Commissioning
4.3 Quick commissioning
Connection macro settings:
Parameter
Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P1016[0]
Fixed frequency mode
P1020[0]
BI: Fixed frequency selection bit 0
P1021[0]
BI: Fixed frequency selection bit 1
P1001[0]
Fixed frequency 1
P1002[0]
Fixed frequency 2
P1074[0]
BI: Disable additional setpoint
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
38
Factory
Default for
default
Cn005
1
2
1
23
0
1
0
15
9
16
15
9
1
1
722.3
722.1
722.4
722.2
10
10
15
15
0
1025.0
21
21
52.3
52.2
52.7
52.3
Remarks
Terminals as command source
Fixed frequency + analog setpoint
ON / OFF
Fixed speed bit 0
Fixed speed bit 1
Fault acknowledgement
Direct selection mode
DI2
DI3
Fixed speed 1
Fixed speed 2
FF disables the additional setpoint
Actual frequency
Inverter running
Inverter fault active
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127