Page 1
Installation, Operation, Maintenance Voyager™ Commercial 27.5 to 50 Ton 60 Hz 22.9 to 41.7 Ton 50 Hz CV or VAV Rooftop Air Conditioners with ReliaTel™ Controls, R-410A Refrigerant Model Numbers “B” and later design sequence TC*, TE*, YC*330B, 360B, 420B, 480B, 600B (60 Hz/3 phase) TC*, TE*, YC*275B, 305B, 350B, 400B, 500B (50 Hz/3 phase) SAFETY WARNING Only qualified personnel should install and service the equipment.
CFCs such as HCFCs and HFCs. Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures.
Warnings, Cautions and Notices Overview of Manual One copy of the appropriate service literature ships inside the control panel of each unit. The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians. Note: Do not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws.
No Heat (TC only) Low Heat (YC only) Digit 14 — Supply Air Fan Drive Digit 22 High Heat (YC only) Selections Trane Communication Low Heat-Stainless Steel Gas Interface (TCI) 550 RPM 500 RPM Heat Exchanger (YC only) High Heat-Stainless Steel Gas...
Page 9
Model Number Descriptions Discharge Temperature Sensor Clogged Filter Switch Digit 32 — Dehumidification Option Modulating Hot Gas Reheat Model Number Notes All voltages are across the line starting only. 2. Option includes Liquid, Discharge, Suction Valves. 3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 &...
Model Number Descriptions 50 Hz Description Throwaway Filters Trane Communication 4” (102 MM) MERV 14, High Eff, Interface (TCI) Throwaway Filters Digit 23 Digits 1, 2 – Unit Function Digit 13 – Supply Fan Motor, HP Ventilation Override TC = DX Cooling, No Heat 7.5 Hp (5.6 kW)
General Information Commonly Used Acronyms/Abbreviations Building Automation System Cubic Feet per Minute Cooling Valve (Reheat only) COMM Module Designation for TCI/LCI Constant Volume Clockwise Counterclockwise Direct Space Pressure control Discharge Air Sensor Daytime Warm-up Exhaust Air Economizer Actuator Entering Evaporator Temperature Sensor Fresh Air Fan Failure Switch Integrated Comfort System (See BAS)
ReliaTel Options Module RTRM ReliaTel Refrigeration Module Supply Air Space Pressure Calibration Solenoid Space Pressure Transducer Static Pressure Transducer Trane Communication Interface Temperature Cutout Temperature Discharge Limit Variable Air Volume Variable Frequency Drive Ventilation Heat Relay (VAV box relay) W.C.
Skin Contact - Wash affected areas gently with soap and warm water after handling. An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
Downflow Models Only: • An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide. •...
Pre-Installation Field Installed Control Wiring (Figure 19, p. 41 Figure 20, p. 42.) Important: All field-installed wiring must comply with NEC and applicable local codes. • Complete the field wiring connections for the constant volume controls as applicable. Refer to “Low Voltage Wiring”...
These clearances are necessary to assure adequate serviceability, cataloged capacities, and peak operating efficiency. If the clearances available on the job site appear to be inadequate, review them with your Trane sales representative.
Page 17
Unit Dimensions and Weights Figure 1. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat) Figure 2. Rear view showing duct openings for horizontal units 1 1/4 3 1/4 (32) (81) RT-SVX34C-EN...
Page 18
Unit Dimensions and Weights Figure 3. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat) NOTES: 1. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION. 90 3/8" 2295.5mm 180 5/16" 4579.9mm SEE NOTE 2 3.25 [82.55mm] TO TOP OF FAN GRILLE 70 7/16"...
Page 20
Unit Dimensions and Weights Figure 7. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat) Figure 8. Duct openings, 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat) 1 1/4 3 1/4 (32) (81)
Page 21
Unit Dimensions and Weights Figure 9. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat) NOTES: 90 5/8" 1. SEE ROOFCURB DRAWING FOR DETAILS 2301.8mm ON FIELD DUCT FITUP AND CONNECTIONS 2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
Unit Dimensions and Weights Figure 11. Location of "Ship With" Items for TC*, TE*, and YC* Units Unit Rigging and Placement WARNING Heavy Objects! Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit.
Page 23
Unit Dimensions and Weights Figure 12. Unit Rigging Table 1. Minimum Operating Clearances Installation (Horizontal and Downflow Configurations) Recommended Clearances Economizer/ Condenser Coil Single Unit Exhaust End Orientation End/Side Service Side Access TC*, TE*, YC* 6 Feet 8 Feet 4 Feet 27.5 to 50 Tons Distance Between Units Economizer/...
Page 24
Unit Dimensions and Weights Figure 13. Center of Gravity Z (see note 2) Table 3. Center of Gravity Center-of-Gravity (inches) YC Low Heat YC High Heat Unit Model Dimension Dimension TC/TE Dimension ***330/275* ***360/305* ***420/350* ***480/400* ***600/500* Note: Center-of-gravity dimensions are approximate, and are based on the unit equipped with: standard efficiency coils, standard efficiency motors, economizer, inlet guide vanes, and throwaway filters Note: Z dimension is upward from the base of the unit.
Page 25
Unit Dimensions and Weights Table 5. Point Loading Average Weight1 — lbs./kg Model **D330/275 **H330/275 **D360/305 **H360/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500 **H600/500 Notes: 1. Point Loading is identified with corner A being the corner with the compressors. As you move clockwise around the unit as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F.
Installation General Requirements Condensate Drain Connection Each commercial rooftop unit is equipped with one (1) 1-1/4 inch Female PVC condensate drain connection. Refer to Figure 11, p. 23 for the location of the connector. A condensate trap must be installed due to the drain connection being on the "negative pressure"...
Installation General Requirements 5. Attach one end of the 50' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing. Units with Statitrac™...
Page 28
Installation General Requirements Figure 16. Statitrac Transducer Assembly Static Reference Tubing Connects Here (O/A Sensor) Space Pressure Sensing Tube Space Pressure Connects Here Transducer Space Pressure Calibration Solenoid Space Pressure Transducer Sensing Tube to Space LO HI Pressure Sensing Tube to Outside Air Reference RT-SVX34C-EN...
Installation Electrical Disconnect Switch External Handle (Factory Mounted Option) Units ordered with the factory mounted disconnect switch come equipped with an externally mounted handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle location and its three positions are shown below; ON - Indicates that the disconnect switch is closed, allowing the main power supply to be applied at the unit.
Installation Electrical Main Power Wiring WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes.
Page 31
Installation Electrical Figure 18. Typical Field Power Wiring RT-SVX34C-EN...
Page 32
Installation Electrical Table 7. 27½-50 Ton Electrical Service Sizing Data—60Hz1 Fan Motors Compressor Supply Condenser Exhaust Allowable Electrical Voltage 100% Model Characteristics Range No/Ton (Ea.) (Ea.) No HP (Ea.) 50% (Ea.) 21.5 1/12,1/ 208/60/3 187-229 44.0/50.5 304/315 10.0 29.0 1/12,1/ 18.8 230/60/3 207-253...
Page 33
Installation Electrical Table 7. 27½-50 Ton Electrical Service Sizing Data—60Hz1 Fan Motors Compressor Supply Condenser Exhaust Allowable Electrical Voltage 100% Model Characteristics Range No/Ton (Ea.) (Ea.) No HP (Ea.) 50% (Ea.) 10.0 29.0 2/13,1/ 208/60/3 187-229 50.5/56.0 315/351 15.0 40.7 20.0 56.1 10.0...
Installation Electrical 1. Calculate the MCA, MOP and/or RDE values using the above equation as if the unit is operating in the cooling mode. 2. Calculate the MCA, MOP and/or RDE values as if the unit is operating in the heating mode, as follows: Note: When determining loads, the compressors and condenser fan motors do not operate during the heating cycle.
Installation Electrical Control Power Transformer WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. The 24 volt control power transformers are equipped with internal circuit breakers.
16 gauge 611-970 feet 14 gauge Units equipped with the Trane Communication Interface (TCI) option, which utilizes a serial communication link; • Must be 18 AWG shielded twisted pair cable Belden 8760 or equivalent). • Must not exceed 5,000 feet maximum for each link.
Page 39
Installation Electrical Figure 19. Typical Field Wiring Requirements for CV Control Options LTB6 Space Humidity Sensor Space Humidistat RT-SVX34C-EN...
Page 40
Installation Electrical Figure 20. Typical Field Wiring Requirements for VAV Control Options LTB6 Customer Changeover for VAV Htg (MOD GAS ONLY *VAV Mode input: RTRM J6-2 to RTRM J6-4 If the unit does not have a Mode (Off, Auto) input from another source, the following default applies: Short from J6-2 to J6-4 = AUTO mode, Open from J6-2 to J6-4 = OFF mode.
Installation Electrical Figure 21. RTRM Zone Sensor/Thermostat Connections (CV ONLY) INPUTS ZSM INPUTS CV/VAV ZSM INPUTS Remote Panels and Sensors Constant Volume Control Options The RTRM must have a zone sensor or conventional thermostat to operate the rooftop unit. If using a zone sensor, mode capability depends upon the type of sensor and/or remote panel selected to interface with the RTRM.
Page 42
Installation Electrical Figure 22. Zone Panel (BAYSENS106*) SINGLE SETPOINT MANUAL CHANGE OVER Zone Panel (BAYSENS108*) This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*.
Installation Electrical Figure 24. Remote Panel W/O NSB (BAYSENS110*) Variable Air Volume Control Options The RTRM must have a mode input in order to operate the rooftop unit. The normal mode selection used with a remote panel with or without night setback, or ICS is AUTO and OFF . Table 9 lists the operating sequence should a CV zone sensor be applied to a VAV system having selectable modes;...
Page 44
Installation Electrical Table 14. Variable Air Volume Mode Operation System Mode Fan "Auto "Fan "On" DWU Active Heat DWU Off VAV Heating Cool VAV Cooling VAV Cooling 1,2,3,4 1,2,3,4 DWU Active DWU or Cooling DWU or Cooling Auto DWU Off VAV Cooling VAV Cooling or Heating Notes:...
Page 45
Figure 27. Remote Zone Sensor (BAYSENS073*) Remote Zone Sensor (BAYSENS074*) This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort building management system. Figure 28. Remote Zone Sensor (BAYSENS074*) Remote Zone Sensor (BAYSENS077*) This electronic sensor can be used with BAYSENS106*, 108*, 110*, 119*, or 021* Remote Panels.
Page 46
Installation Electrical The liquid crystal display (LCD) displays zone temperature, temperature setpoints, week day, time, and operational mode symbols. The options menu is used to enable or disable these applicable functions: Morning warm-up, economizer minimum position override during unoccupied status, heat installed, remote zone temperature sensor, 12/24 hour time display, and daytime warm-up.
Installation Electrical Remote Minimum Position Potentiometer (BAYSTAT023*) This device can be used with units with an economizer. It allows the operator to remotely set the position of the economizer dampers from 0% to 50% of fresh air entering the space. Figure 31.
Page 48
Installation Electrical Figure 32. Space Temperature Averaging To RTRM J6-1 and J6-2 or to ZSM terminals 1 and 2 or NSB panel terminals S1 and S2. Shield to terminal 11. Table 15. Temperature vs. Resistance (temperature vs. resistance coefficient is negative) Nominal Degrees F°...
Page 49
Installation Electrical Table 15. Temperature vs. Resistance (temperature vs. resistance coefficient is negative) Nominal Degrees F° Resistance 50° 19.96 K - Ohms 55° 17.47 K - Ohms 60° 15.33 K - Ohms 65° 13.49 K - Ohms 70° 11.89 K - Ohms 75°...
Installation Piping General Requirements All internal gas piping for YC* rooftop units are factory installed and leak tested. Once the unit is set into place, a gas supply line must be field installed and connected to the gas train located inside the gas heat compartment.
Installation Piping 7. Pressure test the supply line before connecting it to the unit to prevent possible gas valve damage and the unsafe operating conditions that will result. Note: Do not rely on gas train shutoff valves to isolate the unit while conducting gas pressure/ leak test.
Page 52
Installation Piping Table 17. Specific Gravity Multiplier Specific Gravity Multiplier 0.55 1.04 0.65 0.96 Figure 33. Gas Train Configuration for Low Heat Units (high heat units utilize two gas trains.) RT-SVX34C-EN...
Startup Unit Control Modules RTRM - ReliaTel Refrigeration Module The RTRM is the main information receiving module. It interprets the information received from all other unit modules, sensors, remote panels, customer binary contacts and responds by activating the various unit components to satisfy the applicable request for economizing, cooling, heating, exhaust, ventilation.
Page 55
Startup Figure 36. RTVM Module = Space Pressure Deadband (iwc) = Space Pressure Deadband (iwc) 2 = Space Pressure Setpoint (iwc) = Space Pressure Deadband (iwc) 2 = Space Pressure Setpoint (iwc) 2 = Space Pressure Setpoint (iwc) = Space Pressure Deadband (iwc) 2 = Space Pressure Setpoint (iwc) RTVM RTVM...
Page 56
This module is used when the application calls for a BACnet building management type control system. It allows the control and monitoring of the system through a Trane Tracer SC panel or 3rd party BACnet system. The module can be ordered from the factory or ordered as a kit to be field installed.
Startup Important: In order to avoid nuisance trips, the overload setpoint dial must be adjusted to the following calculated value: Overload Setting = (Motor FLA) x 1.12 Overload Setting = (Compressor RLA) x 1.12 Figure 38. Manual Motor Protectors System Operation Economizer Operation with a Conventional Thermostat (CV only) If the ambient conditions are suitable for economizer operation, the economizer is activated as the 1st step of cooling from Y1.
Page 58
Startup 2. Delay between stages timer function. When combined with a standard Zone Sensor Module, the Reliatel Refrigeration Module (RTRM) provides a 10 second minimum “ON” delay for compressor staging. 3. Built in Fan Delay Relay function for Constant Volume Units. When the fan mode switch on the Zone Sensor Module is set in the auto position, the RTRM provides individual supply fan timing sequences for each system in heating and cooling.
Page 59
Startup 1. The zone temperature minus the economizer setpoint, and 2. The zone temperature minus the outdoor air temperature. Note: Table 19 lists the percentages the dampers will open based on these conditions. Table 19. Percent of Damper Travel Zone Temp - Econ Setpoint °F Zone - ODT 0.0 - 0.5 0.5 - 1.0...
Page 60
Startup Figure 39. Compressors Zone Temperature - Occupied Cooling (CV only) When the unit is in the cooling mode and the zone temperature raises above the cooling setpoint controlband, the economizer and the compressor stages will be cycled as required by the zone sensor, remote panel, or Tracer®.
Startup Variable Air Volume Applications Supply Air Temperature Control - Occupied Cooling and Heating The RTRM is designed to maintain a selectable supply air temperature of 40° F to 90° F with a +/- 3.5° F deadband. In cooling, if supply air temperature is more than 3.5 degrees warmer than the selected temperature, a stage of cooling will be turned "On"...
Page 62
Startup Daytime Warm-up (DWU) Control Daytime Warm-up is applicable during occupied status and when the zone temperature is below the initiation temperature. It can be activated or deactivated through ICS or a night setback zone sensor. If ICS or a night setback zone sensor is not utilized, DWU can be activated by setting the DWU enable DIP switch (RTAM) to ON and supplying a valid morning warm-up setpoint.
Startup Supply Air Temperature Reset The supply air temperature can be reset by using one of four DIP switch configurations on the RTAM or through ICS when a valid supply air reset setpoint with a supply air reset amount is given. A selectable reset amount of 0°...
Page 64
Startup Table 21. Economizer Effectiveness Method used to determine econmizer effectiveness Required Comparative Enthalpy OAT, OAH, RAT, RAH Reference Enthalpy OAT, OAH Reference Dry Bulb Unable to determine effectiveness OAT data is invalid or unavailable Two of the three methods for determining the suitability of the outside air can be selected utilizing the potentiometer on the Economizer Actuator, as described below: 1.
Page 65
Startup can be set for a particular application. The clogged filter switch is normally open and will automatically close when the pressure differential across the filters falls below the clogged filter setpoint. The RTOM will generate a SERVICE diagnostic that will be sent to the zone sensor or remote panel when the clogged filter switch has been closed for at least 2 minutes during supply fan operation.
Page 66
Startup Phase Monitor The Phase Monitor is a 3 phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 VAC, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
Page 67
Startup Figure 41. Transducer Voltage Output vs. Pressure Input for Supply, Return and Building Pressure -0.75 to 9.0 Iwc Pressure Transducer Voltage Output vs. Pressure Input 4.50 4.00 3.50 3.00 2.50 2.00 1.50 1.00 0.50 0.00 Pressure (inches w.c.) Power Exhaust Control (Tracking) The power exhaust dampers proportionally track or follow the fresh air (economizer) damper position.
Page 68
Startup Coil Frost Protection The Frostat™ control monitors the suction line temperature to prevent the evaporator from freezing due to low operating temperatures whenever there is a demand for cooling. When a closed circuit has occurred for 5 seconds minimum, the RTRM turns off all of the cooling outputs providing the 3 minute minimum "On"...
Page 69
Startup Table 25. Condenser Fan/Compressor Sequence O/A Temp. Unit Size Compressor Staging Sequence Condenser Fan Output (°F) (Tons) Step 1 Step2 Step 3 Output A Output B Fans "Off" Fan #2 Fan #3, 4 CPR 1 ** Fan #2 Fan #3, 4 CPR 2*** Fan #2 CPR 1, 2...
Startup Preparing the Unit for Operation Use the checklist provided below in conjunction with the "Installation Checklist” to ensure that the unit is properly installed and ready for operation. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
Startup • Turn the "System" selection switch to the "Off" position and the "Fan" selection switch (if Applicable) to the "Auto" position. • Close the disconnect switch or circuit protector switch that provides the supply power to the unit's power terminal block or unit mounted disconnect switch. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary...
Startup The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance at the job site is over 2%, notify the proper agencies to correct the voltage problem to within 2.0% before operating this equipment.
Page 73
Startup at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System"...
Page 74
Startup Table 28. Test Mode States for VAV Units with Modulating Dehumidification TEST Cool Reheat STEP MODE ECON COMP 1 COMP 2 HEAT 1 HEAT 2 Pumpout Valve Valve IGV TEST OPEN OPEN CLOSED 100% IGV TEST CLOSED CLOSED 100% CLOSED MIN VENT 100%...
Startup Verifying Proper Fan Rotation Using the Service Test guide in Table 28, momentarily jump across the test terminals one time for constant volume applications, or three consecutive times for a variable air volume application, to start the Minimum Ventilation Test. WARNING Rotating Components! Disconnect all electric power, including remote disconnects before servicing.
Page 76
Startup 2. To determine the actual CFM (within + 5%), plot the fan's operating RPM and the Theoretical BHP onto the appropriate Fan Performance Curve in Figure 43, p. 78 Figure 44, p. Theoretical BHP Formula: Actual Motor Amps ----------------------------- ------------------------------------------ - Motor HP Theoretical BHP Motor Nameplate Amps...
Page 85
Startup Table 36. TC*/YC* 300 - 600 MBH Economizer (R/A) Damper Pressure Drop — 60 Hz Unit Airflow Pressure Unit Airflow Pressure Unit Airflow Pressure Capacity (Cfm) Drop Capacity (Cfm) Drop Capacity (Cfm) Drop 27.5 8000 0.035 9000 0.042 10000 0.051 8000 0.035...
Page 86
Startup Table 37. Component Static Pressure Drops (in. W.G.)1—60 Hz Heating System Filters2 MERV1 Throw- 4 High Gas Heat Electric Heat3 ID Coil away MERV 8 High Eff. Inlet Nominal Guide Tons Std Air High Element Element 2" 2" 4" 4"...
Page 87
Startup Table 38. Supply Fan Drive Selection — 60Hz 7.5 HP 10 HP 15 HP 20 HP Nominal Drive Drive Drive Drive Tons 750* 27.5T 790** 800* Notes: * For YC gas/electric only. ** For TC and TE Cooling and Electric Heat units only. RT-SVX34C-EN...
Page 88
Startup Table 39. Component Static Pressure Drops in. wg (I-P)—50 Hz Heating System Filters Throw- MERV14 Gas Heat Electric Heat ID Coil away MERV 8 High Eff. High Eff Nominal Inlet Std Tons Guide (kW) Std Air High Element Element 2”...
Page 89
Startup Table 40. Component Static Pressure Drops Pa (SI)—50 Hz Heating System Filters MERV1 Throw- MERV 8 High 4 High Gas Heat Electric Heat ID Coil away Eff. Nominal Inlet Std Tons Guide (kW) Std Air High Element Element Adder 50 mm Vanes Economizer 3150...
Startup Table 41. Supply Air Fan Drive Selections - 50 Hz 7.5 hp (5.6 kW) 10 hp (7.5 kW) 15 hp (10 kW) 20 hp (15 kW) Nominal Tons (kW) Drive No Drive No Drive No Drive No — — —...
Page 91
Startup Verify that the fans are operating properly and the CFM is within the job specifications. Refer to power exhaust fan performance tables beginning with Table 42, p. 92 for the exhaust fan performance characteristics. Available power adjustments: 1. The power exhaust fan(s) comes on based on the position of the of the exhaust fan setpoint potentiometer on the RTOM (Reliatel Options Module).
Startup Figure 49. (Downflow) Standard Exhaust Maximum Damper Position More Exhaust Less Exhaust Figure 50. (Horizontal) Standard Exhaust Maximum Damper Position Less Exhaust More Exhaust Economizer Damper Adjustment Economizer (O/A) Dampers Arbitrarily adjusting the outside air dampers to open fully when the return air dampers are fully closed can overload the supply fan motor or deliver higher CFM to the space than designed.
Page 95
Startup 3. Add the measured return duct static pressure and the return air damper pressure drop together to obtain the Total Return Static Pressure. Apply this calculation and the calculated CFM to the appropriate Table 46, p. 95 through Table 49, p. 4.
Page 96
Startup Table 48. 40 - 50 Ton Downflow Unit Economizer (O/A) Damper Static Pressure Setup Return Air Duct Static + Return Air Damper Static System Design (Inches of Water) 0.20 0.40 0.60 0.80 1.00 1.20 1.40 Drive Rod Position 12000 12500 13000 13500...
Startup Figure 51. Economizer (O/A) damper assembly Manual Fresh Air Damper Units ordered with the 25% manual fresh air option have two slidable dampers. By adjusting one or both, the desired amount of fresh air entering the system can be obtained. To adjust the fresh air damper;...
Startup 6. With the supply fan "On" and rotating in the proper direction, measure the return duct static pressure. 7. Using the Table below, enter the desired amount of fresh air and the return air static pressure reading to obtain the proper damper opening dimension. Table 50.
Startup rotation. Refer to the unit wiring schematic and/or wire color markers vs. the compressor terminal block color markers. Figure 52. Economizer (O/A) damper assembly If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed.
Page 100
Startup Figure 53. Line Weight Locations—50 Ton Figure 54. Line Weight Locations—40 Ton RT-SVX34C-EN...
Startup Compressor Oil Once all of the compressors have been started, verify that the oil level is visible through the sight glass or above the sight glass. Use appropriate lighting (flash light) to verify the presence of oil. A tandem manifold set may have different oil heights, but still must be visible in the sight glass or above the sight glass.
Page 102
Startup Table 52. 30 Ton—Operating Pressure (60 Hz) TC, TE, YC* 36 0 FULL LOAD 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient 3 50 75 F OD Ambient...
Page 103
Startup Table 54. 40 Ton Dual Circuit—Operating Pressure (60 Hz) TC, TE , YC* 4 80 Circuit # 1 Full Load 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient...
Page 104
Startup Table 56. 50 Ton Dual Circuit—Operating Pressures (60 Hz) TC, TE, Y C* 600 Circ uit # 1 FULL LO AD 115 F OD Ambient 105 F OD Ambient 95 F OD Ambient 85 F OD Ambient 75 F OD Ambient 65 F OD Ambient 55 F OD Ambient 11 0...
Page 105
Startup Table 58. 22.9 Ton—Operating Pressure (50 Hz) TC, TE, YC* 27 5 FULL LOAD 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient 3 50 75 F OD Ambient...
Page 106
Startup Table 60. 29.2 Ton—Operating Pressures (50 Hz) TC, TE, YC* 35 0 FULL LOAD 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient 3 50 75 F OD Ambient...
Page 107
Startup Table 62. 33.3 Ton Dual Circuit—Operating Pressure (50 Hz) TC, TE , YC* 4 00 Circuit # 2 Full Load 4 200 3 700 46.1 F OD Ambient 40.6 F OD Ambient 3 200 35.0 F OD Ambient 2 700 29.4 F OD Ambient 23.9 F OD Ambient 2 200...
Startup Table 64. 41.7 Ton Dual Circuit—Operating Pressures (50 Hz) TC, TE , YC* 5 00 Circuit # 2 Full Load 4 200 3 700 46.1 F OD Ambient 40.6 F OD Ambient 3 200 35.0 F OD Ambient 2 700 29.
R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components could result in equipment or components exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
Startup WARNING Hazardous Gases and Flammable Vapors! Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual.
Startup Final Unit Checkout After completing all of the checkout and startup procedures outlined in the previous sections (i.e., operating the unit in each of its modes through all available stages of cooling and heating), perform these final checks before leaving the unit: •...
Sequence of Operation Units without an Economizer For 27.5 to 35 Ton units, when mechanical cooling is required, the RTRM energizes the Compressor Contactor (CC1) coil. When the CC1 contacts close, the Compressor CPR1 and Outdoor Fan Motor (ODM1) will start providing the 3 minute "off" time has elapsed. ODM2 and ODM3 cycles off/on based on the outdoor ambient temperature as measured by the Outdoor Air Sensor (OAS).
Sequence of Operation one stop on each side of each damper. The practical range of blade position control is between 1.5" and 4.0" blade opening. The damper is wide-open at 4.0". The stops on each side of a damper must be in the same position, such that the damper blade connecting member contacts the stops at the same time.
Sequence of Operation applications). The ECA modulates the economizer dampers from minimum position to fully open based on a 1.5° F control point below either the space temperature setpoint for constant volume applications or 1.5° F around the supply air temperature setpoint for variable air volume applications.
Sequence of Operation Ignition Control Module There is a green LED located on the ignition module. Any time the Ignition module is powered, the LED will be on to provide status of the ignition system. • Steady OFF - no power/ internal failure •...
Sequence of Operation Low Pressure Control (LPC) Sequence of Operation (ReliaTel Control) When the LPC is opened for one (1) continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of three (3) minutes. If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communicated to ICSTM if applicable, and a manual reset will be required to restart the compressor.
Maintenance Fan Belt Adjustment The Supply Fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. When installing new belts, do not stretch them over the sheaves;...
Page 119
Maintenance Table 65. Supply Fan Sheave and Belt Table (a)(b)(c) )(d) )(e) Fan Sheave Fan Bushing Motor Sheave Motor Bushing Tons Motor RPM Browning Browning Browning Browning Belt BX108 BK190 X 1 7/16 BK190-1-7/16 BK62H BK62H H 1-3/8 H-1-3/8 Notched BX100 BK160 X 1 7/16 BK160-1-7/16 BK57H...
Maintenance Monthly Maintenance WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
Page 121
Maintenance Table 67. Deflection Force Deflection Force (Lbs.) Belts Super Gripbelts Gripnotch Steel Cable Gripbelts Cross Small P.D Section Range Min. Max. Min. Max. Min. Max. 3.0 -3.6 4 1/2 3 7/8 5 1/2 3 1/4 3.8 - 4.8 3 1/2 4 1/2 6 1/4 3 3/4...
Maintenance • compressor suction and discharge pressures (each circuit); • superheat and subcooling (each circuit); Record this data on an “operator’s maintenance log” like the one shown in Table 31. If operating pressures indicate a refrigerant shortage, measure the system superheat and system subcooling. For guidelines, refer to "Charging by Subcooling".
Be sure to follow these instructions as closely as possible to avoid damaging the coils. To clean refrigerant coils, use a soft brush and a sprayer. Contact the local Trane Parts Center for appropriate detergents.
Maintenance 4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability. 5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used: a.
R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components could result in equipment or components exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
Maintenance If a motor burn out has occurred, change the oil in both compressors in a tandem set. This will require that the oil equalizer tube be removed to suck the oil out of the oil sump. A catch pan must be used to catch the oil when the compressor oil equalizer line is loosened.
Diagnostics The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information. Before turning the main power disconnect switch "Off", follow the steps below to check the Unit Control. All diagnostics and system status information stored in the RTRM will be lost when the main power is turned "Off".
Diagnostics Terminal locations System Status / Diagnostics checkout procedure (DC volt meter required) The method described below to determine unit status or to see if diagnostics are present assumes the Zone Sensor or NSB panel is not within sight or close by or is not being used. If a zone sensor is within sight however, DC readings need not be taken - just look at the LED or display and go to STEP 3.
Diagnostics (see DIAGNOSTICS section). Note: Diagnostics for CV or VAV units are listed separately. The same diagnostic may have a different meaning depending on whether the unit has VAV controls or CV controls. Diagnostics (CV units only) If only one diagnostic is present, refer to that diagnostic listing below. If more than one diagnostic is present, refer to combination diagnostics such as COOL + HEAT as appropriate.
Diagnostics Diagnostics (VAV only) If only one diagnostic is present, refer to that diagnostic. If more than one diagnostic is present, refer to combination diagnostics such as COOL + HEAT as appropriate. On a BAYSENS119*, the display will show HEAT FAIL or COOL FAIL or SERVICE (or an appropriate combination) if a diagnostic is present.
Diagnostics Method 1 To reset the system from the space, turn the "Mode" selection switch at the zone sensor to the "Off" position. After approximately 30 seconds, turn the "Mode" selection switch to the desired mode, i.e. Heat, Cool or Auto. Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch "Off"...
Diagnostics Test 1 Zone Temperature Thermistor (ZTEMP) This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. The following are some typical indoor temperatures, and corresponding resistive values. Table 73. Resistance Values Zone or Set Nominal ZTEMP Nominal CSP or HSP...
Diagnostics Test 4 LED indicator test, (SYS ON, HEAT, COOL & SERVICE). Method 1 Testing the LED using a meter with diode test function. Test both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an Over Load, or open circuit indication if LED is functional.
Page 135
Diagnostics Table 75. Constant Volume Defaults Component or Function Default Operation Cooling Setpoint (CSP) 74° F Heating Setpoint (HSP) Economizer 71° F Normal Operation Economizer Minimum Position Normal Operation Mode Normal operation, or auto if ZSM mode switch has failed Normal operation, or continuous if fan mode switch on ZSM has failed Night Setback Mode Disabled - Used with Integrated Comfort™...
Diagnostics 6 Flashes: OA Humidity Sensor out of range 7 Flashes: OA Temp Sensor out of range 8 Flashes: MA Temp Sensor out of range 9-11 Flashes: Internal ECA failure Note: The Outdoor Air Sensor (OAS) is also used for the economizer operation. It is connected to the RTRM.
Diagnostics Note: If voltage is incorrect, verify RTAM DIP switch settings. 2. If the voltage to the IGV/VFD is not present, verify that the wires are properly connected between the RTRM or COMM (Communications Module) and the RTAM. If Step 2 checks out and the voltage is still not present at the IGV/VFD output, replace the RTAM. Test 2 Testing the Static Pressure Transducer (SPT) Input 1.
Diagnostics Test 5 Testing the VFD 1. Verify that the keypad in control box is powered. If not, check the power wires to the VFD and the Keypad cable. 2. Using the "Step Test Mode", procedure described in the "Unit Startup" section (Step 3 for VAV). Verify that the fan starts and the speed increases until the SA Pressure reaches the "Setpoint"...
Page 139
Diagnostics Table 77. Troubleshooting SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. No power to the Unit. 1. Check line voltage at service disconnect. 2. No power to the RTRM. 2. Check for 24 VAC at RTRM J1-1 to system ground. 3. Zone Sensor Module (ZSM) is 3.
Page 140
Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. No power to CC1 coil. Possible 1. Check wiring, terminals and applicable controls Cool Failure (CCB1, HPC1, TDL1, WTL1, LPC1) 2. CC1 coil defective. Cool Failure 2. Check CC1 coil. If open or shorted, replace CC1. Indicated.
Page 141
Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. CFM has failed. 1. Check CFM, replace if necessary. 2. Disconnect BROWN wires from capacitor, test, and 2. CFM capacitor has failed. replace if necessary. 3. Check wiring, and terminals. Repair, or replace if J.
Page 142
Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. Check for 24 VAC at AH, BH,CH, and DH contactor 1. Heater contactor(s) have coils. If 24 VAC is present on a call for heat, and the failed. contacts do not close, the contactor has failed. 2.
Page 143
Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. Check the return air sensor (RAS) at connector P10 by disconnecting P10 from RAT on the ECA. Check for resistance between P10-1 and P10-2, refer to the 1. Comparative enthalpy setup, Resistance versus Temperature Chart.
Page 144
Diagnostics Table 78. Component Failure Mode COMPONENT FAILURE RESPONSE NORMAL RANGE DIAGNOSTIC 4 to 20 mA Check at ECA ECA 3 flashes. (RHS) Return Humidity 1. Economizer operates using 10 to 90% RH Honeywell RAH-1 and RAH-2 by Sensor Referance Enthalpy. C7600A.
Page 145
Diagnostics Table 78. Component Failure Mode COMPONENT FAILURE RESPONSE NORMAL RANGE DIAGNOSTIC This input is for "indication only "Normal operation = 0 VAC SERVICE LED ON 2-30 VDC (CFS) Clogged Filter and does not effect the normal measured between terminals present at RTRM J6-6 and J6- Switch operation of the unit.
] buttons. When the desired selection has been made, press the OK button. Should replacing the a VFD become necessary, the replacement is not configured with all of Trane's operating parameters. The VFD must be programmed before attempting to operate the unit.
Page 147
Diagnostics g. Press [OK] ►◄ h. To move to a different digit within a parameter setting, use the [ ] buttons (Highlighted area indicates digit selected for change) ▲ ▼ i. Use [ ] and [ ] buttons to adjust the digit j.
Unit Wiring Diagram Numbers Table 81. Unit Wiring Diagram Numbers Diagram No. Descriptions 2313-0601 Power Schematic (208V-575V) 2313-0700 Heat Power and Controls Schematic - Low Heat Gas Unit 2313-0701 Heat Power and Controls Schematic - High Heat Gas Unit 2313-0605 Heat Power and Controls Schematic - Low Heat Modulating Gas Unit 2313-0702 Heat Power and Controls Schematic - High Heat Modulating Gas Unit...
Page 149
Unit Wiring Diagram Numbers Table 81. Unit Wiring Diagram Numbers Diagram No. Descriptions 2313-0654 Control Box Connection Print - 27.5-35T, VAV, 36KW-54KW Electric Heat 208-230V 2313-0655 Control Box Connection Print - 27.5-35T, VAV, 36KW-54KW Electric Heat 380-575V 2313-0656 Control Box Connection Print - 40T, VAV, 54KW Electric Heat 208-230V 2313-0657 Control Box Connection Print - 40T, VAV, 54KW Electric Heat 380-575V 2313-0658...
COMMERCIAL EQUIPMENT RATED 20 TONS AND LARGER AND RELATED ACCESSORIES PRODUCTS COVERED - This warranty* is extended by Trane Inc. and applies only to commercial equipment rated 20 Tons and larger and related accessories. The Company warrants for a period of 12 months from initial startup or 18 months from date of...