9.1 Write-Only Registers

Register
Bit
word
01
Frequency command
02
0
RUN command
1
STOP Command (has priority
over RUN command)
Forward • reverse run
2
selection
3
Acc/dec #1 / #2 selection
4
Reserved
5
Reserved
6
Reserved
7
Jog mode selection
8
Feedback control
9
Compulsory DC injection
braking mode
A
Fundamental parameter
switching
B
Gate block command
(coast stop command)
C
Emergency off command
D
Reset command
(trip clear)
E
Reserved
F
Reserved
word
03
Reserved
word
04
Reserved
Function
Bank
DPRAM
DPRAM
DPRAM
DPRAM
22
Mask
Adjustment Range
0.00 ∼ 400.00Hz
FFFF
Actual frequency will be
limited by LL, UL and Fmax.
0: Stop
1: Run
0: run enabled
1: stop
0: reverse
1: forward
0: Acc / dec #1
1: Acc / dec #2
0: Normal (acc/dec mode)
1: Jog mode
0: Feedback valid
1: Feedback invalid
0: No compulsory DC
injection braking
1: Compulsory DC injection
below DC INJECTION
START FREQUENCY
0: V/F #1
1: V/F #2
0: Normal
1: Gate block
0: Does nothing
1: Emergency off
0: Does nothing
1: Reset
Multiplier
0.01