Potterton Paramount 40 Installation, Operation & Maintenance Manual page 24

Wall hung condensing boiler
Hide thumbs Also See for Paramount 40:

Advertisement

SECTION 5
PAGE 22
Turning off S/W changeover: The automatic S/W
changeover
feature
difference of + 1K.
If a temperature of equal to or
greater than 30°C is set. in program No.516,
changeover is not accomplished.
519 (TiAussen/Norm) (modulating pump only):
NOT REQUIRED U.K.
ADJUSTING HEATING CURVE
520 (dTrAvsenk) Night Setback room temperature
setting: The room temperature setting is reduced by
the value set here by a connected timer (e.g. EMS) in
night setback mode. Adjustment range 0 to 10K the
room temperature setting made here is included in
calculating the boiler temperature setting when
outdoor compensation control is used.
521 (dTkTrNenn) (modulating pump only): NOT
REQUIRED IN THE U.K.
532
(Sth1)
bzw.
533
steepness HC1 or 2: When used without the room
control module RRG the steepness of the heating
curves can be set here for the CTC (HC 1) or VTC
(HC 2). Note: When used with a RRG, the heating
curves in the RRG are effective and can be set there!
Standard value for heating curve (delivery state): The
settings at the heating engineer level for the BMU
control centre can be made with the room control
module RRG.
The parameters, which can be set are shown in
Table 5.
The factory settings for the heating curve as follows:
- CT heating circuit 25 and
- VT heating circuit 25 (See below)
The heating curve can be adjusted as follows,
depending on the system equipment.
with room control module RRG: On heating
-
engineer level for RRG program No.70 or 80.
The
values
from
parameters "532" and "533"!
with heating circuit module HKM: On boiler
-
module parameter "P 5" or with RRG as
service unit (Table 5)
534
(DtR1)
and
(DtR2)
temperature
setting
parameters shift the heating curve for heating circuit
1 and 2 parallel. If the room temperature setting is
not achieved with the heating curve set, this allows
adaptation. (See table below)
POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
operates
with
a
switching
(Sth2)
Heating
the
RRG
write
Correction
of
HC1
and
2: These two
536 (NHZmAX) Fan maximum speed for output
adjustment of Paramount: The maximum boiler output in
the heating mode can be limited by reducing the speed of
the fan to the desired output. For this purpose, set the
maximum speed in program no. 536 (NhzMax) and
program no.541 (PhzMax) according to Table 9.
Table 7: Max boiler output in heating mode (guide values)
Model
Paramount 40
curve
Paramount 60
Paramount 80
537 (NqmodNenn) Speed stage at design point of
heating system: NOT REQUIRED IN THE U.K.
538 (NqmodMin) Min pump speed for heating system:
NOT REQUIRED IN THE U.K.
541 (PhzMax) Degree of modulation in heating
mode: In order to ensure optimum operation of the
PARAMOUNT, it is necessary to adapt the PWM
signal (% increments) for the max. degree of
modulation in the heating mode to the maximum
speed, program No. 536 (NhzMax) (see Table 7).
over
SETTINGS FOR THE BURNER
542 (PminHuKw) Min boiler input in kW: Differ
depending on type of boiler:
PARAMOUNT 40 → 9kW or
PARAMOUNT 60 → 14 kW or
room
PARAMOUNT 80 → 20 kW
543 (PmaxHuKw) Max boiler input in kW: Differ
depending on type of boiler:
PARAMOUNT 40 → 38 kW or
PARAMOUNT 60 → 58 kW or
PARAMOUNT 80 → 77 kW
Programs No. 542 and 543 serve only for indication
of the specific boiler output (no function) and
balancing the output when the cascade controller
EUROCONTROL BCA 2 is used.
PARAMOUNT
Max heat load
Para 536 rpm
32
4900
22
3300
11
1700
50
4900
45
4400
40
3900
60
4750
50
3950
40
3150
Para 541 %
75
44
18
76
69
60
80
67
53

Hide quick links: