Note: Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
Note: Ensure that the wiring between controls and the
unit's termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
Route low voltage wiring per illustrations on page 38.

DC Conductors

Table 6.
Zone sensor module wiring
Distance from Unit to Control
0 - 150 feet
0 - 45.7 m
151 - 240 feet
46 - 73.1 m
241 -385 feet
73.5 - 117.3 m
386 - 610 feet
117.7 - 185.9 m
611 - 970 feet
186.2 - 295.7 m
Figure 40. Typical field wiring diagrams for
electromechanical
RT-SVX21P-EN
Recommended Wire Size
22 gauge
.33 mm2
20 gauge
.50 mm2
18 gauge
.75 mm2
16 gauge
1.3 mm2
14 gauge
2.0 mm2
Figure 41. ReliaTel™ conventional thermostat field
wiring diagrams
Figure 42. ReliaTel™ options module
Figure 43. ReliaTel™ relative humidity sensor
(dehumidification option)