Unit Dimensions - Trane YSC037E Installation & Operation Manual

Packaged rooftop air conditioners precedent — gas/electric 3 to 10tons – 60 hz
Table of Contents

Advertisement

Unit Dimensions

Figure 1, p. 15
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation.These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged
unit capacity, and peak operating efficiency.
Figure 1.
Typical installation clearances for single & multiple unit applications
YSC036-060E & YHC036E, YHC037E Units
RT-SVX21P-EN
Providing less than the recommended clearances may
result in condenser coil starvation, "short-circuiting" of
exhaust and economizer airflows, or recirculation of hot
condenser air.
YSC072-120F, YHC048-102F, YHC047-120E Units
15