Siemens SINAMICS V20 Compact Operating Instructions

Siemens SINAMICS V20 Compact Operating Instructions

Up to 30 kw
Hide thumbs Also See for SINAMICS V20:

Advertisement

SINAMICS
SINAMICS V20 Inverter
Compact Operating Instructions

Table of contents

1
Fundamental safety instructions ................................................................................................................................. 2
1.1
General safety instructions ...................................................................................................................... 2
1.2
Industrial security .................................................................................................................................... 2
2
Installation .................................................................................................................................................................. 3
2.1
Mechanical installation ............................................................................................................................ 3
2.2
Electrical installation ................................................................................................................................ 5
2.3
Technical specifications ......................................................................................................................... 14
3
Commissioning ......................................................................................................................................................... 15
3.1
The built-in Basic Operator Panel (BOP) ............................................................................................... 15
3.2
Quick commissioning............................................................................................................................. 17
3.2.1
Powering up and setting to factory defaults ........................................................................................... 17
3.2.2
Setting motor data ................................................................................................................................. 18
3.2.3
Setting connection macros .................................................................................................................... 18
3.2.4
Setting application macros .................................................................................................................... 21
3.2.5
Setting common parameters ................................................................................................................. 22
3.3
Restoring to defaults ............................................................................................................................. 22
4
Technical support information ................................................................................................................................... 22
Parameters, faults, and alarms ................................................................................................................................. 23
A.1
Parameter list ........................................................................................................................................ 23
A.2
Faults and alarms .................................................................................................................................. 30
General license conditions ........................................................................................................................................ 31
© Siemens AG 2016. All rights reserved
A5E37281078-003, 05/2016
1

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS V20

  • Page 1: Table Of Contents

    Setting common parameters ......................... 22 Restoring to defaults ..........................22 Technical support information ........................... 22 Parameters, faults, and alarms ..........................23 Parameter list ............................23 Faults and alarms ..........................30 General license conditions ............................31 © Siemens AG 2016. All rights reserved A5E37281078-003, 05/2016...
  • Page 2: Fundamental Safety Instructions

    With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered.
  • Page 3: Installation

    If condensation or conductive pollution can be excluded at the installation site, a lower degree of control cabinet protection may be permitted. Mounting orientation and clearance Note Install the inverter on a metal mounting plate in a control cabinet. The mounting plate has to be unpainted and with a good electrical conductivity. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 4 For FSAA/FSAB, you only need to drill these two holes for cabinet mounting. For push-through mounting only. For more information about the push-through mounting and the installation of the Flat Plate inverter, see the SINAMICS V20 Inverter Operating Instructions. SINAMICS V20 Inverter...
  • Page 5: Electrical Installation

    To reduce the risk of fire or electric shock, current-carrying parts and other components of the controller should be examined and the controller should be replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 6 Wiring diagram Note The resistance of the potentiometer for each analog input must be ≥ 4.7 kΩ. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 7 For detailed information about the permissible types, see the following tables in accordance with UL/cUL standards. Branch circuit protection according to UL/cUL standards You may operate the SINAMICS V20 on a branch circuit with the specified short-circuit current rating (SCCR) provided the specified branch-circuit protection device is installed as detailed in the following tables.
  • Page 8 Branch circuit protection with circuit breakers (DIVQ1/DIVQ7) Frame size Inverter power Maximum rated Circuit breaker type SCCR of SINAMICS V20 Minimum enclo- rating (kW) current of circuit with circuit breaker sure volume breaker (A) /cu. in.) 400 V 0.37 to 2.2...
  • Page 9 NCGA and HCGA are UL Listed 3VL11 series (Siemens type VL150x UL) circuit breakers; NDGA, NDGB, HDGA and HDGB are UL listed 3VL25 series (Siemens type VL150 UL) circuit breakers shown in the European circuit breaker cat- alog LV 16.
  • Page 10 3RV104.-4FA## UL/cUL listed (NKJH/NKJH7) Siemens CMCs of the same type with a current rating lower than that is specified in the table above corresponding to the inverter power rating, and with a voltage rating as well as an interrupting current rating at least equal to those of the supply circuit may be used.
  • Page 11 Terminal description SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 12 11 kW to 15 kW 10 mm 10 mm 18.5 kW (HO) 10 mm 6 mm 22 kW (LO) 16 mm 10 mm 22 kW (HO) 16 mm 10 mm 30 kW (LO) 25 mm 16 mm SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 13 EMC (RE/CE C2) compliant, first environment (residential area). RE/CE C2 refers to EMC compliance to EN61800-3 Category C2 for Radiated and Conducted Emissions. For the specifications of external line filters, refer to the SINAMICS V20 Inverter Operating Instructions. EMC (RE/CE C1) compliant, first environment (residential area). RE/CE C1 refers to EMC compliance to EN61800-3 Category C1 for Radiated and Conducted Emissions.
  • Page 14: Technical Specifications

    Chemical gases: class 3C2 (SO Climate class: 3K3 For more information about current deratings, see the SINAMICS V20 Inverter Operating Instructions. When the input voltage is below the rated value, current deratings are permissible and therefore the voltage-dependent speed and/or torque may be reduced.
  • Page 15: Commissioning

    Note: Jog mode is only available if the motor is stopped. Moves the selection up through a menu, increases a value or a setpoint. • Long press (>2 s) to quickly scroll up the values. • SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 16 Inverter is running (motor frequency may be 0 rpm). (flashing): Inverter may be energized unexpectedly (for example, in frost protection mode). Motor rotates in the reversed direction. Inverter is in HAND mode. (flashing): Inverter is in JOG mode. Menu structure SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 17: Quick Commissioning

    This section describes how to perform the quick commissioning through the setup menu. If you are used to commissioning the inverter by setting parameters of your choice in the parameter menu, refer to the SINAMICS V20 Inverter Operating Instructions for a detailed description.
  • Page 18: Setting Motor Data

    External control - Potentiometer with setpoint Both NPN and PNP can be realized with the same parame- ters. You can change the connection of the digital input com- mon terminal to 24 V or 0 V to decide the mode. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 19 Cn007 - External push buttons with analog control Cn008 - PID control with analog reference Note that the command sources are pulse signals. If a negative setpoint for the PID control is desired, change the setpoint and feedback wiring as needed. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 20 P1021[0] BI: Fixed frequency selection bit 1 - 722.2 722.1 722.2 P1022[0] BI: Fixed frequency selection bit 2 - 722.3 722.2 P1023[0] BI: Fixed frequency selection bit 3 - 722.3 P1040[0] Setpoint of the MOP SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 21: Setting Application Macros

    P1312[0] Starting boost Boost only effective when accelerating for the first time (standstill) P1311[0] Acceleration boost Boost only effective when accelerating or braking P1310[0] Continuous boost Additional boost over the complete fre- quency range SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 22: Setting Common Parameters

    +39 (02) 24362000 Brazil +55 11 3833 4040 India +91 22 2760 0150 Korea +82 2 3450 7114 Turkey +90 (216) 4440747 +1 423 262 5710 Further service contact information: Support contacts (https://support.industry.siemens.com/cs/ww/en/ps) Manual download (https://support.industry.siemens.com/cs/ww/en/ps/13208/man) SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 23: A Parameters, Faults, And Alarms

    [0] Factor for kWh to currency conversion [1] Factor for kWh to CO2 conversion r0043[0...2] Energy saved [kWh] r0050 CO / BO: Active command data set r0051[0...1] CO: Active inverter data set (DDS) r0052.0...15 CO / BO: Active status word 1 SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 24 Calculation of V/f control data Complete parameterization Calculation of controller settings only Calculation of equivalent circuit data P0507 Application macro 0 - 255 r0512 CO: Scaled filtered frequency P0604[0...2] Threshold motor temperature [°C] 0.0 - 200.0 130.0 SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 25 CO / BO: Digital input values P0727[0...2] Selection of 2 / 3-wire method 0 - 3 Siemens (start / dir) 3-wire (fwd / rev) 2-wire (fwd / rev) 3-wire (start / dir) P0731[0...2] BI: Function of digital output 1 0 - 4294967295 52.3...
  • Page 26 P1001[0...2] Fixed frequency 1 [Hz] -550.00 - 550.00 10.00 P1002[0...2] Fixed frequency 2 [Hz] -550.00 - 550.00 15.00 P1003[0...2] Fixed frequency 3 [Hz] -550.00 -550.00 25.00 P1004[0...2] Fixed frequency 4 [Hz] -550.00 - 550.00 50.00 SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 27 1 signal Signal name signal 00 Voltage reduced Current could not be applied 02 Voltage reduced Slope-filter started 04 Current less threshold Current-minimum 07 Speed could not be found P1210 Automatic restart 0 - 8 Disabled SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 28 [0] 6 [1] 8 9600 bps 76800 bps 19200 bps 93750 bps 38400 bps 115200 bps 57600 bps Index: [0] USS / MODBUS on RS485 [1] USS on RS232 (reserved) P2011[0...1] USS address 0 - 31 SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 29 0 - 3 No quick commissioning End quick commissioning with factory reset End quick commissioning End quick commissioning only for motor data P8553 Menu type 0 - 1 Menus with no text Menus with some text SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 30: Faults And Alarms

    Cavitation protection warn A535 Braking resistor overload A936 PID autotuning active A541 Motor data identification active A952 Belt failure detected Note that alarms cannot be acknowledged. They are cleared automatically once the warning has been rectified. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 31: B General License Conditions

    For Resellers: In order to avoid infringements of the license conditions by the reseller or the buyer these instructions and license conditions and accompanying CD – if applicable - have to be forwarded to the buyers. 1) Siemens License Conditions General License Conditions for Software Products for Automation and Drives...
  • Page 32 Clauses 5.1 and 5.2 with respect to the above parts of the E-SW. SINAMICS V20 Inverter A5E37281078-003, 05/2016...
  • Page 33 - its own programs or data containing RSW or parts thereof, in accordance with the relevant intended Type of Use and on the basis of the Siemens catalog valid at that time. In the event that the Licensee supplies the specified programs or data to third parties for their use, these parties shall be bound in writing to adhere to stipulations corresponding to those in Section 5, with respect to the R-SW parts contained therein.
  • Page 34 In most cases, Siemens provides this information on or with the device. In case Siemens is technically unable to do so, you may request a copy of this information against payment of shipping and handling charges.

Table of Contents