Eaton Powerware 9125 User Manual page 31

Two-in-one ups 5000/6000 va
Hide thumbs Also See for Powerware 9125:
Table of Contents

Advertisement

To hardwire the UPS:
1.
If you are installing power management software, connect your
computer to the USB port or UPS communication port (see
page 37). For the communication port, use only the serial cable
supplied in the accessory kit.
2.
Switch off utility power at the distribution point where the UPS will
be connected. Be absolutely sure there is no power.
3.
Remove the wiring access cover and the conduit landing plate and
retain (see Figure 12).
Punch holes in the conduit landing plate for the input and output
conduit using a Greenlee
Conduit Landing Plate
Wiring Access Cover
4.
Pull the input and output wires through separate conduit, leaving
approximately 0.5m (2 ft) of exposed wire. Attach a flexible metal
fitting to the end of each conduit.
5.
Insert each conduit through a wiring access entry and attach the
conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the
end of each incoming wire.
®
EATON Powerware
9125 Two-in-One UPS (5000/6000 VA) User's Guide
punch or similar device.
®
USB Port
Communication Port
Figure 12. Hardwired UPS Rear Panel
S
www.powerware.com
INSTALLATION
X-Slot Communication
Bay
REPO Connector
Battery Connector
Battery Circuit
Breaker
25
164201513 Rev B