Commissioning
4.4 Restoring to defaults
Parameter
Access
level
P1003[0]
2
P2201[0]
2
P2202[0]
2
P2203[0]
2
4.4
Restoring to defaults
Restoring to factory defaults
Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset
Restoring to user defaults
Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset
After the setting for P0970, the inverter displays "8 8 8 8 8" and then the screen shows
"P0970". P0970 and P0010 are automatically reset to their original value 0.
48
Function
Fixed frequency setpoint 3
Fixed PID frequency setpoint 1
Fixed PID frequency setpoint 2
Fixed PID frequency setpoint 3
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 21: parameter reset to factory defaults deleting user defaults if
stored
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 1: parameter reset to user defaults if stored, else factory
defaults
Text menu
(if P8553 = 1)
(FIX F3)
(PID F1)
(PID F2)
(PID F3)
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127