Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove
to Combustibles
See figs. 2-3.
Rear:
2" (51 mm) - measured from Draft Hood
Ceiling:
32 1/4" (819 mm) - measured from stove top
Corner:
3" (76 mm) - measured from stove top
Sides:
3" (76 mm - measured from stove top)
Minimum Clearances from the Vent Pipe to
Combustibles
Horizontal Run:
Top:
Off the top of the pipe
Sides: Off the sides and bottom 2" (50mm)
Vertical Run:
All sides: 1" (25 mm)
All vent components must be installed in accordance
with the manufacturer's instructions and within the
terms of their listing. Refer to the manufacturer's
instructions for approved clearances from the vent pipe
to combustible materials.
Minimum Alcove Dimensions
Maintain clearances to combustibles as noted above.
Width:
36" (914 mm)
Depth:
24" (610 mm)
Height:
61" (1550 mm)
Mantel Clearances -
Figure 4. Mantel and Trim specifications -
Stove installed flush with fireplace face.
2" (50 mm)
Stove shown with standard legs. With Short Legs, subtract 2 1/4" (51 mm)
from the clearances indicated below.
3"
(76 mm)
Figure 2. Parallel Installation Clearances.
Figure 3. Vent adaptor centerline at minimum clearance
to corner walls.
Figure 4a. Mantel specifications -
Stove recessed into fireplace no more than 6 1/2".
2"
(51 mm)
To Rear Wall
3"
(76 mm)
7