Eaton Powerware 9125 User Manual page 32

Two-in-one ups 5000/6000 va
Hide thumbs Also See for Powerware 9125:
Table of Contents

Advertisement

INSTALLATION
6.
7.
Table 1. UPS Wiring Specifications
UPS Terminal
Terminal
Block
Position
Input
1
2
3
No Connection
4
Output
5
6
7
2
* Use 2.0 mm
(14 AWG) 75_C copper wire minimum.
26
EATON Powerware
www.powerware.com
Connect the input and ground wires to the UPS terminal block
according to Figure 13 and Table 1.
Connect the output and ground wires to the UPS terminal block
according to Figure 13 and Table 1.
L2/Neutral In
L1 In
Input
Ground
Figure 13. UPS Terminal Block
UPS Wire Function
Input Ground
L1 In
L2/Neutral In
No Connection
L1 Out
L2/Neutral Out
Output Ground
®
9125 Two-in-One UPS (5000/6000 VA) User's Guide
No Connection
L1 Out
L2/Neutral Out
Terminal Wire
Tightening
Size Rating*
2
2.5–16 mm
1.8 Nm (16 lb in)
(14–6 AWG)
(14–6 AWG)
2
2.5–16 mm
1.8 Nm (16 lb in)
(14–6 AWG)
(14–6 AWG)
S
164201513 Rev B
Output
Ground
Torque
(
)
(
)