POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PARAMOUNT
ADJUSTMENT TABLE FOR HEATING ENGINEERS
Table 6 – Setting system dependent parameters in heating engineer level of control centre BMU (with RRG room control module or RRG
service module).
Procedure for changing parameters:
• press info button, then press +/
appears on the display (final user level, only parameters with "X" are displayed)
• Select heating specialist level: Press both buttons
(Level for heating specialist)
• Select the desired program no. by pressing the programming keys.
• Set the desired value by pressing the +/- keys.
• After selecting the next program No. the new value is taken over.
• Press the info. button to quit the programming level.
Display on room control module RRG
Program
BUM parameter final
user level
No.
501
TrSmin
502
TrSmax
503
TkSmin
504
TkSmax
505
TkSnorm
506
TvSmin
507
TvSmax
510
TuebBW
511
TkSfrostEin
512
TkSfrost Aus
514
TruebVor
516
THG
517
dTbreMinP
519
TiAussen Norm
520
dTrAbsenk
521
dTkTrNenn
523
SdHzEin
524
SdHzAusMin
525
SdHzAusMax
526
SdBwEin1
527
SdBwAus1Min
528
SdBwAus1Max
529
SdBwEin2
SdBwAus2Max
531
532
Sth1
533
Sth2
534
DrR1
535
DrR2
536
NhzMax
537
NqmodNenn
538
NqmodMin
539
NqmodMinBw
541
PhzMax
542
PminHuKw
543
PmaxHuKw
544
ZqNach
545
ZbreMinP
5
6
or +/
buttons until "Initialise BMU parameters"
5
6
and
for longer than 3 sec until the display "Initialisation BMU specialist" appears
Min. room temperature setting
Max room temperature setting
Min. boiler temperature setting
Max. boiler temperature setting.
Boiler temperature setting at standard outdoor temperature
Min. flow temperature setting 2
Max. flow temperature setting 2
Boiler temperature setting increase for hot water charging
Boiler frost protection switch on temperature
Boiler frost protection switch off temperature
Boiler temperature setting increase for VTC
X
Summer/winter switchover temperature
Max. control difference for termination when minimum pause
time is exceeded.
Standard outdoor temperature
X
Reduction of room temperature setting when timer is
connected (HKM + EMS)
Flow/return temperature spread at standard outdoor
temperature
Switch on difference – burner in heating mode
Min. switch off difference – burner in heating mode
Max. switch off difference – burner in heating mode
Switch on difference – burner in hot water mode on sensor 1
Min. switch off difference – burner in hot water mode on
sensor 1.
Max. switch off difference – burner in hot water mode on
sensor 1.
Switch on difference – burner in hot water mode on sensor
2.
Max switch off difference – burner in hot water mode on
sensor 2
X
Heating curve steepness, heating circuit 1
X
Heating curve steepness, heating circuit 2
X
Correction, room temperature setting, heating circuit 1
X
Correction, room temperature setting, heating circuit 2
Max. speed at max. output in heating mode
Speed stage at heating system design point
Min. pump speed for heating system
Min. pump speed for layer tank charging
Max. degree of modulation in heating mode
Min. boiler input in kW (Hu)
Max. boiler input in kW (Hu)
Pump overrun delay time, max 218 min.
Minimum pause time for burner
Function
nd
heating circuit
nd
heating circuit
SECTION 5
PAGE 19
Basic Setting
New
(set at factory)
settings *
10°C
30°C
20°C
85°C
5)
80°C
20°C
70°C
18°C
5°C
10°C
10K
20°C => 17°C
30K
-20 °C
5)
10K
5)
20K
2)
4 K
2)
5 K
2)
5 K
2)
4 K
2)
2 K
2
2 K
)
2)
3 K
2)
3 K
1)
25
1)
25
0 K
0 K
rpm
6100 or 5400
5)
30
5)
34%
40% (not activated)
3)
100 or 90 %
3)
9,14 or 20 kW
3)
38, 58 or 77 kW
10 min
2)
120 s