Note: Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
Note: Ensure that the wiring between controls and the
unit's termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
•
Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
•
Route low voltage wiring per illustrations on page 38.
DC Conductors
Table 6.
Zone sensor module wiring
Distance from Unit to Control
0 - 150 feet
0 - 45.7 m
151 - 240 feet
46 - 73.1 m
241 -385 feet
73.5 - 117.3 m
386 - 610 feet
117.7 - 185.9 m
611 - 970 feet
186.2 - 295.7 m
Figure 40. Typical field wiring diagrams for
electromechanical
RT-SVX21P-EN
Recommended Wire Size
22 gauge
.33 mm2
20 gauge
.50 mm2
18 gauge
.75 mm2
16 gauge
1.3 mm2
14 gauge
2.0 mm2
Figure 41. ReliaTel™ conventional thermostat field
wiring diagrams
Figure 42. ReliaTel™ options module
Figure 43. ReliaTel™ relative humidity sensor
(dehumidification option)
Installation
RTRM
37