Operation
7.8 Servicing message
7.9 Emergency mode (Manual
control)
7.10 Restoring factory setting
48
If the maintenance sign
or the heating system is in special operation.
- Press information button (i)
- Further information can be called up (see section Maintenance code- table).
Note: The maintenance message has not been activated by the setting in the fac-
tory.
Activation of manual control. If the manual control function is activated the boiler
will be controlled to the Setpoint manual control. All pumps will be activated. Ad-
ditional request will be ignored!
1. Press OK button
2. Select menu point Maintenance/service
3. Press OK button
4. Select parameters Manual control (prog.-no. 7140)
5. Press OK button
6. Select parameter"On"
7. Press OK button
8. Leave programming level by pressing the operation mode button heating oper-
ation
The factory settings will be restored as follows:
1. Press OK button
2. Select Setting level Engineer (see section Programming at Programming proce-
dure)
3. Select menu point Operator section
4. Press OK button
5. Select parameters Operator section activate basic settings (prog.-no. 31)
6. Press OK button
7. Change setting to"Yes" and wait until setting returns to "No"
8. Press ESC button
9. Factory setting is restored
Note: You can find more information for adjusting parameters in the section Pro-
gramming.
Condensing gas boiler Eurocondense three125-300 kW
appears in the display, a maintenance message exists
7308536-02 06.13