Summary Of Ul Requirements - NAPCO MAGNUM ALERT 1008e Installation Instructions Manual

Control panel / communicator
Table of Contents

Advertisement

Gentex 812, 812T, 812P, 812PT, 812PH, 8120, 8120T,
8120P, 8120PT, 8120PH
Hochiki SLG with YBC-RL4-RA Base
2-Wire
System Sensor 1400*, 2400*, 2400TH*, each with B101B
Base; 1451*, 2451*, 2451TH*, each with B401B Base
Subtract total smoke-detector alarm current from a available
standby current.
Horn:
Wheelock 34T-12R* (Rated at 85dB for indoor household
applications)
*Note: Devices not identified with an asterisk (*) require
optional power supply PS3002 for UL installations. Compati-
bility of detectors without "*" has not been evaluated by UL.
For Mercantile control panels (MA1008eM)
Bells:
Ademco AD8-12, AD10-12
Amseco MBL-8/12V, -10/12V
Mercantile Bell:
Ademco AB-12, Bell in Box
Speakers:
Ademco 713
Atlas Sound VT-158U

SUMMARY OF UL REQUIREMENTS

Note: The MA1008e may not be used for fire protection
where prohibited by local codes. The MA1008eM may not
be used for fire protection in any installation.
Residential
The following summarizes UL programming and wiring
requirements for Residential Household Fire and Burglary
installations.
• Recognized Limited-Energy Cable for initiating, indicat-
ing and supplementary circuits;
• Initiating loops supervised if longer than 3 feet;
• FT2200 End-of-Line Relay for Fire (if using 4-wire smoke
detectors);
• Minimum alarm timeout of 4 minutes;
• Maximum exit time: 60 seconds; maximum entry time:
45 seconds;
• Do not program Don't Wait for Handshake, Telco 1 & 2;
Swinger Shutdown; Force Arming; Group Bypass; 7mS
or 50mS Loop Response. Abort Delay may not exceed
45 seconds.
• Program Disable Callback Download; Disable Function
6 Download;
• Key Input on Zone 7 feature may not be enabled;
• Automatic dialer may not dial a police-station number
that has not been dedicated for such service;
• System must be tested at least weekly under AC battery
and battery-only conditions;
• Replace the rechargeable battery at least every 5 years;
• If the battery is heavily discharged, replace it or have it
tested by a qualified technician;
• Remote panic switches must be located in the same
room as the control unit and keypad. Wiring may not
L
NAPCO Security Systems
pass through any barrier;
• For silent panic, connect only to UL-Listed holdup de-
vices.
In California: CFM-Ilsted for residential use (Listing No.
7165-992:111).
Mercantile
The following summarizes UL programming and wiring
requirements for Mercantile installations.
• TRF11 (40VA) and RBAT6 (7AH) are required;
• Heavy-duty enclosure with door tamper (MA1008eM) is
required;
• Digital communicator must be utilized for Low Battery
reporting, but not Low Battery restore;
• Program Audible Test on Arming; Force-Arm Code; a
maximum exit delay of 10 seconds; Disable Display By-
pass; Auto-Reset;
• Do not use Fire Zones;
• Ademco AB12 Bell & Box is required.
MA1008e / 1008eM Installation Instructions