Potterton Paramount 40 Installation, Operation & Maintenance Manual page 22

Wall hung condensing boiler
Hide thumbs Also See for Paramount 40:

Advertisement

SECTION 5
PAGE 20
Display on room control module RRG
Progra
BUM parameter final user
m
level
No.
546
ZbreMinL
547
ZregiVerz
551
Kon
552
HydrSystem
553
KonfigHks
555
KonfigRg1
556
KonfigRg2
557
KonfigRg3
558
KonfigRg4
561
KonfigRg7
562
pH2Omin
563
PHOmax
584
ZkickFkt
596
ZeitAuZu
598
LmodRgVerz
604
LPBKonfigO
605
LPBAdrGerNr
606
LPBAdrSegNr
607
TbwBereit
614
KonfigEingang
615
KongigAusgang
618
KonfigEingangR
619
KonfigAusgang 1R
620
KonfigAusgang2R
621
KonfigAusgang3R
622
TanfoExtMax
623
PAnfoExtSchwelle
632
WanfoQ8
POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Function
Minimum running time for burner.
Control delay after burner start-up.
Constant for rapid reduction (without room influence)
Hydraulic system setting
Assignment of HKM or RRG to heating circuit (0...255), see
Table 11.
Adjustment codes
Adjustment codes
Adjustment codes
Adjustment codes
Adjustment codes
Min. boiler water pressure
Max. boiler water pressure
Time for pump output kick function
Running time for drive in heating circuit 2(CIM);30 to 873s
Output during control delay time
Adjustment code for bus module CIB
LPB application address for BMU
LPB segment address for BMU
Reduced setting for hot water
Programmable input F2
0 = Standard; 1 = Modem function
2 = Modern function "neg. logic"; 3 = Door veil
7 = not used on PARAMOUNT
Programmable output M5
0 = Standard; 1 = Signal output; 2 = Alarm output
3 = Operating signal; 4 = External transformer
(transformer T2); 5 = M5 (Q2Y2);
6 = DHW circulation pump; 7 = Door veil
8 = Primary loop pump M1; 9 = Primary loop pump M5;
10 = Basic function K2; 11= DHW loading
function (layer tank only); 12 = Analogue threshold
13 = control of flue gas flap
Programmable input on relay module CISP
0 – 3 = not available with CISP relay module
4 = temperature setpoint; 5 = heat output setpoint;
6 = sensor hydraulic switch
7 = not used on PARAMOUNT
Function of output 1 relay module CISP
0 = Standard; 1 = Signal output; 2 = Alarm output;
3 = Operating signal; 4 = External transformer
(transformer T2); 5 = M2 (Q2Y2)
6 = DHW circulation pump; 7 = Door veil
8 = Primary loop pump; 9 = Primary loop pump M 5
10-11 = not available; 12 = Analogue threshold
13 = control of flue gas flap
Function of output 2 relay module CISP
Setting possibilities as parameter 619
Function of output 3 relay module CISP
Setting possibilities as parameter 619
Max. value of heat demand in case of external temperature
setpoint (if param. 618 = 4)
Switchpoint of the analogue threshold
(% of max. value) (if parm. 618 = 4)
Heat demands to be satisfied by primary loop pump M5 (only
if param. 615 or 619 or 620 or 621= 9)
PARAMOUNT
Basic Setting
New
(set at factory)
Setting *)
0 s
2)
60 s
4
2
21
00110100
00000000 (not used)
00000100 (not used
01000000
00001110
0.7bar (
)
not activated
2.5bar (
)
not activated
2)
5 s
150 s
2)
25%
00010000
1 - -
0 - -
40°C
0
2
0
2
3
4
100°C
5%
b0.0, b1.0, b2.0,
b3.0, b4.0, b5.0,
b6.0, b7.0