Omron 3G3RX-V1 Series Connection Manual page 40

Devicenet connection guide
Hide thumbs Also See for 3G3RX-V1 Series:
Table of Contents

Advertisement

7.6.2.
Checking Data That Are Sent and Received
Confirm that the correct data are sent and received.
Always confirm safety at the destination node before you transfer a user
program, configuration data, setup data, device variables, or values in memory
used for CJ-series Units from the Sysmac Studio.
The devices or machines may perform unexpected operation regardless of the
operating mode of the CPU Unit.
The Inverter will run if you proceed to this section. Confirm safety before
operation. If you cannot confirm safety, do not proceed to this section after
completing until Section 7.6.1.
If you proceed to this section, make sure to complete all the steps and place the
Inverter in the safe state.
1
Select Watch Tab Page from the
View Menu.
2
The Watch Tab Page 1 is displayed
in the lower section of the Edit
Pane.
3
The following names are entered in
the Watch Tab Page for monitoring.
DN00_STA_IN[5]
DN00_STA_IN[6]
DN00_CMD_OUT[0]
DN00_DATA_OUT
4
Set the display format as follows:
DN00_STA_IN[5]: [Boolean]
DN00_STA_IN[6]: [Boolean]
DN00_CMD_OUT[0]: [Boolean]
DN00_DATA_OUT: [Decimal]
7.Connection Procedure
37