Cables And Wiring Length - Mitsubishi Electric FR-D700 Instruction Manual

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

Main circuit terminal specifications
2.2.3

Cables and wiring length

(1) Applied wire size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to
decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
Three-phase 400V class (when input power supply is 440V)
Terminal
Applicable Inverter
Model
FR-D740-012 to 080
FR-D740-120
FR-D740-160
Single-phase 200V class (when input power supply is 220V)
Terminal
Applicable Inverter
Model
FR-D720S-008 to 042
FR-D720S-070
FR-D720S-100
∗1
The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes
that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
∗2
The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding
air temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in the United States.)
∗3
The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 70°C. Assumes that the surrounding
air temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in Europe.)
∗4
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
For single-phase power input, the terminal screw size indicates the size of terminal screw for L1, N, U, V, W, and a screw for earthing (grounding).
NOTE
Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit
or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit
breakage.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
16
Crimping
Terminal
Tightening
Screw
Torque
R/L1
Size
N·m
∗4
S/L2
U, V, W
T/L3
M4
1.5
2-4
M4
1.5
5.5-4
M4
1.5
5.5-4
Crimping
Terminal
Tightening
Screw
Torque
Size
N·m
∗4
L1
U, V, W
N
M3.5
1.2
2-3.5
M4
1.5
2-4
M4
1.5
5.5-4
1000
HIV Cables, etc. (mm
R/L1
Earth
S/L2
U, V, W
(ground)
T/L3
cable
2-4
2
2
2-4
3.5
2
5.5-4
3.5
3.5
HIV Cables, etc. (mm
Earth
L1
U, V, W
(ground)
N
cable
2-3.5
2
2
2-4
2
2
2-4
3.5
2
Cable Size
PVC Cables, etc. (mm
2
AWG
)
∗2
∗1
R/L1
R/L1
S/L2
U, V, W
S/L2
T/L3
T/L3
2
14
14
2.5
3.5
12
14
4
3.5
12
12
4
Cable Size
PVC Cables, etc. (mm
2
AWG
)
∗2
∗1
L1
L1
U, V, W
N
N
2
14
14
2.5
2
14
14
2.5
3.5
12
14
4
2
)
∗3
Earth
U, V, W
(ground)
cable
2.5
2.5
2.5
4
4
4
2
)
∗3
Earth
U, V, W
(ground)
cable
2.5
2.5
2.5
2.5
2.5
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents