Group:am/Fm Terminal Adjustment Params - Toshiba TOSVERT-130 G3 Interface Manual

High performance transistor inverter true torque control drive series
Hide thumbs Also See for TOSVERT-130 G3:
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
Register
Function / Title
211
TOSLINE-S20 COMM
ERROR MODE
212
TOSLINE-S20 COMM
OPTION RESET
213
RS485/12-BIT BINARY
BIAS,GAIN
214
1
RS485/12-BIT
BINARY POINT #1
215
RS485/12-BIT
BINARY PT. #1
FREQ
216
RS485/12-BIT
BINARY POINT #2
217
RS485/12-BIT
BINARY PT. #2
FREQ
Note: Registers 1D0 ∼ 1D2 are not standard G3 parameters accessible via the LCD keypad. They are Modbus-
specific parameters that are only accessible via the Modbus network.

9.3.11 GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS

Register
Function / Title
218
FM TERMINAL
FUNCTION SELECTION
219
FREQUENCY METER
ADJUSTMENT
21A
AM TERMINAL
FUNCTION SELECTION
21B
CURRENT METER
ADJUSTMENT
Bank
Mask
1
0002
0000: Data cleared
0002: Data retained
1
0004
0000: No effect
0004: Reset
0 / 1
0020
0000: OFF
0020: ON
0000 ∼ 0064 (0 ∼ 100)
0 / 1
00FF
0000 ∼ Fmax (0 ∼ Fmax)
0 / 1
FFFF
0000 ∼ 0064 (0 ∼ 100)
0 / 1
00FF
0000 ∼ Fmax (0 ∼ Fmax)
0 / 1
FFFF
Bank
Mas k
0 / 1
FFFF
1194: Pre-comp ref. frequency
6686: Post-comp output freq.
1500: Frequency setting
2576: Output current
2689: DC voltage
5668: Output voltage
3684: Torque current
2688: Excitation current
7506: PID feedback value
0584: Motor overload ratio
0586: Inverter overload ratio
0588: DBR overload ratio
835C: Input power
835E: Output power
A000: Fixed output
2304: Peak output current
8302: Peak input voltage
0000 ∼ FFFF
0 / 1
FFFF
0 / 1
FFFF
Same as FM TERMINAL
FUNCTION SELECTION
0000 ∼ FFFF
0 / 1
FFFF
44
Adjustment Range
(0)
(1)
(0)
(1)
(0)
(1)
Adjustment Range
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
Multiplier
1
1
1
0.01
1
0.01
Multiplier
1