efesotomasyon.com -Toshiba inverter,drive,servo,plc
ROM version is 6401. This version number will be used later in the installation
process. Option ROM version =
Record the standard ROM version number prior to option ROM installation. The
standard ROM version can be read from parameter ROM VERSION in
GROUP:UTILITY PARAMETERS.
Standard ROM version =
CAUTION!
2.
been turned OFF and are locked and tagged out.
DANGER!
3.
capacitors to discharge before proceeding to step 4. Do not touch any internal
parts with power applied to the inverter, or for at least 5 minutes after
power to the inverter has been removed. A hazard exists temporarily for
electrical shock even if the source power has been removed.
4.
Remove the inverter's cover (open the door on units with hinged doors).
Verify that the CHARGE LED has gone out before continuing the installation
process.
5. Loosen the 4 screws attaching the G3's operation panel support bracket to the
control board support bracket, and then remove the operation panel and support
bracket as a unit (refer to Figure 1).
operation panel
support bracket
operation panel support
bracket screws
.
Verify that all input power sources to the inverter have
Wait at least 5 minutes for the inverter's electrolytic
Figure 1: G3 with front cover removed