Table 8. Weights and Dimensions
Dimensions
(WxDxH)
Weights
Table 9. Battery
Configuration
EBM Configuration
Type
Charging
Monitoring
Table 10. Battery Runtimes (in Minutes)
UPS Internal
Load
6000 VA/4200W
5000 VA/3500W
4000 VA/2800W
3000 VA/2100W
2000 VA/1400W
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
EATON Powerware
UPS
44.2 x 68.3 x 21.8 cm
17.4" x 26.9" x 8.6" (5U)
UPS Chassis: 35 kg (77 lb)
Internal Battery Trays (2): 27.4 kg (60.5 lb) each
Total UPS Weight: 89.8 kg (198 lb)
(20) 12V, 7.2 Ah internal batteries
PW9125 240 EBM: (20) 12V, 9 Ah
Sealed, maintenance-free, valve-regulated, lead-acid
Internal battery: less than 2 hours to 80% usable capacity at nominal line voltage after
External battery: no more than 15x discharge time to 90% usable capacity at nominal
line voltage after full load discharge
Advanced monitoring for earlier failure detection and warning
1 EBM
Batteries
9.7
29.7
13.2
37.4
19.2
49.2
24.3
70.1
37.7
107.5
®
9125 Two-in-One UPS (5000/6000 VA) User's Guide
Extended Battery Module (EBM)
44.2 x 68.3 x 13 cm
17.4" x 26.9" x 5.1" (3U)
69.9 kg (154 lb)
full load discharge
2 EBMs
3 EBMs
52.1
76.3
65.3
95.6
85.8
125.4
121.9
178.0
186.2
271.4
S
164201513 Rev B
www.powerware.com
SPECIFICATIONS
4 EBMs
102
127.7
167.5
237.4
361.6