11.0 Specifications

Table 7:
Specifications
Operating Voltage
Standby Current
Receiver Alarm
Current
Range (the distance
between the
transmitter and
receiver)
Spacing (the distance
between the systems)
Pointability
Sensitivity
Alarm Contacts
Trouble Contacts
Auxiliary Alarm
Contacts:
Tamper
System Signaling
Signal Delay
Temperature
Mounting
Listings
and Approvals
Standard
Accessories
Optional
Accessories
Bosch Security Systems, Inc. | 09/06 | 31344F
D296: 18.0 VDC to 32.0 VDC
D297: 10.2 VDC to 15.0 VDC
D296 Receiver: 45 mA at 24 VDC
D296 Transmitter: 20 mA at 24 VDC
D297 Receiver: 50 mA at 12 VDC
D297 Transmitter: 20 mA at 12 VDC
D296: 70 mA maximum
D297: 75 mA at 12 VDC
30 ft to 350 ft (9 m to 107 m)
Allow no more than 60 ft (18 m) between systems. Spacing of 60 ft (18 m) is confirmed by
Underwriters Laboratories, Inc. (UL) testing.
Internally pointable optics for ±90° horizontal, and ±10° vertical adjustment.
Field selectable for 20%, 30%, 40%, 50%, 60%, or 70% beam obscuration.
Normally Open (N/O) contacts rated 1 A, 60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive loads.
Normally Closed (N/C) contacts rated 1 A, 60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive loads.
Form "C" (N/O, C, N/C) contacts rated 1 A, 60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive loads.
Receiver: Access door tamper switch in series with trouble contacts.
Transmitter: When the cover is removed, the cover tamper switch interrupts transmission.
Conventional four-wire system. Do not use with systems incorporating an alarm verification feature.
Fire: Selectable 30 sec or 5 sec
Trouble: 20 ± 2 sec
Storage and operating temperature range is -22°F to +130°F (-30°C to +54°C). For UL Listed
installations, the range is +32°F to +130°F (0°C to +54°C).
The detectors are designed for mounting to 4-in. (10-cm) square or octagonal electrical boxes
(not supplied).
C-UL-US
S3019
MSFM
Permit #1943
NY City MEA
Acceptance #MEA274-93-E
CSFM
#7260-1062:106
FM
Job #OX2A9.AY
CE
D306 Remote Test Indicator Plate and Test Cable
D307 Remote Test Indicator Plate
D308 Field Test Kit
D309 Alignment Light
D1005 Test Cord
D296/D297 | Installation Instructions | 11.0
Specifications