function the minimum speed for the heating circuit pump can be (882, 1182, 1482) specified. 7308272-03 03.14 Paramount three 30-115 kW...
DHW temperature value and the reduced nominal DHW temperature value depending on the time switching programs. Every time, the switching-on time will be moved forward. - Die Vorverlegung beträgt 1 Stunde (siehe Fig. 20 ). Paramount three 30-115 kW 7308272-03 03.14...
Page 89
Legionella funct weekday Selection of the weekday for the legionella function fixed weekday (factory set- (1642) ting). 7308272-03 03.14 Paramount three 30-115 kW...
Setting of the flow setpoint is done with this function, which is effective during active request of the consumer circuit. DHW charging priority Setting, if the connected consumerscircuit pump should be used with priority for (1874, 1924, 1974) domestic hot water charging. Paramount three 30-115 kW 7308272-03 03.14...
- Before buffer storage tank: the primary controller/feed pump is arranged with (2150) existing buffer storage tank hydraulically before the buffer storage tank - After buffer storage tank: the primary controller/feed pump is arranged with existing buffer storage tank hydraulically after the buffer storage tank 7308272-03 03.14 Paramount three 30-115 kW...
Caution! The limit of the boiler stroke is only performed if a modulating heat cir- cuit pump is configured, i.e. if Prog. no. 6085 (PWM-output P1) is assigned to a heating circuit pump. Paramount three 30-115 kW 7308272-03 03.14...
Page 93
Note: These are calculated values. The actual output must be calculated using a gas meter, for example. Max fan output heating full With this parameter the maximum boiler capacity can be limited in full charging charging mode at layer storage. (2442) 7308272-03 03.14 Paramount three 30-115 kW...
Page 94
Boiler capacity which is used during the duration of the control delay. (2452) Note: The calculated value see prog-no. 2444. Controller delay duration Duration of the control delay. The time duration starts as soon as after ignition a (2453) positive flame detection is done. Paramount three 30-115 kW 7308272-03 03.14...
- Early on, late off: additional boiler is switched on as early as possible (output range min) and back off as late as possible (output range min). I.e. boiler in op- eration as much as possible, or as long as possible running times for additional boiler. 7308272-03 03.14 Paramount three 30-115 kW...
8.17 Solar Temp diff on The switching-on and switching-off point of the collector pump is set with these (3810) functions. Basis is the temperature difference between collector temperature and Temp diff off storage temperature. (3811) Paramount three 30-115 kW 7308272-03 03.14...
Page 97
Temp diff ON swi pool For exceeding or not reaching the difference between solar collector temperature (3816) and swimming pool temperature, the solar pump is switched on and off. Temp diff OFF swi pool (3817) 7308272-03 03.14 Paramount three 30-115 kW...
Page 98
(e.g. with vacuum tubes), then a periodic switching on of the pump is possible. The temperature on a certain collector cannot be measured correctly, if the pump is switched-off. For this reason, the pump must be activated from time to time. Paramount three 30-115 kW 7308272-03 03.14...
(prog. no. 4133). Setpoint min The boiler pump is only put into operation if the boiler temperature has reached (4110) the minimum setpoint set here in addition to the necessary temperature differ- ence. 7308272-03 03.14 Paramount three 30-115 kW...
If the temperature difference between buffer storage and heating circuit temper- (4722) ature request is sufficiently large, the heat required by the heating circuit will be taken from the buffer storage. The heat generator is locked. Paramount three 30-115 kW 7308272-03 03.14...
Page 101
(prog. no. 4795), the return can be preheated by redirecting over the lower part of the storage tank. In this way, for example, a re- turn reheating can be implemented. 7308272-03 03.14 Paramount three 30-115 kW...
Through the transfer, energy can be moved from the buffer storage tank into the (5021) DHW storage tank. For this the current buffer storage tank temperature must be higher than the current temperature in the DHW storage tank. This temperature difference is set here. Paramount three 30-115 kW 7308272-03 03.14...
Page 103
If the DHW-charging value is exceeded, the collector pump switches off. The collector pump can be re-activated by the collector overheating protecting function see prog.no. 3850) until the storage safety temperature has been reached. 7308272-03 03.14 Paramount three 30-115 kW...
Page 104
- No: the domestic hot water storage tank will be charged without primary con- pump troller/system pump. (5092) - Yes: the domestic hot water storage tank will be charged from the primary con- troller on/with the system pump. Paramount three 30-115 kW 7308272-03 03.14...
Page 105
- No: the end of the full charging is detected via the temperature on the upper and lower storage sensor B3 and B31. - Yes: the end of the full charging is detected via the temperature on the upper storage sensor B3. 7308272-03 03.14 Paramount three 30-115 kW...
- Heating circuit: The diverting valve (DV) goes into the heating circuit position after the last request has ended. - DHW: The diverting valve (DV) goes into the DHW position after the last re- quest has ended. Paramount three 30-115 kW 7308272-03 03.14...
Page 107
- DHW mixing pump Q35: separate pump for cylinder content circulation whilst pasteurisation is active. - Heat request K27: output K27 will be activated as soon as a heat demand exists in the system. 7308272-03 03.14 Paramount three 30-115 kW...
Page 108
- Consumer request VK1/VK2: The set flow temperature setpoint is activated via the connecting terminals (e.g. a ventilation heater function for door curtain units). Note: The setpoint is set under programme number 1859/1909. Paramount three 30-115 kW 7308272-03 03.14...
Page 109
The linear sensor curve is defined over two fixed points. The setting is done with Function values 1/2 H4 two parameter pairs for function value and frequency value (F1 / U1 and F2 / U2). (5973-5976) 7308272-03 03.14 Paramount three 30-115 kW...
Page 110
The linear sensor curve is defined over two fixed points. The setting is made with ule 1-2 two parameter pairs for Function value and Voltage value (F1 / U1 and F2 / U2). (6049, 6051, 6057, 6059) Function values 1/2 H2 mod- ule 1-2 (6050, 6052, 6058, 6060) Paramount three 30-115 kW 7308272-03 03.14...
Page 111
(see also Quick setback prog.-no. 780, ... ): - 40 for buildings with thick walls or outer insulation. - 20 For buildings of normal building design. - 10 For buildings of light building design. 7308272-03 03.14 Paramount three 30-115 kW...
Page 112
1/storage/heating circuit scheme, which is composed of the numbers listed in Tab. 11 (Page 112) (6212, 6213, 6215, 6217) Tab. 11: Check no. heat source 1 (prog.-no. 6212) Solar No solar DHW/B DHW+B DHW/B Paramount three 30-115 kW 7308272-03 03.14...
- Locally: the local heating circuit is switched on and off. (6623) - Centrally: depending on the settings made in prog no. 6620 either the heating circuit in the segment or in the entire system is switched on and off. Paramount three 30-115 kW 7308272-03 03.14...
Error history/error codes The last 20 error messages with error code and time of error occurrence will be (6800 - 6995) stored in the error storage. 7308272-03 03.14 Paramount three 30-115 kW...
Here the desired telephone number of customer service can be entered. (7170) PStick storage pos Via the parameter PStick Storage Pos the data set (data set number on the stick) (7250) can be selected which should be written or read. Paramount three 30-115 kW 7308272-03 03.14...
8.25 Input/output test Input/output tests Tests for checking the connected components for function. (7700 - 7872) 8.26 State State With this function the state of the selected system can be requested. (8000 bis 8011) 7308272-03 03.14 Paramount three 30-115 kW...
Page 118
Optimum stop control Reduced heating mode Frost protection active Frost prot room active Frost protection flow active Frost prot plant active Summer operation Summer operation 24-hour Eco active Setback reduced Setback frost protection Room temp limitation Paramount three 30-115 kW 7308272-03 03.14...
Page 119
Frost protection Instantaneous water heater Overrun active Overrun active Standby charging Standby charging Charged Charged, max st tank temp Charged, max charging temp Charged, legionella temp Charged, nominal temp Charged, reduced temp Ready Ready 7308272-03 03.14 Paramount three 30-115 kW...
Page 120
In operation for HC In part load op for HC In part load op for HC Released for HC Released for HC Overrun active Overrun active Released Released Frost protection active Frost prot plant active Paramount three 30-115 kW 7308272-03 03.14...
Page 121
Charging DHW+swi pool Charging buffer+swi pool Charging buffer+swi pool Charging DHW Charging DHW Charging buffer Charging buffer Charging swimming pool Charging swimming pool Radiation insufficient Min charg temp not reached Temp diff insufficient Radiation insufficient 7308272-03 03.14 Paramount three 30-115 kW...
Page 122
The following messages are possible under burners: End user (Eu) Commissioning, Engineer (menu state) Fault position Fault position Start prevention Start prevention In operation In operation Commissioning Safety time Prepurge Commissioning Postpurge Shutdown Home mode Standby Standby Paramount three 30-115 kW 7308272-03 03.14...
Heating mode solar off Heating mode source off Cold Cold 8.27 Diagnostics cascade/heat generation/consumers Diagnostics cascade/heat Displays of different nominal and actual values, relay switching statuses and generation/consumers counter statuses for diagnosis purposes. (8100 - 9058) 7308272-03 03.14 Paramount three 30-115 kW...
- Prog. no. 9627 equates to the shift of the fan characteristic curve in Y-direction 8.29 Info Option Display of different information values which depend on the current operation state. Furthermore, informations about the different states are displayed (see sec- tion State). Paramount three 30-115 kW 7308272-03 03.14...
The value switched over to stays active until the next modification by the time programme. 3 ) accessories 7308272-03 03.14 Paramount three 30-115 kW...
Remove the siphon completely from the gas-condensing boiler with hose from the boiler, dismantle and rinse thoroughly with clean water. Re-assemble the siphon in reverse order. Paramount three 30-115 kW 7308272-03 03.14...
1. Disconnect the electrical connection cables to the fan at the coupler 2. Pull off air hose from the fan 3. Pull the connector from the electrodes 4. Undo fixing screw (1) in the inlet silencer at the top of the Paramount 7308272-03 03.14 Paramount three 30-115 kW...
When re-fitting, new gaskets should be used, particularly for the the gas connect- ing pipe. 10.5 Protection against contact Danger of electric shock! To ensure shock-proof protection, all parts of the device to be screwed on, have to be screwed on correctly; especially the cover parts! Paramount three 30-115 kW 7308272-03 03.14...
Pressure controller Siphon Exhaust gas adapter with test openings Ignition transformer (under the lid) Intake muffler 10 Gas jet 11 Fan 12 Gas valve 13 Pump replacement pipe 14 Control LMS 15 EWM *) Accessories 7308272-03 03.14 Paramount three 30-115 kW...
Page 130
Exhaust gas adapter with test openings Ignition transformer (under the lid) Intake muffler 10 Gas jet 11 Fan 12 Gas valve 13 Pump replacement pipe 14 Control LMS 15 EWM 16 cleaning cover *) Accessories Paramount three 30-115 kW 7308272-03 03.14...
14. For cleaning the heat exchanger, rinse with soft water jet (without additives). 10.8 At the end of the maintenance work - After finishing the cleaning work, re-install heat exchanger and burner. - Check the nominal heat load and exhaust gas values. 7308272-03 03.14 Paramount three 30-115 kW...
- The ignition spark must not spark-over to the ionisation electrode. Installation position and electrode clearance has to be maintained according to Fig. 33 10.10 Fault switch-off Safety switch-off in case of flame failure during the operation. Paramount three 30-115 kW 7308272-03 03.14...
Page 133
- ionisation electrode has ground connection - no gas In spite of flame formation the burner goes on fault after expiration of the safety time: - Ionisation electrode defective or soiled. - Ionisation electrode does not penetrate the flame 7308272-03 03.14 Paramount three 30-115 kW...
Expansion module 1 fault (collective fault) Expansion module 2 fault (collective fault) Two time masters (LPB) Check time master Clock time master without backup Servicing message See maintenance code (press information button once) for detailed information Boiler temperature monitoring Paramount three 30-115 kW 7308272-03 03.14...
Page 135
Return sensor solar sensor fault Swimming pool sensor fault Flow temperature 3 Sensor fault Monitoring function Ned frequency outside of valid range DHW Charging temp sensor fault BX same sensors BX/e'module same sens BX/m'grp same sens 7308272-03 03.14 Paramount three 30-115 kW...
Page 136
2) Check parameter according to table Setting Table Heating Specialist and program basic settings or call-up internal LMS SW-diagnosis code and correct respective parameter fault according to fault information! 3) Switching off and interlock; can only be unlocked by reset Paramount three 30-115 kW 7308272-03 03.14...
Permitted fan run-on time Start prevention No internal or external release exists (e.g. no water pres- sure, lack of gas) Safety switch-off STOE Fault position The actual fault code is displayed, see fault code table 7308272-03 03.14 Paramount three 30-115 kW...
Page 138
Corrosion damage Legionella function Customer service; Telephone Liquid gas under ground Lock Device fuse -Operation DHW operation -Programming DHW temperature Diagnostics consumers Mains isolator Maintenance Maintenance Contract Emergency operation Maintenance message Error message Manometer Paramount three 30-115 kW 7308272-03 03.14...
Page 139
-Comfort setpoint -Reduced setpoint Safety valve Service message Set frost protection temperature Shortening Shut-off valve Software version Spare parts Standards State Strain relief fittings Summer/winter heating limit Supply pressure Time programme Topping up water 7308272-03 03.14 Paramount three 30-115 kW...