FAULT MESSAGES
Table 11 Fault Messages (display 13 flashing)
Display
flashing
(Code No)
10
Outdoor temperature sensor short circuit or discontinuity
20
Boiler flow sensor short circuit or open circuit
40
Boiler return sensor short circuit or open circuit
50
Hot water sensor 1 short circuit or open circuit
52
Hot water sensor 2 short circuit or open circuit
61
Fault, room control module RRG
62
Wrong room control module connected
81
Short circuit on LPB bus or no bus feed
82
Address conflict on LPB bus (EUROCONTROL)
91
EEPROM data loss
92
Hardware error
100
Two time master
110
Limit stat tripped
111
Max. temperature tripped
119
Water pressure switch tripped
132
Safety switch off
133
No flame detected (no flame message after expiration of
safety time)
134
Flame failure during operation
135
Incorrect air supply
140
Impermissible LPB segment number or equipment number
148
Incompatibility between LPB interface basic unit
151
Internal error in BMU
152
Error in BMU parameter settings
153
PARAMOUNT disabled
154
Temperature fault
160
Fan speed error
161
Max. speed exceeded
180
Chimney sweep function active
181
Controller stop mode active
183
PARAMOUNT in parameter setting mode
bu
Faulty connection between Control unit and LMU
Display of 3-digit error messages: The 1 in the number 100 is displayed alternately with the 10's position
1)
Switch off and disable; can be enabled only with reset
2)
Switch off, start prevention; starts backup after fault disappears
3)
Check parameters according to Table 8 and program basic settings or
check value "b 0" (internal BMU-SW diagnostic code, Table 5) and correct parameter error according to error specification!
4)
Error display only, no switch off.
POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Description
Explanations
Possible caused and function sequence
Check connection and outdoor temperature sensor
Check connection 2)
Check connection 2)
Check connection; emergency operation 2)
Check connection 2) (not present)
Check room control module RRG
Connect compatible room control module
Check bus
Check addresses of connected control modules
Internal BMU error, process sensor, change BMU
internal BMU error, process sensor, change BMU
Check EUROCONTROL time master
Allow unit to cool dow n and reset. If fault occurs several
times, notify heating engineer 1) temperature stat open
circuit (possible short circuit in gas valve) 3)
No heat requirement, pump defective, radiator valves closed
Check water pressure and add water if required 2)
e,g, contact F7 open (Pressure Switch)
Possible low gas pressure
Reset, if fault occurs a number of time, notify heating
engineer, insufficient gas 9see Page 20) check polarity of
line power connection, ignition electrodes and ionisation
current 1) 2)
Automatic restart attempt by PARAMOUNT
Fan speed above or below speed threshold 2)
Check setting on EUROCONTROL
Check setting on EUROCONTROL
Check parameters (Tables 5 and 6) heating engineer 1) 2)
Repeat parameter settings
Press reset button 1)
1.
Boiler temperature rises too fast.
2.
Return temperature higher than flow temperature
3.
Return temperature more than 50°C below flow temp,
check water flow through boiler.
4.
Parameter incorrectly set (tables 5 & 6) check
parameters 1) 3)
Fan speed not reached 1)
Max. fan speed exceeded
4)
4)
1)
Check wiring in-between and replace control unit if
necessary