WALL mountInG tEmPLAtE

note. The template shows the positions for the
top fixing holes. Care must be taken to ensure
the correct holes are drilled.
1. Tape template into the selected position.
2. Ensure squareness by hanging a plumbline.
3. Mark on to the wall:
a. The top 4 wall mounting plate screw
positions.
b. The 2 boiler lower fixing positions using
diagram below
c. The position of the flue duct. Mark
the centre of the hole as well as the
circumference.
4. Remove the template from the wall.
BOILER LOWER FIXING POSITIONS
Ø12mm
332mm
8

PREPARInG tHE WALL

ImPoRtAnt. Ensure that, during the cutting
operation, masonry falling outside of the building
does not cause damage or personal injury.
1. Cut the flue hole ensuring that the hole
is square to the wall. Both wall faces
immediately around the cut hole should be flat.
2. Drill 4 boiler top fixing holes with a 12mm
(
/
") masonry drill and insert the plastic plugs
1
2
provided, for the wall mounting plate.
3. Drill the 2 boiler lower fixing holes with a 12mm
(
/
") masonry drill, insert the plastic plugs
1
2
provided .
4. Fix the wall bracket into place with 4 M10x70
hex head coach screws provided.
EVOMAX -
Installation & Servicing
InStALLAtIon
note: Horizontal flue runs must be
inclined at 1.5-3
o
condensate to drain back to the boiler.
Vertical Offset From X mm
Y
X
Distance from flue centre line (Y) to outside wall surface.
For lengths greater than 4m, increase offset (X) by 26mm
for every additional 1m.
to the horizontal to allow
26
52
1m
2m
3m
4m
78
104
11