Download Print this page

Potterton Paramount 40 Installation, Operation & Maintenance Manual page 31

Wall hung condensing boiler
Hide thumbs Also See for Paramount 40:

Advertisement

POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PARAMOUNT
Heating Circuit Module HKM (Fig.7) Supplied
with the PARAMOUNT
Operation without Outdoor Temperature Sensor:
-
Boiler temperature setting on heating circuit
control
-
Hot water temperature setting on hot-water
control
Operation with Outdoor Temperature Sensor:
-
Room temperature setting on heating circuit
control
-
Hot water temperature setting on hot water
control.
Automatic Summer/Winter Switchover:
With the automatic Summer/Winter switchover
button it is possible to switch back and forth
manually
between
Summer
Automatic mode.
LED "Auto"
LED "Auto"
O
LED
O
*) For example the display for winter mode is active
(• = active) depending on the automatic setting.
Room Control Module RRG (Fig 8)
With the room control module (optional extra) you
can
-
control the functions from the room (remote
control)
-
make settings (e.g. your own timer programs)
-
call up information (e.g. temperature values)
etc.
All possibilities are described in the instructions
included with the room control module. Only a few
of the most important functions are described
below.
Presence Button
With the Presence button you can manually
manipulate
the
set
program):
"Sun"
symbol:
Heating
-
temperature.
"Moon" symbol: Heating operates at reduced
-
temperature
The Presence button is effective until the timer
program switches the next time.
The Presence button has no effect on the hot water
heating!
Temperature Knob
You can readjust the set temperature with the
temperature knob. One increment corresponds to
approx. 1°C. Before changing the temperature
and
Winter
LED "Auto"
O
LED
LED
o OR • *)
timer
program
(heating
operates
at
setting
on
thermostatic valves to the desired temperature.
Correct again only after the temperature has
adapted.
Temperature Sensor in Room Control Module
The temperature sensor integrated into the room
control module is effective only when the room
influence is enabled on the PARAMOUNT.
Error Messa ges
No display: - Faulty connection from room control
module to PARAMOUNT
- PARAMOUNT switched off or no mains
- Room control module defective
- Room control module and PARAMOUNT not
compatible
and
Display OFF - PARAMOUNT not set to "Automatic
mode"
Display ---: No sensor present or sensor defective.
SERVICE
Cleaning: The heat exchanger and burner should
be cleaned by a certified gas installer. Before
starting the work, shut off the gas shut-off device
and the hot water shut-off valves and disconnect all
power to the boiler.
Condensate Trap: The condensate trap should be
cleaned every one to two years. For this purpose,
loosen the threaded fitting on the trap and pull the
trap off downward. Completely remove the trap
together with hose from boiler, disassemble and
rinse with clear water.
opposite order.
Replacing Air Vent: Ensure that the air vent is
replaced only with genuine replacement part when
defective to ensure optimum venting!
Removing Gas Burner: Burner: Before cleaning
the heat exchanger, remove the gas burner. For
this purpose, disconnect the electric connections to
the fan at the plug connector, pull the air hose off
the
fan
and
set
electrodes.
Remove silencer
Disconnect threaded fittings for g as connection
pipe on mixing duct and on gas valve. Remove
gas connection pipe and gas injector. Loosen
the 5 mounting nuts on the mixing duct/heat
exchanger.
together with mixing duct and fan.
Clean burner pipe with soft brush.
When installing, use new gaskets, particularly for
the gas connection pipe.
SECTION 6
the
temperature
knob,
Reinstall the trap in the
disconnect
the
plug
Pull
burner
out
PAGE 29
set
the
from
the
toward
front

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Paramount 60Paramount 80