Trane Voyager Commercial Installation & Operation Manual
Trane Voyager Commercial Installation & Operation Manual

Trane Voyager Commercial Installation & Operation Manual

Commercial 27.5 to 50 ton 60 hz, 22.9 to 41.7 ton 50 hz cv or vav rooftop air conditioners with reliatel controls, r-410a refrigerant
Hide thumbs Also See for Voyager Commercial:
Table of Contents

Advertisement

Installation, Operation,
Maintenance
Voyager™ Commercial
27.5 to 50 Ton 60 Hz
22.9 to 41.7 Ton 50 Hz
CV or VAV Rooftop Air Conditioners
with ReliaTel™ Controls, R-410A Refrigerant
Model Numbers
"B" and later design sequence
TC*, TE*, YC*330B, 360B, 420B, 480B, 600B (60 Hz/3 phase)
TC*, TE*, YC*275B, 305B, 350B, 400B, 500B (50 Hz/3 phase)
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
November 2010
RT-SVX34C-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane Voyager Commercial

  • Page 1 Installation, Operation, Maintenance Voyager™ Commercial 27.5 to 50 Ton 60 Hz 22.9 to 41.7 Ton 50 Hz CV or VAV Rooftop Air Conditioners with ReliaTel™ Controls, R-410A Refrigerant Model Numbers “B” and later design sequence TC*, TE*, YC*330B, 360B, 420B, 480B, 600B (60 Hz/3 phase) TC*, TE*, YC*275B, 305B, 350B, 400B, 500B (50 Hz/3 phase) SAFETY WARNING Only qualified personnel should install and service the equipment.
  • Page 2: Literature Change History

    CFCs such as HCFCs and HFCs. Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures.
  • Page 3: Overview Of Manual

    Warnings, Cautions and Notices Overview of Manual One copy of the appropriate service literature ships inside the control panel of each unit. The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians. Note: Do not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws.
  • Page 4: Table Of Contents

    Table of Contents Literature Change History ......... . . 2 Overview of Manual .
  • Page 5 Constant Volume Control Options ....... 41 Variable Air Volume Control Options ......43 Installation Piping .
  • Page 6 Gas Heat Sequence Of Operation ........115 Electric Heat Sequence Of Operation .
  • Page 7 TR-1 and TR-200 VFD Programming Parameters ....146 Unit Wiring Diagram Numbers ......... 148 Warranty and Liability Clause .
  • Page 8: 60 Hz Description

    No Heat (TC only) Low Heat (YC only) Digit 14 — Supply Air Fan Drive Digit 22 High Heat (YC only) Selections Trane Communication Low Heat-Stainless Steel Gas Interface (TCI) 550 RPM 500 RPM Heat Exchanger (YC only) High Heat-Stainless Steel Gas...
  • Page 9 Model Number Descriptions Discharge Temperature Sensor Clogged Filter Switch Digit 32 — Dehumidification Option Modulating Hot Gas Reheat Model Number Notes All voltages are across the line starting only. 2. Option includes Liquid, Discharge, Suction Valves. 3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 &...
  • Page 10: 50 Hz Description

    Model Number Descriptions 50 Hz Description Throwaway Filters Trane Communication 4” (102 MM) MERV 14, High Eff, Interface (TCI) Throwaway Filters Digit 23 Digits 1, 2 – Unit Function Digit 13 – Supply Fan Motor, HP Ventilation Override TC = DX Cooling, No Heat 7.5 Hp (5.6 kW)
  • Page 11: General Information

    General Information Commonly Used Acronyms/Abbreviations Building Automation System Cubic Feet per Minute Cooling Valve (Reheat only) COMM Module Designation for TCI/LCI Constant Volume Clockwise Counterclockwise Direct Space Pressure control Discharge Air Sensor Daytime Warm-up Exhaust Air Economizer Actuator Entering Evaporator Temperature Sensor Fresh Air Fan Failure Switch Integrated Comfort System (See BAS)
  • Page 12: About The Unit

    ReliaTel Options Module RTRM ReliaTel Refrigeration Module Supply Air Space Pressure Calibration Solenoid Space Pressure Transducer Static Pressure Transducer Trane Communication Interface Temperature Cutout Temperature Discharge Limit Variable Air Volume Variable Frequency Drive Ventilation Heat Relay (VAV box relay) W.C.
  • Page 13: First Aid Measures

    Skin Contact - Wash affected areas gently with soap and warm water after handling. An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
  • Page 14: Pre-Installation

    Downflow Models Only: • An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide. •...
  • Page 15: Field Installed Control Wiring

    Pre-Installation Field Installed Control Wiring (Figure 19, p. 41 Figure 20, p. 42.) Important: All field-installed wiring must comply with NEC and applicable local codes. • Complete the field wiring connections for the constant volume controls as applicable. Refer to “Low Voltage Wiring”...
  • Page 16: Unit Dimensions And Weights

    These clearances are necessary to assure adequate serviceability, cataloged capacities, and peak operating efficiency. If the clearances available on the job site appear to be inadequate, review them with your Trane sales representative.
  • Page 17 Unit Dimensions and Weights Figure 1. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat) Figure 2. Rear view showing duct openings for horizontal units 1 1/4 3 1/4 (32) (81) RT-SVX34C-EN...
  • Page 18 Unit Dimensions and Weights Figure 3. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat) NOTES: 1. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION. 90 3/8" 2295.5mm 180 5/16" 4579.9mm SEE NOTE 2 3.25 [82.55mm] TO TOP OF FAN GRILLE 70 7/16"...
  • Page 19 Unit Dimensions and Weights Figure 5. Duct openings, 60 Hz 27½-35, 50 Hz 23-29 Tons (YC High Heat) 1 1/4 3 1/4 (32) (81) Figure 6. 60 Hz 27½-35, 50 Hz 23-29 Tons (YC High Heat) 90 5/8" NOTES: 2301.8mm 1.
  • Page 20 Unit Dimensions and Weights Figure 7. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat) Figure 8. Duct openings, 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat) 1 1/4 3 1/4 (32) (81)
  • Page 21 Unit Dimensions and Weights Figure 9. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat) NOTES: 90 5/8" 1. SEE ROOFCURB DRAWING FOR DETAILS 2301.8mm ON FIELD DUCT FITUP AND CONNECTIONS 2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
  • Page 22: Unit Rigging And Placement

    Unit Dimensions and Weights Figure 11. Location of "Ship With" Items for TC*, TE*, and YC* Units Unit Rigging and Placement WARNING Heavy Objects! Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit.
  • Page 23 Unit Dimensions and Weights Figure 12. Unit Rigging Table 1. Minimum Operating Clearances Installation (Horizontal and Downflow Configurations) Recommended Clearances Economizer/ Condenser Coil Single Unit Exhaust End Orientation End/Side Service Side Access TC*, TE*, YC* 6 Feet 8 Feet 4 Feet 27.5 to 50 Tons Distance Between Units Economizer/...
  • Page 24 Unit Dimensions and Weights Figure 13. Center of Gravity Z (see note 2) Table 3. Center of Gravity Center-of-Gravity (inches) YC Low Heat YC High Heat Unit Model Dimension Dimension TC/TE Dimension ***330/275* ***360/305* ***420/350* ***480/400* ***600/500* Note: Center-of-gravity dimensions are approximate, and are based on the unit equipped with: standard efficiency coils, standard efficiency motors, economizer, inlet guide vanes, and throwaway filters Note: Z dimension is upward from the base of the unit.
  • Page 25 Unit Dimensions and Weights Table 5. Point Loading Average Weight1 — lbs./kg Model **D330/275 **H330/275 **D360/305 **H360/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500 **H600/500 Notes: 1. Point Loading is identified with corner A being the corner with the compressors. As you move clockwise around the unit as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F.
  • Page 26: Installation General Requirements

    Installation General Requirements Condensate Drain Connection Each commercial rooftop unit is equipped with one (1) 1-1/4 inch Female PVC condensate drain connection. Refer to Figure 11, p. 23 for the location of the connector. A condensate trap must be installed due to the drain connection being on the "negative pressure"...
  • Page 27: Units With Statitrac

    Installation General Requirements 5. Attach one end of the 50' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing. Units with Statitrac™...
  • Page 28 Installation General Requirements Figure 16. Statitrac Transducer Assembly Static Reference Tubing Connects Here (O/A Sensor) Space Pressure Sensing Tube Space Pressure Connects Here Transducer Space Pressure Calibration Solenoid Space Pressure Transducer Sensing Tube to Space LO HI Pressure Sensing Tube to Outside Air Reference RT-SVX34C-EN...
  • Page 29: Installation Electrical

    Installation Electrical Disconnect Switch External Handle (Factory Mounted Option) Units ordered with the factory mounted disconnect switch come equipped with an externally mounted handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle location and its three positions are shown below; ON - Indicates that the disconnect switch is closed, allowing the main power supply to be applied at the unit.
  • Page 30: Main Power Wiring

    Installation Electrical Main Power Wiring WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes.
  • Page 31 Installation Electrical Figure 18. Typical Field Power Wiring RT-SVX34C-EN...
  • Page 32 Installation Electrical Table 7. 27½-50 Ton Electrical Service Sizing Data—60Hz1 Fan Motors Compressor Supply Condenser Exhaust Allowable Electrical Voltage 100% Model Characteristics Range No/Ton (Ea.) (Ea.) No HP (Ea.) 50% (Ea.) 21.5 1/12,1/ 208/60/3 187-229 44.0/50.5 304/315 10.0 29.0 1/12,1/ 18.8 230/60/3 207-253...
  • Page 33 Installation Electrical Table 7. 27½-50 Ton Electrical Service Sizing Data—60Hz1 Fan Motors Compressor Supply Condenser Exhaust Allowable Electrical Voltage 100% Model Characteristics Range No/Ton (Ea.) (Ea.) No HP (Ea.) 50% (Ea.) 10.0 29.0 2/13,1/ 208/60/3 187-229 50.5/56.0 315/351 15.0 40.7 20.0 56.1 10.0...
  • Page 34 Installation Electrical Table 9. Electrical Service Sizing Data—50Hz Fan Motors Compressor Supply Condenser Exhaust 100% Electrical Characteristic Model No/Ton (Ea.) (Ea.) HP(kW) FLA No. HP(kW) (Ea.) (kW) (Ea.) 13.6/ TC/TE/YC*275 380-415/50/3 1/10, 1/11 21.0/23.0 147/ 158 7.5 (5.6) .75 (.56) 14.1 (.56) 16.0/...
  • Page 35: Electrical Wire Sizing And Protection Device Equations

    Installation Electrical Table 11. Electrical Service Sizing Data — Electric Heat Module (Electric Heat Only) Models: TED/TEH 330—600 Electric Heat FLA KW Heater Nominal Nominal Unit Size Unit (Tons) Voltage 74.9 112.4 — — — 86.6 129.9 — — — 27½-35 43.3 65.0...
  • Page 36: Low Voltage Wiring

    Installation Electrical 1. Calculate the MCA, MOP and/or RDE values using the above equation as if the unit is operating in the cooling mode. 2. Calculate the MCA, MOP and/or RDE values as if the unit is operating in the heating mode, as follows: Note: When determining loads, the compressors and condenser fan motors do not operate during the heating cycle.
  • Page 37: Control Power Transformer

    Installation Electrical Control Power Transformer WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. The 24 volt control power transformers are equipped with internal circuit breakers.
  • Page 38: Field Installed Dc Control Wiring

    16 gauge 611-970 feet 14 gauge Units equipped with the Trane Communication Interface (TCI) option, which utilizes a serial communication link; • Must be 18 AWG shielded twisted pair cable Belden 8760 or equivalent). • Must not exceed 5,000 feet maximum for each link.
  • Page 39 Installation Electrical Figure 19. Typical Field Wiring Requirements for CV Control Options LTB6 Space Humidity Sensor Space Humidistat RT-SVX34C-EN...
  • Page 40 Installation Electrical Figure 20. Typical Field Wiring Requirements for VAV Control Options LTB6 Customer Changeover for VAV Htg (MOD GAS ONLY *VAV Mode input: RTRM J6-2 to RTRM J6-4 If the unit does not have a Mode (Off, Auto) input from another source, the following default applies: Short from J6-2 to J6-4 = AUTO mode, Open from J6-2 to J6-4 = OFF mode.
  • Page 41: Remote Panels And Sensors

    Installation Electrical Figure 21. RTRM Zone Sensor/Thermostat Connections (CV ONLY) INPUTS ZSM INPUTS CV/VAV ZSM INPUTS Remote Panels and Sensors Constant Volume Control Options The RTRM must have a zone sensor or conventional thermostat to operate the rooftop unit. If using a zone sensor, mode capability depends upon the type of sensor and/or remote panel selected to interface with the RTRM.
  • Page 42 Installation Electrical Figure 22. Zone Panel (BAYSENS106*) SINGLE SETPOINT MANUAL CHANGE OVER Zone Panel (BAYSENS108*) This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*.
  • Page 43: Variable Air Volume Control Options

    Installation Electrical Figure 24. Remote Panel W/O NSB (BAYSENS110*) Variable Air Volume Control Options The RTRM must have a mode input in order to operate the rooftop unit. The normal mode selection used with a remote panel with or without night setback, or ICS is AUTO and OFF . Table 9 lists the operating sequence should a CV zone sensor be applied to a VAV system having selectable modes;...
  • Page 44 Installation Electrical Table 14. Variable Air Volume Mode Operation System Mode Fan "Auto "Fan "On" DWU Active Heat DWU Off VAV Heating Cool VAV Cooling VAV Cooling 1,2,3,4 1,2,3,4 DWU Active DWU or Cooling DWU or Cooling Auto DWU Off VAV Cooling VAV Cooling or Heating Notes:...
  • Page 45 Figure 27. Remote Zone Sensor (BAYSENS073*) Remote Zone Sensor (BAYSENS074*) This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort building management system. Figure 28. Remote Zone Sensor (BAYSENS074*) Remote Zone Sensor (BAYSENS077*) This electronic sensor can be used with BAYSENS106*, 108*, 110*, 119*, or 021* Remote Panels.
  • Page 46 Installation Electrical The liquid crystal display (LCD) displays zone temperature, temperature setpoints, week day, time, and operational mode symbols. The options menu is used to enable or disable these applicable functions: Morning warm-up, economizer minimum position override during unoccupied status, heat installed, remote zone temperature sensor, 12/24 hour time display, and daytime warm-up.
  • Page 47: Remote Minimum Position Potentiometer

    Installation Electrical Remote Minimum Position Potentiometer (BAYSTAT023*) This device can be used with units with an economizer. It allows the operator to remotely set the position of the economizer dampers from 0% to 50% of fresh air entering the space. Figure 31.
  • Page 48 Installation Electrical Figure 32. Space Temperature Averaging To RTRM J6-1 and J6-2 or to ZSM terminals 1 and 2 or NSB panel terminals S1 and S2. Shield to terminal 11. Table 15. Temperature vs. Resistance (temperature vs. resistance coefficient is negative) Nominal Degrees F°...
  • Page 49 Installation Electrical Table 15. Temperature vs. Resistance (temperature vs. resistance coefficient is negative) Nominal Degrees F° Resistance 50° 19.96 K - Ohms 55° 17.47 K - Ohms 60° 15.33 K - Ohms 65° 13.49 K - Ohms 70° 11.89 K - Ohms 75°...
  • Page 50: Installation Piping

    Installation Piping General Requirements All internal gas piping for YC* rooftop units are factory installed and leak tested. Once the unit is set into place, a gas supply line must be field installed and connected to the gas train located inside the gas heat compartment.
  • Page 51: Connecting The Gas Supply Line To The Furnace Gas Train

    Installation Piping 7. Pressure test the supply line before connecting it to the unit to prevent possible gas valve damage and the unsafe operating conditions that will result. Note: Do not rely on gas train shutoff valves to isolate the unit while conducting gas pressure/ leak test.
  • Page 52 Installation Piping Table 17. Specific Gravity Multiplier Specific Gravity Multiplier 0.55 1.04 0.65 0.96 Figure 33. Gas Train Configuration for Low Heat Units (high heat units utilize two gas trains.) RT-SVX34C-EN...
  • Page 53: Startup

    Startup Unit Control Modules RTRM - ReliaTel Refrigeration Module The RTRM is the main information receiving module. It interprets the information received from all other unit modules, sensors, remote panels, customer binary contacts and responds by activating the various unit components to satisfy the applicable request for economizing, cooling, heating, exhaust, ventilation.
  • Page 54 Startup Figure 34. RTAM Module = Supply Air Heating Setpoint 2 = Static Pressure Setpoint (iwc) 3 = Static Pressure Deadband (iwc) 4 = Reset Setpoint 5 = Reset Amount 6 = Morning W armup Setpoint 7 = Supply Air Cooling Setpoint RTAM Figure 35.
  • Page 55 Startup Figure 36. RTVM Module = Space Pressure Deadband (iwc) = Space Pressure Deadband (iwc) 2 = Space Pressure Setpoint (iwc) = Space Pressure Deadband (iwc) 2 = Space Pressure Setpoint (iwc) 2 = Space Pressure Setpoint (iwc) = Space Pressure Deadband (iwc) 2 = Space Pressure Setpoint (iwc) RTVM RTVM...
  • Page 56 This module is used when the application calls for a BACnet building management type control system. It allows the control and monitoring of the system through a Trane Tracer SC panel or 3rd party BACnet system. The module can be ordered from the factory or ordered as a kit to be field installed.
  • Page 57: System Operation

    Startup Important: In order to avoid nuisance trips, the overload setpoint dial must be adjusted to the following calculated value: Overload Setting = (Motor FLA) x 1.12 Overload Setting = (Compressor RLA) x 1.12 Figure 38. Manual Motor Protectors System Operation Economizer Operation with a Conventional Thermostat (CV only) If the ambient conditions are suitable for economizer operation, the economizer is activated as the 1st step of cooling from Y1.
  • Page 58 Startup 2. Delay between stages timer function. When combined with a standard Zone Sensor Module, the Reliatel Refrigeration Module (RTRM) provides a 10 second minimum “ON” delay for compressor staging. 3. Built in Fan Delay Relay function for Constant Volume Units. When the fan mode switch on the Zone Sensor Module is set in the auto position, the RTRM provides individual supply fan timing sequences for each system in heating and cooling.
  • Page 59 Startup 1. The zone temperature minus the economizer setpoint, and 2. The zone temperature minus the outdoor air temperature. Note: Table 19 lists the percentages the dampers will open based on these conditions. Table 19. Percent of Damper Travel Zone Temp - Econ Setpoint °F Zone - ODT 0.0 - 0.5 0.5 - 1.0...
  • Page 60 Startup Figure 39. Compressors Zone Temperature - Occupied Cooling (CV only) When the unit is in the cooling mode and the zone temperature raises above the cooling setpoint controlband, the economizer and the compressor stages will be cycled as required by the zone sensor, remote panel, or Tracer®.
  • Page 61: Variable Air Volume Applications

    Startup Variable Air Volume Applications Supply Air Temperature Control - Occupied Cooling and Heating The RTRM is designed to maintain a selectable supply air temperature of 40° F to 90° F with a +/- 3.5° F deadband. In cooling, if supply air temperature is more than 3.5 degrees warmer than the selected temperature, a stage of cooling will be turned "On"...
  • Page 62 Startup Daytime Warm-up (DWU) Control Daytime Warm-up is applicable during occupied status and when the zone temperature is below the initiation temperature. It can be activated or deactivated through ICS or a night setback zone sensor. If ICS or a night setback zone sensor is not utilized, DWU can be activated by setting the DWU enable DIP switch (RTAM) to ON and supplying a valid morning warm-up setpoint.
  • Page 63: Constant Volume Or Variable Air Volume Applications

    Startup Supply Air Temperature Reset The supply air temperature can be reset by using one of four DIP switch configurations on the RTAM or through ICS when a valid supply air reset setpoint with a supply air reset amount is given. A selectable reset amount of 0°...
  • Page 64 Startup Table 21. Economizer Effectiveness Method used to determine econmizer effectiveness Required Comparative Enthalpy OAT, OAH, RAT, RAH Reference Enthalpy OAT, OAH Reference Dry Bulb Unable to determine effectiveness OAT data is invalid or unavailable Two of the three methods for determining the suitability of the outside air can be selected utilizing the potentiometer on the Economizer Actuator, as described below: 1.
  • Page 65 Startup can be set for a particular application. The clogged filter switch is normally open and will automatically close when the pressure differential across the filters falls below the clogged filter setpoint. The RTOM will generate a SERVICE diagnostic that will be sent to the zone sensor or remote panel when the clogged filter switch has been closed for at least 2 minutes during supply fan operation.
  • Page 66 Startup Phase Monitor The Phase Monitor is a 3 phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 VAC, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
  • Page 67 Startup Figure 41. Transducer Voltage Output vs. Pressure Input for Supply, Return and Building Pressure -0.75 to 9.0 Iwc Pressure Transducer Voltage Output vs. Pressure Input 4.50 4.00 3.50 3.00 2.50 2.00 1.50 1.00 0.50 0.00 Pressure (inches w.c.) Power Exhaust Control (Tracking) The power exhaust dampers proportionally track or follow the fresh air (economizer) damper position.
  • Page 68 Startup Coil Frost Protection The Frostat™ control monitors the suction line temperature to prevent the evaporator from freezing due to low operating temperatures whenever there is a demand for cooling. When a closed circuit has occurred for 5 seconds minimum, the RTRM turns off all of the cooling outputs providing the 3 minute minimum "On"...
  • Page 69 Startup Table 25. Condenser Fan/Compressor Sequence O/A Temp. Unit Size Compressor Staging Sequence Condenser Fan Output (°F) (Tons) Step 1 Step2 Step 3 Output A Output B Fans "Off" Fan #2 Fan #3, 4 CPR 1 ** Fan #2 Fan #3, 4 CPR 2*** Fan #2 CPR 1, 2...
  • Page 70: Preparing The Unit For Operation

    Startup Preparing the Unit for Operation Use the checklist provided below in conjunction with the "Installation Checklist” to ensure that the unit is properly installed and ready for operation. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
  • Page 71: Voltage Supply And Voltage Imbalance

    Startup • Turn the "System" selection switch to the "Off" position and the "Fan" selection switch (if Applicable) to the "Auto" position. • Close the disconnect switch or circuit protector switch that provides the supply power to the unit's power terminal block or unit mounted disconnect switch. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary...
  • Page 72: Starting The Unit

    Startup The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance at the job site is over 2%, notify the proper agencies to correct the voltage problem to within 2.0% before operating this equipment.
  • Page 73 Startup at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System"...
  • Page 74 Startup Table 28. Test Mode States for VAV Units with Modulating Dehumidification TEST Cool Reheat STEP MODE ECON COMP 1 COMP 2 HEAT 1 HEAT 2 Pumpout Valve Valve IGV TEST OPEN OPEN CLOSED 100% IGV TEST CLOSED CLOSED 100% CLOSED MIN VENT 100%...
  • Page 75: Verifying Proper Fan Rotation

    Startup Verifying Proper Fan Rotation Using the Service Test guide in Table 28, momentarily jump across the test terminals one time for constant volume applications, or three consecutive times for a variable air volume application, to start the Minimum Ventilation Test. WARNING Rotating Components! Disconnect all electric power, including remote disconnects before servicing.
  • Page 76 Startup 2. To determine the actual CFM (within + 5%), plot the fan's operating RPM and the Theoretical BHP onto the appropriate Fan Performance Curve in Figure 43, p. 78 Figure 44, p. Theoretical BHP Formula: Actual Motor Amps ----------------------------- ------------------------------------------ - Motor HP Theoretical BHP Motor Nameplate Amps...
  • Page 77 Startup Table 31. Supply Fan Performance—40 and 50 Ton—60 Hz Total Static Pressure (in. wg)1 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 CFM Std. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM 12000 2.29 2.86...
  • Page 78 Startup Figure 43. Supply Fan Performance Curves 27.5 - 35 Ton—60Hz Supply Fan Performance 27-35T 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 Volumetric Airflow Rate(CFM) Figure 44. Supply Fan Performance Curves 40 and 50 Ton—60Hz Supply Fan Performance 40 and 50 Ton 2000 4000...
  • Page 79 Startup — Table 32. Supply Fan Performance 22.9-29.1 Ton (I-P)—50 Hz Static Pressure (in. wg) 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 6670 283 0.80 351 1.18...
  • Page 80 Startup Figure 45. Supply Fan Performance—22.9-29.2 Tons—50Hz Supply Fan Performance (996) (872) (747) (623) (498) (374) (249) (125) (0.0) 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 Volumetric Airflow Rate(CFM) (.94) (1.89) (2.83) (3.78) (4.72) (5.66) (6.61) (7.55)
  • Page 81 Startup — Table 33. Supply Fan Performance 82-105 kW (SI)—50 Hz Static Pressure (Pascals) 62.9 124.1 186.2 248.3 310.4 372.5 434.6 496.7 558.8 (L/s) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) 3148 0.59 0.88...
  • Page 82 Startup — Table 34. Supply Fan Performance 33.3 and 41.7 Tons (I-P)—50 Hz Static Pressure (in. wg) 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 9996 1.46 1.95 2.49 3.04 3.64 4.25 4.92 5.59 6.23 10829 1.78 2.30 2.87 3.44 4.06 4.71...
  • Page 83 Startup Figure 46. Supply Fan Performance—33.3 and 41.7 Ton (IP)—50Hz Supply Fan Performance 40 and 50 Ton (1245) (996) (747) (498) (249) (0.0) 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 Volumetric Airflow Rate(CFM) (.94) (1.89) (2.83)
  • Page 84 Startup — Table 35. Supply Fan Performance 105-148 kW (SI)—50 Hz Static Pressure (Pascals) 62.1 124.2 186.3 248.1 310.4 372.5 434.6 496.7 558.8 (L/s) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) 4717 1.09 1.46...
  • Page 85 Startup Table 36. TC*/YC* 300 - 600 MBH Economizer (R/A) Damper Pressure Drop — 60 Hz Unit Airflow Pressure Unit Airflow Pressure Unit Airflow Pressure Capacity (Cfm) Drop Capacity (Cfm) Drop Capacity (Cfm) Drop 27.5 8000 0.035 9000 0.042 10000 0.051 8000 0.035...
  • Page 86 Startup Table 37. Component Static Pressure Drops (in. W.G.)1—60 Hz Heating System Filters2 MERV1 Throw- 4 High Gas Heat Electric Heat3 ID Coil away MERV 8 High Eff. Inlet Nominal Guide Tons Std Air High Element Element 2" 2" 4" 4"...
  • Page 87 Startup Table 38. Supply Fan Drive Selection — 60Hz 7.5 HP 10 HP 15 HP 20 HP Nominal Drive Drive Drive Drive Tons 750* 27.5T 790** 800* Notes: * For YC gas/electric only. ** For TC and TE Cooling and Electric Heat units only. RT-SVX34C-EN...
  • Page 88 Startup Table 39. Component Static Pressure Drops in. wg (I-P)—50 Hz Heating System Filters Throw- MERV14 Gas Heat Electric Heat ID Coil away MERV 8 High Eff. High Eff Nominal Inlet Std Tons Guide (kW) Std Air High Element Element 2”...
  • Page 89 Startup Table 40. Component Static Pressure Drops Pa (SI)—50 Hz Heating System Filters MERV1 Throw- MERV 8 High 4 High Gas Heat Electric Heat ID Coil away Eff. Nominal Inlet Std Tons Guide (kW) Std Air High Element Element Adder 50 mm Vanes Economizer 3150...
  • Page 90: Exhaust Fan Operation

    Startup Table 41. Supply Air Fan Drive Selections - 50 Hz 7.5 hp (5.6 kW) 10 hp (7.5 kW) 15 hp (10 kW) 20 hp (15 kW) Nominal Tons (kW) Drive No Drive No Drive No Drive No — — —...
  • Page 91 Startup Verify that the fans are operating properly and the CFM is within the job specifications. Refer to power exhaust fan performance tables beginning with Table 42, p. 92 for the exhaust fan performance characteristics. Available power adjustments: 1. The power exhaust fan(s) comes on based on the position of the of the exhaust fan setpoint potentiometer on the RTOM (Reliatel Options Module).
  • Page 92 Startup Table 42. Power Exhaust Fan Performance—27.5-35 Ton—60 Hz Power Exhaust Selection 50% (min) 100% (max) Damper Blade Open Distance (in) 1.5 (min) 4.0 (max) 1.5 (min) 4.0 (max) Return Duct Static (in. wc) 3812 6866 7624 13742 3497 5296 6995 10591 3190...
  • Page 93 Startup Table 45. Power Exhaust Fan Performance—33.3 - 41.7 Ton—50 Hz Power Exhaust Selection 50% (min) 100% (max) Damper Blade Open Distance (mm) 38.1 (min) 101.6 (max) 38.1 (min) 101.6 (max) Return Duct Static (Pa) 1909 3160 3818 6321 24.9 1800 2915 3599...
  • Page 94: Economizer Damper Adjustment

    Startup Figure 49. (Downflow) Standard Exhaust Maximum Damper Position More Exhaust Less Exhaust Figure 50. (Horizontal) Standard Exhaust Maximum Damper Position Less Exhaust More Exhaust Economizer Damper Adjustment Economizer (O/A) Dampers Arbitrarily adjusting the outside air dampers to open fully when the return air dampers are fully closed can overload the supply fan motor or deliver higher CFM to the space than designed.
  • Page 95 Startup 3. Add the measured return duct static pressure and the return air damper pressure drop together to obtain the Total Return Static Pressure. Apply this calculation and the calculated CFM to the appropriate Table 46, p. 95 through Table 49, p. 4.
  • Page 96 Startup Table 48. 40 - 50 Ton Downflow Unit Economizer (O/A) Damper Static Pressure Setup Return Air Duct Static + Return Air Damper Static System Design (Inches of Water) 0.20 0.40 0.60 0.80 1.00 1.20 1.40 Drive Rod Position 12000 12500 13000 13500...
  • Page 97: Manual Fresh Air Damper

    Startup Figure 51. Economizer (O/A) damper assembly Manual Fresh Air Damper Units ordered with the 25% manual fresh air option have two slidable dampers. By adjusting one or both, the desired amount of fresh air entering the system can be obtained. To adjust the fresh air damper;...
  • Page 98: Starting The Compressor

    Startup 6. With the supply fan "On" and rotating in the proper direction, measure the return duct static pressure. 7. Using the Table below, enter the desired amount of fresh air and the return air static pressure reading to obtain the proper damper opening dimension. Table 50.
  • Page 99: Starting 40 To 50 Ton Units

    Startup rotation. Refer to the unit wiring schematic and/or wire color markers vs. the compressor terminal block color markers. Figure 52. Economizer (O/A) damper assembly If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed.
  • Page 100 Startup Figure 53. Line Weight Locations—50 Ton Figure 54. Line Weight Locations—40 Ton RT-SVX34C-EN...
  • Page 101: Compressor Oil

    Startup Compressor Oil Once all of the compressors have been started, verify that the oil level is visible through the sight glass or above the sight glass. Use appropriate lighting (flash light) to verify the presence of oil. A tandem manifold set may have different oil heights, but still must be visible in the sight glass or above the sight glass.
  • Page 102 Startup Table 52. 30 Ton—Operating Pressure (60 Hz) TC, TE, YC* 36 0 FULL LOAD 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient 3 50 75 F OD Ambient...
  • Page 103 Startup Table 54. 40 Ton Dual Circuit—Operating Pressure (60 Hz) TC, TE , YC* 4 80 Circuit # 1 Full Load 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient...
  • Page 104 Startup Table 56. 50 Ton Dual Circuit—Operating Pressures (60 Hz) TC, TE, Y C* 600 Circ uit # 1 FULL LO AD 115 F OD Ambient 105 F OD Ambient 95 F OD Ambient 85 F OD Ambient 75 F OD Ambient 65 F OD Ambient 55 F OD Ambient 11 0...
  • Page 105 Startup Table 58. 22.9 Ton—Operating Pressure (50 Hz) TC, TE, YC* 27 5 FULL LOAD 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient 3 50 75 F OD Ambient...
  • Page 106 Startup Table 60. 29.2 Ton—Operating Pressures (50 Hz) TC, TE, YC* 35 0 FULL LOAD 7 00 6 50 6 00 5 50 115 F OD Ambient 5 00 105 F OD Ambient 4 50 95 F OD Ambient 4 00 85 F OD Ambient 3 50 75 F OD Ambient...
  • Page 107 Startup Table 62. 33.3 Ton Dual Circuit—Operating Pressure (50 Hz) TC, TE , YC* 4 00 Circuit # 2 Full Load 4 200 3 700 46.1 F OD Ambient 40.6 F OD Ambient 3 200 35.0 F OD Ambient 2 700 29.4 F OD Ambient 23.9 F OD Ambient 2 200...
  • Page 108: Scroll Compressor Operational Noises

    Startup Table 64. 41.7 Ton Dual Circuit—Operating Pressures (50 Hz) TC, TE , YC* 5 00 Circuit # 2 Full Load 4 200 3 700 46.1 F OD Ambient 40.6 F OD Ambient 3 200 35.0 F OD Ambient 2 700 29.
  • Page 109: Charging By Subcooling

    R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components could result in equipment or components exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
  • Page 110: Electric Heat Units

    Startup WARNING Hazardous Gases and Flammable Vapors! Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual.
  • Page 111: Final Unit Checkout

    Startup Final Unit Checkout After completing all of the checkout and startup procedures outlined in the previous sections (i.e., operating the unit in each of its modes through all available stages of cooling and heating), perform these final checks before leaving the unit: •...
  • Page 112: Sequence Of Operation

    For 40-50 ton Voyager Commercial units the reheat circuit is circuit# 2. For 27.5-35 ton Voyager Commercial units there is only one circuit.
  • Page 113: Units Without An Economizer

    Sequence of Operation Units without an Economizer For 27.5 to 35 Ton units, when mechanical cooling is required, the RTRM energizes the Compressor Contactor (CC1) coil. When the CC1 contacts close, the Compressor CPR1 and Outdoor Fan Motor (ODM1) will start providing the 3 minute "off" time has elapsed. ODM2 and ODM3 cycles off/on based on the outdoor ambient temperature as measured by the Outdoor Air Sensor (OAS).
  • Page 114: Economizer Operation Based On Reference Enthalpy

    Sequence of Operation one stop on each side of each damper. The practical range of blade position control is between 1.5" and 4.0" blade opening. The damper is wide-open at 4.0". The stops on each side of a damper must be in the same position, such that the damper blade connecting member contacts the stops at the same time.
  • Page 115: Gas Heat Sequence Of Operation

    Sequence of Operation applications). The ECA modulates the economizer dampers from minimum position to fully open based on a 1.5° F control point below either the space temperature setpoint for constant volume applications or 1.5° F around the supply air temperature setpoint for variable air volume applications.
  • Page 116: Electric Heat Sequence Of Operation

    Sequence of Operation Ignition Control Module There is a green LED located on the ignition module. Any time the Ignition module is powered, the LED will be on to provide status of the ignition system. • Steady OFF - no power/ internal failure •...
  • Page 117: Low Pressure Control (Lpc) Sequence Of Operation (Reliatel Control)

    Sequence of Operation Low Pressure Control (LPC) Sequence of Operation (ReliaTel Control) When the LPC is opened for one (1) continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of three (3) minutes. If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communicated to ICSTM if applicable, and a manual reset will be required to restart the compressor.
  • Page 118: Maintenance

    Maintenance Fan Belt Adjustment The Supply Fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. When installing new belts, do not stretch them over the sheaves;...
  • Page 119 Maintenance Table 65. Supply Fan Sheave and Belt Table (a)(b)(c) )(d) )(e) Fan Sheave Fan Bushing Motor Sheave Motor Bushing Tons Motor RPM Browning Browning Browning Browning Belt BX108 BK190 X 1 7/16 BK190-1-7/16 BK62H BK62H H 1-3/8 H-1-3/8 Notched BX100 BK160 X 1 7/16 BK160-1-7/16 BK57H...
  • Page 120: Monthly Maintenance

    Maintenance Monthly Maintenance WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
  • Page 121 Maintenance Table 67. Deflection Force Deflection Force (Lbs.) Belts Super Gripbelts Gripnotch Steel Cable Gripbelts Cross Small P.D Section Range Min. Max. Min. Max. Min. Max. 3.0 -3.6 4 1/2 3 7/8 5 1/2 3 1/4 3.8 - 4.8 3 1/2 4 1/2 6 1/4 3 3/4...
  • Page 122: Heating Season

    Maintenance • compressor suction and discharge pressures (each circuit); • superheat and subcooling (each circuit); Record this data on an “operator’s maintenance log” like the one shown in Table 31. If operating pressures indicate a refrigerant shortage, measure the system superheat and system subcooling. For guidelines, refer to "Charging by Subcooling".
  • Page 123: Coil Cleaning

    Be sure to follow these instructions as closely as possible to avoid damaging the coils. To clean refrigerant coils, use a soft brush and a sprayer. Contact the local Trane Parts Center for appropriate detergents.
  • Page 124: Fall Restraint

    Maintenance 4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability. 5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used: a.
  • Page 125: Refrigeration System

    R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components could result in equipment or components exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
  • Page 126: Compressor Replacements

    Maintenance If a motor burn out has occurred, change the oil in both compressors in a tandem set. This will require that the oil equalizer tube be removed to suck the oil out of the oil sump. A catch pan must be used to catch the oil when the compressor oil equalizer line is loosened.
  • Page 127 Maintenance Table 70. Compressor Models/Restrictor Locations Restrictor Location Model Compressor Compressor Compressor T**/Y** CPR3 CPR2 CPR1 CPR3 CPR2 CPR1 CSHD142 CSHD161 CSHD161 CSHD184 CSHD155 CSHD183 CSHD161 Figure 60. Compressors Table 71. Sample Operator’s Maintenance Log (see note) Refrigerant Circuit #1 Refrigerant Circuit #2 Current Ambien...
  • Page 128: Diagnostics

    Diagnostics The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information. Before turning the main power disconnect switch "Off", follow the steps below to check the Unit Control. All diagnostics and system status information stored in the RTRM will be lost when the main power is turned "Off".
  • Page 129: Terminal Locations

    Diagnostics Terminal locations System Status / Diagnostics checkout procedure (DC volt meter required) The method described below to determine unit status or to see if diagnostics are present assumes the Zone Sensor or NSB panel is not within sight or close by or is not being used. If a zone sensor is within sight however, DC readings need not be taken - just look at the LED or display and go to STEP 3.
  • Page 130: Diagnostics (Cv Units Only)

    Diagnostics (see DIAGNOSTICS section). Note: Diagnostics for CV or VAV units are listed separately. The same diagnostic may have a different meaning depending on whether the unit has VAV controls or CV controls. Diagnostics (CV units only) If only one diagnostic is present, refer to that diagnostic listing below. If more than one diagnostic is present, refer to combination diagnostics such as COOL + HEAT as appropriate.
  • Page 131: Diagnostics (Vav Only)

    Diagnostics Diagnostics (VAV only) If only one diagnostic is present, refer to that diagnostic. If more than one diagnostic is present, refer to combination diagnostics such as COOL + HEAT as appropriate. On a BAYSENS119*, the display will show HEAT FAIL or COOL FAIL or SERVICE (or an appropriate combination) if a diagnostic is present.
  • Page 132: Zone Temperature Sensor (Zsm) Service Indicator

    Diagnostics Method 1 To reset the system from the space, turn the "Mode" selection switch at the zone sensor to the "Off" position. After approximately 30 seconds, turn the "Mode" selection switch to the desired mode, i.e. Heat, Cool or Auto. Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch "Off"...
  • Page 133: Test 1

    Diagnostics Test 1 Zone Temperature Thermistor (ZTEMP) This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. The following are some typical indoor temperatures, and corresponding resistive values. Table 73. Resistance Values Zone or Set Nominal ZTEMP Nominal CSP or HSP...
  • Page 134: Test 4

    Diagnostics Test 4 LED indicator test, (SYS ON, HEAT, COOL & SERVICE). Method 1 Testing the LED using a meter with diode test function. Test both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an Over Load, or open circuit indication if LED is functional.
  • Page 135 Diagnostics Table 75. Constant Volume Defaults Component or Function Default Operation Cooling Setpoint (CSP) 74° F Heating Setpoint (HSP) Economizer 71° F Normal Operation Economizer Minimum Position Normal Operation Mode Normal operation, or auto if ZSM mode switch has failed Normal operation, or continuous if fan mode switch on ZSM has failed Night Setback Mode Disabled - Used with Integrated Comfort™...
  • Page 136: Test 1

    Diagnostics 6 Flashes: OA Humidity Sensor out of range 7 Flashes: OA Temp Sensor out of range 8 Flashes: MA Temp Sensor out of range 9-11 Flashes: Internal ECA failure Note: The Outdoor Air Sensor (OAS) is also used for the economizer operation. It is connected to the RTRM.
  • Page 137: Test 2

    Diagnostics Note: If voltage is incorrect, verify RTAM DIP switch settings. 2. If the voltage to the IGV/VFD is not present, verify that the wires are properly connected between the RTRM or COMM (Communications Module) and the RTAM. If Step 2 checks out and the voltage is still not present at the IGV/VFD output, replace the RTAM. Test 2 Testing the Static Pressure Transducer (SPT) Input 1.
  • Page 138: Compressor-Blink Codes

    Diagnostics Test 5 Testing the VFD 1. Verify that the keypad in control box is powered. If not, check the power wires to the VFD and the Keypad cable. 2. Using the "Step Test Mode", procedure described in the "Unit Startup" section (Step 3 for VAV). Verify that the fan starts and the speed increases until the SA Pressure reaches the "Setpoint"...
  • Page 139 Diagnostics Table 77. Troubleshooting SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. No power to the Unit. 1. Check line voltage at service disconnect. 2. No power to the RTRM. 2. Check for 24 VAC at RTRM J1-1 to system ground. 3. Zone Sensor Module (ZSM) is 3.
  • Page 140 Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. No power to CC1 coil. Possible 1. Check wiring, terminals and applicable controls Cool Failure (CCB1, HPC1, TDL1, WTL1, LPC1) 2. CC1 coil defective. Cool Failure 2. Check CC1 coil. If open or shorted, replace CC1. Indicated.
  • Page 141 Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. CFM has failed. 1. Check CFM, replace if necessary. 2. Disconnect BROWN wires from capacitor, test, and 2. CFM capacitor has failed. replace if necessary. 3. Check wiring, and terminals. Repair, or replace if J.
  • Page 142 Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. Check for 24 VAC at AH, BH,CH, and DH contactor 1. Heater contactor(s) have coils. If 24 VAC is present on a call for heat, and the failed. contacts do not close, the contactor has failed. 2.
  • Page 143 Diagnostics Table 77. Troubleshooting (continued) SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION 1. Check the return air sensor (RAS) at connector P10 by disconnecting P10 from RAT on the ECA. Check for resistance between P10-1 and P10-2, refer to the 1. Comparative enthalpy setup, Resistance versus Temperature Chart.
  • Page 144 Diagnostics Table 78. Component Failure Mode COMPONENT FAILURE RESPONSE NORMAL RANGE DIAGNOSTIC 4 to 20 mA Check at ECA ECA 3 flashes. (RHS) Return Humidity 1. Economizer operates using 10 to 90% RH Honeywell RAH-1 and RAH-2 by Sensor Referance Enthalpy. C7600A.
  • Page 145 Diagnostics Table 78. Component Failure Mode COMPONENT FAILURE RESPONSE NORMAL RANGE DIAGNOSTIC This input is for "indication only "Normal operation = 0 VAC SERVICE LED ON 2-30 VDC (CFS) Clogged Filter and does not effect the normal measured between terminals present at RTRM J6-6 and J6- Switch operation of the unit.
  • Page 146: Tr-1 And Tr-200 Vfd Programming Parameters

    ] buttons. When the desired selection has been made, press the OK button. Should replacing the a VFD become necessary, the replacement is not configured with all of Trane's operating parameters. The VFD must be programmed before attempting to operate the unit.
  • Page 147 Diagnostics g. Press [OK] ►◄ h. To move to a different digit within a parameter setting, use the [ ] buttons (Highlighted area indicates digit selected for change) ▲ ▼ i. Use [ ] and [ ] buttons to adjust the digit j.
  • Page 148: Unit Wiring Diagram Numbers

    Unit Wiring Diagram Numbers Table 81. Unit Wiring Diagram Numbers Diagram No. Descriptions 2313-0601 Power Schematic (208V-575V) 2313-0700 Heat Power and Controls Schematic - Low Heat Gas Unit 2313-0701 Heat Power and Controls Schematic - High Heat Gas Unit 2313-0605 Heat Power and Controls Schematic - Low Heat Modulating Gas Unit 2313-0702 Heat Power and Controls Schematic - High Heat Modulating Gas Unit...
  • Page 149 Unit Wiring Diagram Numbers Table 81. Unit Wiring Diagram Numbers Diagram No. Descriptions 2313-0654 Control Box Connection Print - 27.5-35T, VAV, 36KW-54KW Electric Heat 208-230V 2313-0655 Control Box Connection Print - 27.5-35T, VAV, 36KW-54KW Electric Heat 380-575V 2313-0656 Control Box Connection Print - 40T, VAV, 54KW Electric Heat 208-230V 2313-0657 Control Box Connection Print - 40T, VAV, 54KW Electric Heat 380-575V 2313-0658...
  • Page 150: Warranty And Liability Clause

    COMMERCIAL EQUIPMENT RATED 20 TONS AND LARGER AND RELATED ACCESSORIES PRODUCTS COVERED - This warranty* is extended by Trane Inc. and applies only to commercial equipment rated 20 Tons and larger and related accessories. The Company warrants for a period of 12 months from initial startup or 18 months from date of...
  • Page 152 HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Produced with paper that uses fewer trees ©...

Table of Contents