Unit Economizer Control (Eca) Test Proce; Dures; Electromechanical Control; Troubleshooting Procedures For Direct Drive - Trane YSC037E Installation & Operation Manual

Packaged rooftop air conditioners precedent — gas/electric 3 to 10tons – 60 hz
Table of Contents

Advertisement

Troubleshooting
Unit Economizer Control (ECA)
Test Procedures

Electromechanical Control

This series of tests will allow you to diagnose, and
determine where, and if a problem exists in the system
economizer operation.Test 1 determines if the problem is
in the Unit, or if it is in the ECA.Test 2 tests sensor inputs.
Test 3 tests the resistors and sensors. Conduct the tests in
numerical order until problem is found.
Test 1
Verifying that the economizer actuator (ECA) is functional:
1. Using the "Test Mode" described in the "System Start-
Up" section, put the unit into the economizer mode
and verify that the economizer actuator (ECA) drives
fully open (approximately 90 seconds).
2. If the ECA is not driving the dampers, verify that 24VAC
is between the ECA terminalsTR andTR1 is present. If
24 volts is not present, a wiring or terminal problem
exists from the control transformer. Make any
necessary repairs, see wiring diagrams to
troubleshoot.
3. If 24 VAC is present, adjust the minimum position
potentiometer fully clockwise. If the actuator does not
drive, the economizer actuator is bad. Replace the ECA.
Test 2
Testing the ECA resistors and sensors
1. Testing the Mixed Air Sensor (MAS). Disconnect the
wires connected toT andT1 on the ECA, and;
a. Measure the resistance of the sensor between the
wires 180B and 181B.
b. Measure the temperature at the MAS location.
Using theTemperature versus Resistance chart,
verify the accuracy of the MAS.
Replace the sensor if it is out of range.
2. Testing the Outdoor Air Switch. If the temperature is
above 60 degrees, it will need to be chilled. Measure
the resistance of the sensor on the ECA SO and +.
The resistance should be approximately 390 Ohms.
Replace the Switch if it is open.
Replace the ECA if it is out of range.
3. Testing the R1 Resistance.
Measure the resistance of the sensor on the ECA SR
and +.
The resistance should be approximately 420 Ohms.
Replace the ECA if it is out of range.
4. Testing the R2 Resistance.
Measure the resistance of the sensor on the ECA P and
P1.
66
The resistance should be approximately 130 Ohms.
Replace the ECA if it is out of range.
Troubleshooting procedures for
Direct Drive Plenum Fan
Prior to troubleshooting, verify all wiring and wiring
connections.The motor has internal protections that will
shut down the motor before damage occurs. A power
cycle is required to reset some of the internal protections.
Before proceeding, power down unit for 1 minute and then
power on.
Please follow steps sequentially unless directed differently
in solution.
Refer to RT-SVB90*-EN for a Comprehensive
Troubleshooting Guide.
RT-SVX21P-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ysc060eYhc036eYsc067eYhc037eYhc072eYsc072f ... Show all

Table of Contents