POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PARAMOUNT
CONTROL CENTRE
Electrodes: To ensure proper function of the
ignition and ionisation, ensure that installation
length and spacings are observed as shown in
Fig.11.
The ionisation current should have the following
values for burner operation:
- at min. output > 5 µ A, DC (switching threshold at
0.7 µA, DC)
- at max. output > µA, DC
Ionisation Current Indicator: The current ionisation
current can be checked as follows directly in µA:
- on boiler module (1) under parameter "C 1"
- using room control module RRG (optional extra)
Function Description: Control and monitoring of
burner by BMU control centre with ionisation
electrode.
Automatic start-up according to program with
monitoring of flame formation
The operation itself can be varied using parameters
The display on the control panel indicates the
individual operating or program states with
numbers or letters (see Table 10)
Table 10 Operating Phases of Control Centre
Code "A 4"
0
Standby (no heat requirement)
1
Start disable
2
Fan start-up
3
Pre-purging time
4
Waiting time
5
Ignition phase
6
Safety time constant
7
Safety time variable
10
Heating operation
11
Hot water mode
12
Parallel operation for heating and hot water
20
Subsequent ventilation with last operating fan speed
21
Subsequent ventilation with pre-purging fan speed
22
Shut down
99
Fault position
Operating State
Reset: Following Reset (power OFF/ON) the BMU
control centre starts in the Home mode.
Fault Switch Off: Safety switch-off in the event of
flame failure during operation. After each safety
switch-off, a new ignition attempt is accomplished
according to program. If this does not lead to flame
formation, a fault shut-off is accomplished. In the
event of a fault shut-off, press the Reset button on
the control panel.
In the event of fault (red light) the numbers on the
display on the control panel indicates the cause of
the fault (see Table 11).
Burner Does Not Operate: No power to control
centre, e.g. no "Burner ON" signal from heating
circuit control (see Table 11).
Burner Goes to Fault: Without flame formation: No
ignition, ionisation electrode has short circuit to
ground, no gas. In spite of flame formation, burner
goes to fault after expiration of safety time:
Ionisation electrode defective or dirty. Ionisation
electrode not submerged in flame, boiler connected
with reverse polarity.
Function Description
Burner on standby
Self-test for burner start and fan start-up
Pre-purging fan deceleration time to starting load speed
Ignition and start of safety time
Flame formation, ionisation current build up
Room heating mode, burner in operation
Hot-water tank charging, burner in operation
Fan continues to run
Fan continues to run
Self-test after controlled shut-down
The current fault code is indicated, see Table 13