Mitsubishi Electric FR-D700 Instruction Manual page 94

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

Frequency setting by external terminals
REMARKS
During jog operation or PID control operation, the remote setting function is invalid.
Setting frequency is "0"
Even
when
frequency is cleared by turning on
the RL (clear) signal after turn off
(on) of both the RH and RM
signals, the inverter operates at
the remotely-set frequency stored
in the last operation if power is
reapplied before one minute has
elapsed since turn off (on) of both
the RH and RM signals
When the remotely-set frequency
is cleared by turning on the RL
(clear) signal after turn off (on) of
both the RH and RM signals, the
inverter operates at the frequency
in
the
remotely-set
cleared state if power is reapplied
after one minute has elapsed
since turn off (on) of both the RH
and RM signals.
When selecting this function, re-set the maximum frequency according to the machine.
Parameters referred to
Pr. 1 Maximum frequency, Pr. 18 High speed maximum frequency
Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 178 to Pr. 182 (input terminal function selection)
90
the
remotely-set
Acceleration (RH)
Deceleration (RM) OFF
Forward rotation (STF)
frequency
Acceleration (RH)
Deceleration (RM) OFF
Forward rotation (STF)
Remotely-set frequency stored last time
Within 1 minute
ON
Clear (RL)
ON
Power supply
ON
Remotely-set frequency
stored last time
More than 1 minute
ON
Clear (RL)
ON
ON
Power supply
CAUTION
Refer to page 78
Refer to page 108
Remotely-set frequency
stored last time
Time
ON
ON
ON
1 minute
Operation is performed
at the set frequency 0Hz.
Time
ON
ON
ON
Refer to page 91