Testing New Batteries - Powerware 5115 User Manual

500–1400 va
Hide thumbs Also See for 5115:
Table of Contents

Advertisement

Use the following steps to replace the batteries:
1.
Pull the top left corner forward and remove the front panel.
2.
Slide up and remove the metal battery cover.
3.
500 unit. Disconnect the red battery cable and then disconnect the black battery
cable. Pull the battery out onto a flat, stable surface.
4.
750 - 1400 VA units. Disconnect the red battery cable and then pull the battery
out onto a flat, stable surface. Disconnect the black battery cable to the UPS as
shown.
5.
Replace the battery. See "Recycling the Used Battery" for proper disposal.
6.
Connect the black battery cable to the new battery and then connect the red
battery cable.
7.
Reinstall the battery.
8.
Reinstall the metal battery cover and front panel.

Testing New Batteries

NOTE
It is recommended that the batteries charge for 6 to 24 hours before testing.
Press and hold the
automatically distributes the load to the batteries for 15 seconds and tests the battery' s
performance. If there is a problem with the battery, the alarm beeps, the
illuminates and the
battery is fully charged.
1015715
Revision B
button for three seconds to initiate a self-test. The UPS
indicator flashes. Check the battery connections and be sure the
User's manual
500 - 1400 VA
indicator
15