Quick Start Installation Flowchart - Bosch D296 Installation Instructions Manual

Long-range beam smoke detectors
Hide thumbs Also See for D296:
Table of Contents

Advertisement

D296/D297 | Installation Instructions | 10.0 Quick Start Installation Flowchart

10.0 Quick Start Installation Flowchart

Figure 19: Quick Start Installation Flowchart
Start
TX = Transmittter
RX = Receiver
• Mount TX and RX
according to
Section 4.0 Mounting
on page 5 and the
applicable fire codes.
• Apply power to the TX
and RX.
• Go to the TX.
• No LED = No power.
• LED steadily on = Not
seeing the TX.
• Flashing yellow LED =
Invalid sensitivity
setting (refer to Table 3
on page 8).
• Recheck the RX
alignment and clear
the beam path.
• Attach the test cord
through the access
door.
• Press the Setup
button to begin the
2-min Learn Mode.
• Do not block either
the TX or RX during
this mode.
• Is the
green LED
flashing?
• Is the meter
voltage between
3.8 VDC and
4.2 VDC?
14
• At the TX, press the
Aim Mode button.
• At the RX, set the
sensitivity according to
Table 3 on page 8.
• Point the RX at the TX
using its alignment
sight for the initial
adjustment.
• Is the
green LED
on the RX
flashing?
No
• Are the red and
yellow LEDs on
the RX
steadily
on?
• Remove the test cable
and replace the outer
cover.
• Remove the access
door.
• Press the Setup button
again.
No
• If still unsuccessful,
recheck the RX
alignment.
• Alignment is complete.
• Remove the test cable.
• Connect the D307
Yes
Remote Test Indicator
Plate to P6, if used.
• Replace the access
door.
• The green LED is off.
Is the
green LED
No
on the TX
• The green LED is
blinking?
Yes
• Point the TX at the RX
using the alignment
sight.
• Fine tune using the
Allen wrench
(supplied).
• The TX alignment is
complete.
• Replace the housing
and access cover.
• Go to the RX.
Yes
• Attach the test cord to
Terminals 2 and 3 of
the P6 connector
(refer to Figure 14 on
page 8).
• Check the voltage
using 20,000 Ω/VDC
VOM.
• Optimize the voltage
reading according to
Figure 15 on page 9
.
Use the Allen wrench
to fine tune.
Verify the operation
using the test filters
(supplied).
End
Bosch Security Systems, Inc. | 09/06 | 31344F
Check the power.
steadily on.
Call Bosch.