Applications and Installation Details
Application example 1a
(Hydraulic system "2")
B9
Paramount
N3
N
Mains Supply
230V AC
B3 – Tank Sensor WWF (QAZ36)*
B5 – Room Control Module RRG (QAA73)*
B9 – Outdoor Temp Sensor (QAC34)
*
Available Optional Extra
Please note that when a RRG unit is used then the HKM (supplied with boiler) unit must be disconnected.
Application example 1d
(Hydraulic system "2")
B9
Paramount
N3
N
N6
Mains Supply
B3 – Tank Sensor WWF (QAZ36)*
B5 – Room Control Module RRG (QAA73)*
B9 – Outdoor Temp Sensor (QAC34)
*
Available Optional Extra
Please note that when a RRG unit is used then the HKM (supplied with boiler) unit must be disconnected.
1 pumped heating circuit (CTC) with remote room control module RRG (B5) or with boiler mounted control
HKM (N3) & EMS (Grasselin Time Clock), including hot-water tank temperature control WWF tank sensor
Hot Water
Cylinder
M1 – Heating Pump (CTC)
M3 – Hot Water pump
N – Control Module
1 pumped heating circuit (CTC) with remote room control module RRG (B5) or with boiler mounted control
HKM (N3) & EMS (Grasselin Time Clock), including hot-water tank temperature control WWF, with primary
loop (or hydraulic switch for Under floor heating).
Hot Water
Cylinder
230V AC
M5
M1 – Heating Pump
M3 – Hot Water pump
M5 – Primary Pump
B5
B3
Constant
Temp
Heating
Circuit
M1
M3
N3 – Heating Circuit module HKM
B5
B3
Constant
Temp
Heating
Circuit
M1
M3
B6
N3 – Heating Circuit module HKM
B6 – Flow Sensor QAD36*
N – Control Module
N6 – Temperature Module CITF* (for B6)
SECTION 3
PAGE 7
– Pump (Not Supplied)
– Isolating Valve (Not Supplied)
– Installer Wiring
– Non return valve
– Pump (Not Supplied)
– Isolating Valve (Not Supplied)
– Installer Wiring
– Low Loss Header (Not
Supplied)*
– Non return valve

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Paramount 60Paramount 80